Model HF65R                                                                                                        7 

WATER HEATING COIL (MODEL SHW4) 

 
ARDENT ENERGY heating units are designed to heat your do-
mestic hot water during the heating season. 
 
The HF65 can accept one or two coils (1 per side). The coil re-
places all but one of the firebrick on the side located. 
 

Procedure: 

NOTE:

      Ensure installation complies with local 

plumbing codes. 

 

1.      Remove both side shrouds by unscrewing 4 or 6 

screws at back 

2.      Remove rear heat shield and hammer out the 2 

knockouts on the side desired. (see Fig 5) 

3.      Loosen cross draft angle nuts on side of unit. (2 

each side located on outside of firebox). 

4.      Remove brick from that side. 
5.      Punch out 2 knockouts at back of stove. Reach in 

through punched out holes with a bar extension 
and punch out knockouts in primary heat ex-
changer. Knock outs are out of necessity tight. A 
sharp blow with a heavy hammer will be required. 

6.      Position water coil in stove, replace brick and 

tighten cross draft angle nuts on side of heater to 
hold coil in place. 

7.      Install mineral wool gasket and plate on outside 

and screw tight. 

8.

Replace shrouds and heat shield. 

 

TANK CONNECTION 

 
It is recommended that the ‘2 tank” system be used. The first 
tank or “Range Boiler” must remain un-insulated to dissipate any 
excess heat generated by the hot water coil. 
 
Connection of piping to Range Boiler must be strictly followed as 
shown in the Diagram. The 2 shut—off valves must be no smaller 
than 3/4 inch GATE valves. Make certain that the PRV (Watts 3L) 
and P&TRV (Watts 100XL) are installed in their respective loca-
tions and not vice versa. Maximum pressure setting is 150 psi. 
Do not use less than 3/4 inch diameter standard pipe between 
range boiler and heater, orientation of pipe must be slightly uphill 
from the coil outlet to the upper connection at the tank, otherwise 
vapor lock will occur and water will not circulate. Min. Range 
Boiler recommended is 30 Imperial gallon capacity.  

 

FIG. 6 

REPLACEMENT PARTS LIST

 

ITEM  QTY  DESCRIPTION 

PART # 

Closer pawl 

6261 

Hug lock nut 

1442 

Scandinavian baffle 

AP014 

Bypass damper 

A237R4 

Fin 

AP038 

Outside fin 

A407R4 

28” 

Ball chain 

6110 

7-A 

Chain pendant 

6121 

Flame deflector 

A533R1 

Down draft baffle 

A532R3 

10 

Cross draft angle 

A217R8 

11 

Air inlet assembly 

6411 

12 

Primary air heat exchange assembly  A900R0 

13 

14 

Firebrick 1  1/4 x 4 1/2 x 9 

7101 

14 

Door sill 

A259R2 

15 

Door hinge 

6260 

16 

60” 

Door gasket 5/8  dia. glass  rope 

7006 

17 

Door liner 

A302R1 

18 

Door assembly 

A317R3 

19 

Door handle 3/8 ID 

6010 

20 

Door  closer assembly 

6201-1 

21 

Door  closer  catch 

A280R1 

22 

Control handle 5/16 ID 

6005 

23 

Bypass  bar 

A264R10 

24 

Draft  control rod assembly 

A168R15 

25 

Bypass lever 

A239R10 

Содержание HF65R

Страница 1: ...Model HF65R SOLID FUEL SPACE HEATER Box 3637 Smithers BC V0J 2N0 INSTALLATION AND OPERATION INSTRUCTION MANUAL PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE Operation Maintenance Installation...

Страница 2: ...f your heater should be included with your order to assure prompt and accurate service We congratulate you on your choice of the ARDENT ENERGY heating system and may your home fires keep burning Yours...

Страница 3: ...the event of an uncontrolled chimney fire shut the bypass damper and turn down the draft damper com pletely On thermostat models turn down thermo stat If chimney fire does not die down keep a watch o...

Страница 4: ...temperature desired When warming up a cold room there will be an initial temperature overrun then the temperature will stabilize RELOADING 1 Have wood on hand to load firebox 2 Open bypass lever for 3...

Страница 5: ...ng over the exact center of the flue of the stove and mark a spot on the ceiling to indicate the center of the chimney 3 Check that the intended location will not interfere with ceil ing joists or raf...

Страница 6: ...cifications CHIMNEY TERMINATION Chimneys are required to extend at least 915 mm 3 above the highest point where they pass through the roof of the building and at least 610 mm 2 higher than any portion...

Страница 7: ...he hot water coil Connection of piping to Range Boiler must be strictly followed as shown in the Diagram The 2 shut off valves must be no smaller than 3 4 inch GATE valves Make certain that the PRV Wa...

Страница 8: ...OUR MODEL AND SERIAL HERE FOR EASY REFERENCE WHEN ORDERING REPLACEMENT PARTS MODEL ____________________________________________ SERIAL I ___________________________________________ DATE OF INSTALLATIO...

Страница 9: ...e replaced or repaired upon return of the defective part to an au thorized Ardent Energy Ltd dealer 2 Any space heater or part thereof that is replaced or serviced during the three year warranty perio...

Отзывы: