VP5000-DC/DC60, VP5000-DC/DC200-HL
Product description
Last edited 2019-02-08
by Sonja Scheunert
Filename
VP5000_DCDC60_200-HL_installation_manual_v1-4en.docx
42 / 173
Power connections
3.6
The dimensions of the power connections are given in the following tables for the respective
VECTOPOWERs.
3.6.1
VECTOPOWER VP5000-DC/DC60
The VECTOPOWER is supplied without EMC cable glands.
ARADEX can help you design the wire cross-sections and offers you a connection set configured
for your application.
EMC cable glands from Pflitsch of the blueglobe TRI type must be used. These EMC cable glands
provide electromagnetic compatibility and the IP protection class.
The external diameter of the selected wire must be within the sealing area of the EMC cable gland.
The diameter of the cable shield must also be within the shield diameter of the EMC cable gland.
Check the specifications of Pflitsch for this. See chapter 3.6.4 Table of blueglobe TRI EMC cable
glands.
Connection
Recommended wire
cross-section* and
material
Thread for cable gland
Fastening thread of the
wire terminal
DC link [DC+/-]
50 mm² / 1 AWG Cu
M32
M8
Output [/-]
50 mm² / 1 AWG Cu
M32
M8
Ground wire
**
-/-
M8
* Recommended wire cross-section at 65 °C ambient temperature and 90 °C wire temperature
** See chapter 3.6.3 Wire cross-section of the ground wire acc. to EN 62477-1.
Table 20: Power connections for the VECTOPOWER VP5000-DC/DC60
3.6.2
VECTOPOWER VP5000-DC/DC200-HL
The VECTOPOWER is supplied without EMC cable glands.
ARADEX can help you design the wire cross-sections and offers you a connection set configured
for your application.
EMC cable glands from Pflitsch of the blueglobe TRI type must be used. These EMC cable glands
provide electromagnetic compatibility and the IP protection class.
The external diameter of the selected wire must be within the sealing area of the EMC cable gland.
The diameter of the cable shield must also be within the shield diameter of the EMC cable gland.
Check the specifications of Pflitsch for this. See chapter 3.6.4 Table of blueglobe TRI EMC cable
glands.