AquatiControl Technology ELC-810 Series Скачать руководство пользователя страница 5

 

ACT 2009 

- 5 -

 

 
C

ONNECTING THE 

S

OLENOID 

V

ALVE

 

 
 

The ELC-810 unit will actuate up to a 2” solenoid valve with a 24 VAC, 10 watt 

(max) supply, without the use of an auxiliary relay. We recommend an anti-water 
hammer or slow close solenoid valve. The power and ground cables should be directly 
connected to the ELC-810 terminal strip.  
 
Refer to 

www.aquaticontrol.com

 for a full line of solenoid valves.  

 

C

ONNECTING 

A

LTERNATE 

L

EVEL 

S

ENSOR

 

 

 

 

The ELC-810 has an alternate level sensing feature that allows a surge tank to run 

at two different levels. This feature is activated with a flow switch or through a signal 
from the contactor on the feature pump located near the starter; and is normally used in 
conjunction with spray features.  
 
 

In order to setup the use of an alternate level on the ELC-810, a second sensing 

application should be placed at the chosen lower water level and a flow switch, supplied 
with the ELC-810, needs to be installed in the feature pump line. The second sensing 
application and flow switch must be wired following the wiring diagram on page 6 of this 
manual. 

 

 

C

ONNECTING 

H

IGH 

L

EVEL 

W

ATER 

D

RAIN 

O

FF

 

 

 

 

The ELC-810 has a high water drain off feature that allows a NC/NO relay inside 

the unit to be used to open a solenoid that will drain water.  
 

In order to setup the use of the high water drain off feature on the ELC-810, a 

third sensing application should be placed at the chosen higher water level and a second 
24 VAC solenoid, not supplied with the ELC-810,should be used (can be a general 
purpose solenoid). The third sensing application and second solenoid must be wired 
following the wiring diagram on page 6 of this manual. 

Содержание ELC-810 Series

Страница 1: ...810 AUTOMATIC WATER LEVEL CONTROLLER AquatiControl Technology 3820 South Federal Blvd Sheridan Colorado 80110 Toll Free 877 755 8817 Fax 303 761 1499 www aquaticontrol com Serial No __________________...

Страница 2: ...ACT 2009 2 TABLE OF CONTENTS Introduction 3 Installation 4 5 Wiring Diagram 6 Operation 7 9 Routine Maintenance 10 Troubleshooting 11 12 Warranty 13...

Страница 3: ...following pages of this manual The ELC 810 should ship with the following contents 1 Control unit Sensing Unit s Standard Well Sight Glass Wet Well Surge Tank Deck Well 1 Mounting Hardware 1 Operation...

Страница 4: ...l water level should sit approximately 1 5 up from the bottom of the end cap The surge tank sensing unit is installed in the surge tank at normal operating water level with the included clic connector...

Страница 5: ...In order to setup the use of an alternate level on the ELC 810 a second sensing application should be placed at the chosen lower water level and a flow switch supplied with the ELC 810 needs to be in...

Страница 6: ...ACT 2009 6...

Страница 7: ...arrows The enter button will bring you back to the startup screen Options can be changed by following the directions below The first six screens as you scroll down through the menu are for informatio...

Страница 8: ...seconds to 99 seconds use up and down arrows to change To activate this option hold the left and right arrows for 3 seconds DEFAULT 10 seconds DELAY TO SHUTOFF time solenoid valve will stay on after s...

Страница 9: ...ally closed flow switches Open or Closed use left and right arrows to change DEFAULT Closed SENSOR TYPE set to Other DEFAULT Other SOUNDER WITH ALARM beeping will occur when in alarm mode if yes is se...

Страница 10: ...RGE TANK The Surge Tank Sensing Unit will not normally need to be cleaned however if the cap on the bottom of the sensing application becomes clogged with debris it can be unscrewed and rinsed until c...

Страница 11: ...ective sensor Replace sensor Sensing unit not set properly Readjust sensor to water level Wiring is incorrect in sensor junction box Check wiring connection Level light does not come on Cable in ELC 8...

Страница 12: ...ACT 2009 12 SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION Can t change settings Forgotten wrong password Reset ELC by turning the power on while holding the left and right arrows...

Страница 13: ...or part which is returned transportation prepaid to the factory within one year of delivery to the original purchaser and which is proven defective upon examination ACT disclaims all liability for da...

Отзывы: