Impulse voltage test
EN 60255-27, IEC 60255-5
5 kV, 1.2/50 µs, 0.5 J
Physical environment compatibility
Table. 9.3 - 169. Mechanical tests.
Vibration test
EN 60255-1, EN 60255-27, IEC 60255-21-1 Class 1
2…13.2 Hz, ± 3.5 mm
13.2…100 Hz, ± 1.0 g
Shock and bump test
EN 60255-1,EN 60255-27, IEC 60255-21-2 Class 1
20 g, 1 000 bumps/direction.
Table. 9.3 - 170. Environmental tests.
Damp heat (cyclic)
EN 60255-1, IEC 60068-2-30
Operational: +25…+55 °C, 93…97 % (RH), 12+12h
Dry heat
EN 60255-1, IEC 60068-2-2
Storage: +70 °C, 16 h
Operational: +55 °C, 16 h
Cold test
EN 60255-1, IEC 60068-2-1
Storage: –40 °C, 16 h
Operational: –20 °C, 16 h
Table. 9.3 - 171. Environmental conditions.
IP classes
Casing protection class
IP54 (front)
IP21 (rear)
Temperature ranges
Ambient service temperature range
–35…+70 °C
Transport and storage temperature range
–40…+70 °C
Other
Altitude
<2000 m
Overvoltage category
III
Pollution degree
2
Casing and package
Table. 9.3 - 172. Dimensions and weight.
Without packaging (net)
Dimensions
Height: 117 mm (4U)
Width: 127 mm (¼ rack)
Depth: 174 mm (no cards & connectors)
Weight
1.5 kg
A
AQ
Q-F201
-F201
Instruction manual
Version: 2.04
241
Содержание AQ-F201
Страница 1: ...AQ F201 Overcurrent and Earth fault relay Instruction manual ...
Страница 220: ...Figure 7 4 146 Example block scheme A AQ Q F201 F201 Instruction manual Version 2 04 219 ...
Страница 226: ...Figure 8 4 151 Device installation A AQ Q F201 F201 Instruction manual Version 2 04 225 ...
Страница 227: ...Figure 8 4 152 Panel cutout dimensions and device spacing A AQ Q F201 F201 Instruction manual Version 2 04 226 ...