2
nd
harmonic blocking pick-up
0.01…50.00 %, step 0.01 %, default 15.00 %
5
th
harmonic blocking pick-up
0.01…50.00 %, step 0.01 %, default 35.00 %
Inaccuracy:
- Differential current
- 2
nd
harmonic
±3.0 %ISET or ±75 mA (0.10…4.0 x ISET)
±1.5 %I
SIDE1
Instant operation time
Instant operation time >1.05 × I
SET
<40 ms (Harmonic blocking active)
Instant operation time >3.00 × I
SET
<30 ms (Harmonic blocking active)
Instant operation time >3.00 × I
SET
~15 ms (No harmonic blocking)
Reset
Reset ratio: differential current
97 % of the differential current setting (typically)
Reset time
<50 ms
No
Notte!
e!
• The harmonic current is set and calculated according to the highest amplitude of side 1, 2 or
3 currents (Ih%/I
SIDE1/2/3
). The harmonic current is calculated individually for each phase.
9.2.1.11 Arc fault protection (IArc>/I0Arc>; 50Arc/50NArc) (optional)
Table. 9.2.1.11 - 213. Technical data for the arc fault protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Residual current channel I
01
(Coarse)
Residual current channel I
02
(Fine)
Current input magnitudes
Sample-based phase current measurement
Sample-based residual current measurement
Arc point sensor inputs
Channels S1, S2, S3, S4 (pressure and light sensor, or light-only sensor)
Up to four (4) sensors per channel
System frequency operating range
6.00…75.00 Hz
Pick-up
Pick-up current setting (phase current)
Pick-up current setting (residual current)
Pick-up light intensity
0.50…40.00 × I
N
, setting step 0.01 × I
N
0.10…40.00 × I
N
, setting step 0.01 × I
N
8, 25 or 50 kLx (the sensor is selected in the order code)
Starting inaccuracy (IArc> and I0Arc>)
±3 % of the set pick-up value > 0.5 × I
N
setting. 5 mA < 0.5 × I
N
setting.
Point sensor detection radius
180 degrees
Operation time
Light only:
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 7 ms (3…12 ms)
Typically 10 ms (6.5…15 ms)
Light + current criteria (zone 1…4):
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 10 ms (6.5…14 ms)
Typically 14 ms (10…18 ms)
Arc BI only:
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 7 ms (2…12 ms)
Typically 10 ms (6.5…15 ms)
Reset
A
AQ
Q-T256
-T256
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00028
299