Name
Range
Step
Default
Description
Delay
characteristics
IEC
0: NI
1: EI
2: VI
3: LTI
4: Param
-
0: NI
Selects the IEC standard delay characteristics.
The options include the following: Normally Inverse ("NI"),
Extremely Inverse ("EI"), Very Inverse ("VI") and Long Time Inverse
("LTI") characteristics. Additionally, the "Param" option allows the
tuning of the constants A and B which then allows the setting of
characteristics following the same formula as the IEC curves
mentioned here.
This setting is active and visible when the "Delay type" parameter is
set to "IDMT" and the "Delay curve series" parameter is set to "IEC".
Delay
characteristics
IEEE
0: ANSI NI
1: ANSI VI
2: ANSI EI
3: ANSI LTI
4: IEEE MI
5: IEEE VI
6: IEEE EI
7: Param
-
0: ANSI
NI
Selects the IEEE and ANSI standard delay characteristics.
The options for ANSI include the following: Normal Inverse ("ANSI
NI"), Very Inverse ("ANSI VI"), Extremely inverse ("ANSI EI"), Long
time inverse ("ANSI LTI") characteristics. IEEE: Moderately Inverse
("IEEE MI"), Very Inverse ("IEEE VI"), Extremely Inverse ("IEEE EI")
characteristics. Additionally, the "Param" option allows the tuning of
the constants A, B and C which then allows the setting of
characteristics following the same formula as the IEEE curves
mentioned here.
This setting is active and visible when the "Delay type" parameter is
set to "IDMT" and the "Delay curve series" parameter is set to
"IEEE".
Time dial
setting k
0.01…25.00s
0.01s
0.05s
Defines the time dial/multiplier setting for IDMT characteristics.
This setting is active and visible when the "Delay type" parameter is
set to "IDMT".
A
0.0000…250.0000 0.0001 0.0860
Defines the Constant A for IEC/IEEE characteristics.
This setting is active and visible when the "Delay type" parameter is
set to "IDMT" and the "Delay characteristic" parameter is set to
"Param".
B
0.0000…5.0000
0.0001 0.1850
Defines the Constant B for IEC/IEEE characteristics.
This setting is active and visible when the "Delay type" parameter is
set to "IDMT" and the "Delay characteristic" parameter is set to
"Param".
C
0.0000…250.0000 0.0001 0.0200
Defines the Constant C for IEEE characteristics.
This setting is active and visible when the "Delay type" parameter is
set to "IDMT" and the "Delay characteristic" parameter is set to
"Param".
A
AQ
Q-F201
-F201
Instruction manual
Version: 2.04
70
Содержание AQ-F201
Страница 1: ...AQ F201 Overcurrent and Earth fault relay Instruction manual ...
Страница 220: ...Figure 7 4 146 Example block scheme A AQ Q F201 F201 Instruction manual Version 2 04 219 ...
Страница 226: ...Figure 8 4 151 Device installation A AQ Q F201 F201 Instruction manual Version 2 04 225 ...
Страница 227: ...Figure 8 4 152 Panel cutout dimensions and device spacing A AQ Q F201 F201 Instruction manual Version 2 04 226 ...