AT-MGS-408 User Manual

4. Operation

4.1.  Overview

4.1.1  Main Function

Every five seconds the AT-MGS-408 Gas Detection Controller collects gas concentration 

and status information from each connected gas detector. Gas concentration appears 

on the LCD display and connection status, fault and alarm conditions are indicated 

by the LED matrix for each channel. When an SD card is installed and data logging is 

enabled

 (see Section 4.4 on page 24)

, concentration and status information is logged 

every 10-seconds for all connected gas detectors. Detector data and controller status 

information can also be communicated via MODBUS, to a master or BMS device.

4.1.2  Power Up

After power up, the firmware revision level will be indicated on the LCD followed by 

an LED/LCD and beacon self test. The controller will then begin scanning connected 

detectors and display their reported gas concentration on the LCD and status 

information on the LED matrix.

4.1.3  Channel Number Keys

Pressing a Channel number key will bring up a scrollable channel detail screen with 

detector specific information. Pressing the channel number key a second time will 

access the channel setup menu.

4.1.4  Menu Access and Navigation

To access the System level menu: 

 

Main Menu

 

 

press 

OK

. The currently selected menu item is indicated with triangle 

pointers to the left and right of the description.

If the menu list is longer than can be displayed, up and down arrow keys on the 

right side of the screen will indicate additional items are available by either scrolling 

up or down.

Figure 4-3 - 

Main Menu

Содержание aquitron AT-MGS-408

Страница 1: ...INSTALLATION OPERATION INSTRUCTIONS AquiTron AT MGS 408 Gas Detection Controller...

Страница 2: ...able Appropriate Locations 10 3 4 Mounting the Gas Detection Controller 10 3 5 Electrical Wiring 11 3 6 Communications Connections 12 3 6 1 AT MGS 408 Gas Detection Controller Network 12 3 6 2 Integra...

Страница 3: ...irements 25 4 4 3 Data Logging Menu 25 MODBUS 27 5 1 MODBUS Overview 27 5 1 1 MASTER BAUD RATE 27 5 1 2 SLAVE NODE ADDRESS 27 5 1 3 SLAVE BAUD RATE 28 5 1 4 SLAVE PARITY 28 5 1 5 SLAVE STOP BIT 28 5 1...

Страница 4: ...c AT MGS 408 User Manual Additional Information 41 7 1 Disposing of Instrument 41 7 2 Technical Specifications 41 Parts and Accessories 42 8 1 Part Numbers 42...

Страница 5: ...ully read and strictly follow the instructions in the manual Ensure that all product documentation is retained and available to anyone operating the instrument 1 2 Conventions 1 2 1 Short Form Instruc...

Страница 6: ...ns in the manual Ensure that all product documentation is retained and available to anyone operating the instrument DANGER This instrument is neither certified nor approved for operation in oxygen enr...

Страница 7: ...t expressly approved will void the warranty CAUTION In case of malfunction DO NOT continue to use this equipment if there are any symptoms of malfunction or failure In the case of such occurrence de e...

Страница 8: ...ed LEDs to indicate the status of the sensor Power Low alarm High alarm Fault The LCD screen will display the current gas reading and gas type for the selected channel or will indicate fault and or al...

Страница 9: ...WARNING For your safety DO NOT use this instrument in locations classified as hazardous because it has not been designed to be intrinsically safe for use in such areas 2 2 Intended Use The AT MGS 408...

Страница 10: ...ster for Gas Detectors Diagnostic Status LEDs y Controller power fault y Gas Detectors power fault low alarm high alarm Outputs y 3 Relays fault low alarm high alarm Fail safe Option y RS485 Modbus RT...

Страница 11: ...mory cards formatted to FAT 32 with a maximum capacity of 32GB DOWNLOAD INSTRUCTIONS For more detailed product information and an installation guide scan here or visit www mybacharach com to access th...

Страница 12: ...Bluetooth LED indicates when a downstream sensor has established a connection with the MGS 400 App 2 5 Communication Features The AT MGS 408 Gas Detection Controller features full two way communicatio...

Страница 13: ...re working inside the monitor CAUTION Drilling holes in the AT MGS 408 Gas Detection Controller enclosure may damage the unit and will void the warranty Please use provided cable glands for electrical...

Страница 14: ...1 AT MGS 408 Gas Detection Controller Network on page 12 The controller provides an interface by which you can monitor acknowledge alarms and observe conditions inside the mechanical room 3 4 Mounting...

Страница 15: ...ower and Ground on the power input terminal block Secure the incoming AC power neutral white blue live black brown and ground wires to the appropriate terminals using a screwdriver on the press to rel...

Страница 16: ...r is 16 20AWG Belden 3106A shielded twisted pair Power Requirements for AquiTron gas sensors Model Load W AT MGS 410 4 AT MGS 450 4 AT MGS 460 4 AT MGS 550 8 NOTE When using an AT MGS 550 Gas Detector...

Страница 17: ...odbus RS 485 connector Secure the wire leads to the connector in the orientation as displayed on the board Check to make sure the polarity matches the wiring to the Building Management System The shie...

Страница 18: ...the firmware revision level will be indicated on the LCD followed by an LED LCD and beacon self test The controller will then begin scanning connected detectors and display their reported gas concent...

Страница 19: ...o move the cursor to the next character When all character selections for the screen are completed press OK to accept the entries Figure 4 4 Example of Data Entry Required 4 2 Controller Setup Figure...

Страница 20: ...ally open contacts will close with the event corresponding the relay designation If fail safe is selected the relay will be normally energized and will be de energized with the relays designated event...

Страница 21: ...o access the AV alarm setup menu f Press the Up Down arrows to select relay and then press OK The configuration type for the selected relay will begin to flash Figure 4 9 AV Alarm Setup 4 2 4 Fault La...

Страница 22: ...rightness menu f Press the Right Left arrows to adjust the brightness press OK A full bright setting of 10 will be visible from a long distance but may be too bright when the user is operating the key...

Страница 23: ...erve settings or monitor network status The unit is shipped with password protection OFF Entering a 3 digit non zero password enables password protection After protection is enabled the user will be p...

Страница 24: ...FACTORY RESET press OK to perform a factory reset f Press press OK to proceed X to exit Figure 4 15 Factory Reset 4 2 10 Update Firmware When updated firmware is available it can be installed via the...

Страница 25: ...press OK to proceed X to exit Figure 4 16 Firmware Screen Figure 4 17 Firmware Reset 4 3 Channel Summary and Setup Pressing a CH X key from the Channel Configuration screen will bring up a channel sum...

Страница 26: ...tor channel there are four parameters the user may set MON TYP ADR LOC Figure 4 19 Channel Setup 4 3 2 CH X MON Monitor This parameter set to ON or OFF enables or disables the monitoring of the gas de...

Страница 27: ...nt type used for a channel f Press the arrow keys to select entry press OK 4 3 4 CH X ADR Node Address Each connected detector must have a unique node address see detector instruction manual for how t...

Страница 28: ...MGS408_LOG_ WEEK_XXX_OF_YYYY csv where XXX is the week number 1 52 and YYYY is the year The file format is comma delimited text which can be opened directly in Microsoft Excel Row 1 will contain a de...

Страница 29: ...ssociated with the SD card will display as a two digit code next to this menu item and selecting it will bring up a scrollable list of faults in English f Main Menu DATA LOGGING press OK to view the f...

Страница 30: ...menu Figure 5 1 MODBUS Menu 5 1 1 MASTER BAUD RATE Slave devices gas detectors communicate with the master device MGS4088 Controller at this baud rate either 9600 default or 19200 f Main Menu MODBUS C...

Страница 31: ...he Slave parity f Press the arrow keys to select entry press OK 5 1 5 SLAVE STOP BIT The number of stop bits 1 or 2 must match the BMS setting f Main Menu MODBUS CONFIG SLAVE STOP X press OK to stop b...

Страница 32: ...t code high byte Sensor 1 Sensor specific R X 30007 Sensor 1 sensor fault code Sensor 1 Sensor specific R X 30008 Sensor 1 C Sensor 1 Sensor specific R X 30009 Sensor 1 Cal expired flag Sensor 1 0 Cal...

Страница 33: ...ar 3 4 Sensor 1 ASCII characters R X 30026 Sensor 1 SID Text Char 5 6 Sensor 1 ASCII characters R X 30027 Sensor 1 SID Text Char 7 8 Sensor 1 ASCII characters R X 30028 Sensor 1 UID Text Char 1 2 Sens...

Страница 34: ...8 R X 31000 Sensor 1 Concentration Sensor 1 R X 31001 Sensor 2 Concentration Sensor 2 R X 31002 Sensor 3 Concentration Sensor 3 R X 31003 Sensor 4 Concentration Sensor 4 R X 31004 Sensor 5 Concentrat...

Страница 35: ...ts Controller related 1 or 2 R W 40005 Parity Controller related 0 none 1 odd 2 even R W 40006 Controller UID Char 1 2 Controller related ASCII characters R W 40007 Controller UID Char 3 4 Controller...

Страница 36: ...gnostics 2500 25 00degC R X 40022 Controller tact and mag switch state Diagnostics Sum of activated switch values R W 40023 Buzzer enable Controller related 0 Disabled 1 enabled R W 40024 Data Logging...

Страница 37: ...33 AT MGS 408 User Manual R W 40025 Fault Latching Enabled Controller related 0 Disabled 1 enabled...

Страница 38: ...0039 Sensor 7 High Alarm Flag 0 or 1 alarm Sensor 7 R X 10040 Sensor 8 High Alarm Flag 0 or 1 alarm Sensor 8 R X 10065 Sensor 1 Any Alarm Flag 0 or 1 alarm Sensor 1 R X 10066 Sensor 2 Any Alarm Flag 0...

Страница 39: ...00004 Relay Closed Test Setting this flag to one closes all 3 relays simultaneously for 5 seconds At the end of the test the relays revert to their normal operation During the test the Modbus flag wil...

Страница 40: ...n the second page of the main menu f Main Menu DIAGNOSTICS press OK to access the Diagnostic menu Figure 6 1 Diagnostic Menu 6 1 1 DISPLAY CURRENT FAULT Displays the current active controller fault co...

Страница 41: ...T FAULT Resets the historical last fault code to zero Use to find recurring intermittent fault conditions f Main Menu DIAGNOSTICS CLEAR LAST FAULT press OK twice to reset the last fault code 6 1 5 CLE...

Страница 42: ...r address requested ADDR and any errors or exceptions on the bottom line 6 1 8 MODBUS MASTER Displays the live Modbus traffic for each channel Use when troubleshooting communication problems with dete...

Страница 43: ...traffic screen to diagnose 0080 BLE EEPROM Error configuring Bluetooth transceiver Reset or Reboot controller if fault persists consult factory 0100 BT SLAVE BUF Buffer overflow communicating with Bl...

Страница 44: ...the relay test f Manually toggle each relay using the CH key indicated 6 3 2 LED TEST f Main Menu SYSTEM TESTS LED TEST press OK to access the LED test f Press OK all front panel LEDs should illumina...

Страница 45: ...e since August 2012 and apply to this device Common household appliances can be disposed of using special collecting and recycling facilities However this device has not been registered for household...

Страница 46: ...Accessories Part Description 40802 AT MGS 408 SR Optional sounder beacon mounts directly onto AT MGS 408 red lens 40803 AT MGS 408 SG Optional sounder beacon mounts directly onto AT MGS 408 green len...

Страница 47: ...Unit 30 Lawson Hunt Industrial Park Broadbridge Heath Horsham West Sussex RH12 3JR 44 0 1403 216100 info aquilar co uk www aquilar co uk...

Отзывы: