11 Technical data
11.1 Mounting and installation
Table. 11.1 - 7. Technical data for relay mounting and installation.
Panel:
- material
- thickness (min...max)
metal
1.0...5.0 mm (0.04...0.20 in)
Panel mounting:
- screw type
- key size
- tightening torque (min...max)
ISO 14581 M4x12, galvanized
Torx T20
1.5...2.0 N·m (13.3...17.7 lbf·in)
Grounding:
- nut type
- key size
- tightening torque (min...max)
DIN934-M5 galvanized
8
2.5...3.0 N·m (22.1...26.6 lbf·in)
Connectors X1 and X2:
- connector type
- wire cross section (min...max)
- minimum stripping length
- screw tightening torque (min...max)
Phoenix Contact MSTB 2,5/15-ST-5,08 BD:1-15
0.2...2.5 mm
2
(24...13 AWG)
7 mm (0.28 in)
0.5...0.6 N·m (4.4...5.3 lbf·in)
Connector X3:
- connector type
- wire cross section (min...max)
- minimum stripping length
Phoenix Contact DFMC 1,5/6-STF-3,5
0.2...1.5 mm
2
(24...16 AWG)
10 mm (0.39 in)
11.2 Operating times
Table. 11.2 - 8. Technical data for relay operating times.
Trip time using mechanical trip relays
7 ms*
Reset time (arc light stage)
2 ms
*) The total trip time when using both the arc light (L>) or phase/residual overcurrent (I>) from an
AQ-110 unit and the arc light (L>) from this unit.
11.3 Auxiliary voltage
Table. 11.3 - 9. Technical data for the relay auxiliary voltage (Uaux).
Auxiliary power supply
92…265 V AC/DC
18…72 V DC (optional)
Maximum interruption
100 ms
Maximum power consumption
5 W, < 10 m
Ω
Standby current
90 mA