Domestic Ventilation with Heat Recovery
KNX-LUNOS-CONTROL4
Subject to change
Arcus-EDS GmbH
www.arcus-eds.de
Rigaer Str. 88 10247 Berlin
[email protected]
Tel.: +49(0)30 25933914
Fax.: +49(0)30 25933915
682x-Lunos-Control-4F
V.13.09.2022
e1
Functional block lead humidity - KNX-Objects
IO
Name
Function
Datapoint type
14
Input
Indoor humidity
Input for indoor
humidity from
another KNX device
DPT 9.008
15
Input
Outdoor humidity
Input for outdoor
humidity from
another KNX device
DPT 9.008
16
Input
Lead Humidity
enable
The lead calculation
of the fan level
through the
humidity can be
deactivated with a
"0".
DPT 1.003
3.12 Functional block lead CO2
This functional block is only available if the CO2 lead function is
activated.
Functional block lead CO2 - Parameters
limits 1/2/3/4
700 .. 4000 ppm
When the switching point X is exceeded, fan level (X-1) is switched on, provided that it or a
higher one is not already active.To switch off, the level next to smaller levels must be fallen
below again.