26
Earthing a busbar section by
means of the bus section coupler
Illustrated: Earthing the left-hand
busbar section
Initial position: bus section coupler
“OFF“
1. Switch on disconnector of left-
hand busbar section (circuit-
breaker panel)
2. Switch on earthing switch in the
busbar riser panel (right-hand
panel). The circuit-breaker is
switched ON automatically.
For earthing the right-hand busbar
section, proceed analogously.
Fig. 5.27
Bus section coupler
“OFF“
Fig. 5.28
Bus section coupler:
left-hand busbar section
“EARTHED”
left-hand
panel
right-hand
panel
left-hand
panel
right-hand
panel
Earthing the busbar by means of
an outgoing feeder via its circuit-
breaker
Initial position:
Feeder EARTHED
1. Remove cable and connect eart-
hing device
2. Switch off earthing switch
The circuit-breaker is first
switched off automatically.
3. Switch on disconnnector
4. Switch on circuit-breaker
Fig. 5.25
Feeder “EARTHED”
Fig. 5.26
Busbar “EARTHED”
Содержание WI
Страница 34: ...34 Fig 8 4 Disconnector and earthing switch drive points of lubrication of bus sectionalizer analogously ...
Страница 40: ...40 Notes ...
Страница 41: ...41 Notes ...
Страница 42: ...42 Notes ...
Страница 43: ......