Par.
11.4.3
Filling flowmeter
This menu is only visible when the filling flowmeter is selected as tank level source (basic settings, chap. 10).
The filling flowmeter allows displaying the tank filling data in real time.
Enter the values for the filling flowmeter installed on the system: the following table indicates the values which will be set automatically by selecting
the corresponding flowmeter code.
If the installed filling flowmeter is not displayed, select
Other
and enter the relevant values.
ORION FLOWMETERS
WOLF FLOWMETERS
Type
Constant Minimum
flowrate
Maximum
flowrate
Type
Constant Minimum
flowrate
Maximum
flowrate
pls/l pls/gal l/min GPM l/min GPM
pls/l pls/gal l/min GPM l/min GPM
462XXA4XXXX
300
1135
10
2.60 200 52.8
462x4xxx
250
946
10.0 2.6
200 52.8
4622XA5XXXX
150
568
20
5.30 400 105.7
462x5xxx
132
500
20.0 5.3
400 105.7
4622XA6XXXX
100
378
30
7.90 600 158.5
462x7xxx
60
227
40.0 10.6 800 211.3
Other
625 2366
10
2.60 200 52.8
The filling flowmeter allows displaying the tank filling data in real time.
Enter the values for the filling flowmeter installed on the system: the following table indicates the values which will be set automatically by selecting
the corresponding flowmeter code.
If the installed filling flowmeter is not displayed, select
Other
and enter the relevant values.
ORION FLOWMETERS
WOLF FLOWMETERS
Type
Constant Minimum
flowrate
Maximum
flowrate
Type
Constant Minimum
flowrate
Maximum
flowrate
pls/l pls/gal l/min GPM l/min GPM
pls/l pls/gal l/min GPM l/min GPM
462XXA4XXXX
300
1135
10
2.60 200 52.8
462x4xxx
250
946
10.0 2.6
200 52.8
4622XA5XXXX
150
568
20
5.30 400 105.7
462x5xxx
132
500
20.0 5.3
400 105.7
4622XA6XXXX
100
378
30
7.90 600 158.5
462x7xxx
60
227
40.0 10.6 800 211.3
Other
625 2366
10
2.60 200 52.8
• Type
Indicate the type of flowmeter installed.
• Constant:
Indicate the constant of the installed filling flowmeter.
• Minimum flowrate
• Maximum flowrate
The items
Minimum flowrate
and
Maximum flowrate
can be modified only when the option
Other
is enabled.
Indicate the minimum and maximum pressure for the filling flowmeter installed on the system.
ADVANCED SETTINGS
"IMPLEMENT"