39
9 Annex
>>
9.1 Screw and bolt
connections
The following elements must be
used for all metal screw couplings:
- Screws and bolts:
Grade ≥ 8.8,
- Nuts:
Grade 8.
Important!
Screw connections must
not be greased.
Thread
Tightening torque
size
[Nm]
min.
max.
M6
7
9
M8
16
24
M10
36
44
M12
63
77
M16
153
187
M20
297
363
Table 1:
Hex. bolts and machine screws
(except slotted screws) and nuts
without ratchet toothing.
Thread
Tightening torque
size
[Nm]
min.
max.
M6
12.5
15.5
M8
32
40
M10
65
79
M12
90
110
M16
243
297
Table 2:
Screws and nuts with ratchet
toothing.
9.2 Auxiliary products
The auxiliary products are available
from the manufacturer.
Warning!
Risk of injury if the
auxiliary products are
handled improperly.
Comply with the safety data
sheets of the auxiliary products.
Ref.
Cleaning agent
1 l can S 008 152
Lubricant KL ;
0.5 kg can ST 312-111-835
Liquid
lubricant FL ;
0.5 l can S 008 153
The use of other auxiliary products is
not admissible
9.3 Accessories
Ref.
Crank (for circuit-
breaker, disconnector,
earthing switch,
busbar earthing
switch) AGS C54 850-01
Double-bit
key AGS 434 101-01
Lever for make-
proof earthing
switch on busbar
end AGS 410 210-01
If equipped with IVIS:
Phase monitor
MS 100 AGS C26 320-01
Constant-voltage
indicator:
Manuf. Horstmann S 065 081
Manuf. Pfisterer S 065 860
Содержание WI
Страница 34: ...34 Fig 8 4 Disconnector and earthing switch drive points of lubrication of bus sectionalizer analogously ...
Страница 40: ...40 Notes ...