7.2 Circuit breaker failure protection
All AQ-101 variants include a selective circuit breaker failure (CBFP) function, which can be enabled
through the DIP switch settings (please refer to the "DIP switch settings" chapter for more information).
When enabled, the CBFP function activates when the tripped breaker fails to operate, or if the unit
detects the presence of light after a set operating time. Please note that if the unit is set to operate on
both arc light and overcurrent, both conditions must persist to activate the CBFP function. The CBFP
function can be set to operate either on a 100-ms or a 150-ms delay (again, please refer to the "DIP
switch settings" chapter for more information).