3.10 Functional block lead temperature
This functional block is only available if the temperature lead function is
activated.
The dynamic cycle time is only active in expert mode.
Functional block Lead temperature - Parameters
Frost protection [°C]
5 .. 16
If the indoor temperature is below this temperature, the ventilation is completely switched
off to avoid frost damage at winter temperatures and a lack of heating
Temperature distance [°C]
0 .. 10
If the distance between the outdoor and indoor temperature is larger than this
temperature distance, the device tries to achieve the target temperature by switching
between summer mode and heat recovery.This supports both heating and cooling systems
in the transition period. A larger distance prevents conflicts with the control of the
heating/cooling circuit.
Behavior of locking control
Slave/Master
Behavior of the object "Lead temperature active"
Slave: Object is input and is blocked with a 0
Master: Object is output und locks the heating/cooling