MAINTENANCE AND OPERATION

MAINTAIN PROPER WATER FLOW

•  It is important to operate and maintain the filter according to the manufacturer’s 

specifications.  As a filter gets dirty, the water flow to the heat pump is reduced. 

The higher the pressure on the filter gauge, the lower the flow rate.

•  Similar to a dirty filter, large amounts of debris in the pump and skimmer baskets 

can reduce water flow. Keep baskets free of debris.

•  Check for improper valve settings. A partially closed valve after the filter, or a 

full-open bypass around the heater, will cause insufficient water flow through 

heater.

•  If the conditions listed above remain unresolved, the water flow through the 

heater may be reduced to a point where internal safety devices (i.e.: “HP” or 

“HP5”) shut the heater off. 

•  Before calling for service, always check the filter, the pump basket, and water 

valve positions. If the problem persists, please call Aquatherm at: 239-482-0606

MAINTAIN PROPER WATER CHEMISTRY

•  IMPORTANT!  Your heat pump is engineered for exceptional durability 

and reliability. This unit’s heat exchanger—being equipped with titanium 

tubing—will be nearly impervious to water chemistry damage. However, other 

components of the heater, and the remainder of the pool/spa equipment in 

general, may be susceptible to damage from prolonged exposure to unbalanced 

water chemistry. There can also be health risks involved with improper water 

chemistry

•  For the longevity of the entire pool/spa installation, and for the safety of users, 

it is strongly  recommended that the water chemistry be checked regularly and 

maintained within proper norms. The table below lists recommended water 

chemistry levels.

Chlorine_......................................1.0_-_3.0_ppm_in_pools,_1.5_-_3.0_ppm_in_spas

Bromine_......................................_2.0_–_4.0_ppm_in_pools,_3.0_–_5.0_ppm_in_spas

pH_...............................................7.4_–_7.6_ppm_in_pools,_7.2_–_7.8_ppm_in_spas

Total_Alkalinity_.............................80_–_140_ppm_in_pools,_80_–_120_ppm_in_spas

Calcium_Hardness_......................200_–_400_ppm_in_pools_and_spas

Total_Dissolved_Solids_.................1,000_–_2,000_ppm_in_pools,_

_

1,500_ppm_above_start-up_TDS_in_spas

*Standards for commercial applications may vary.  

RECOMMENDED WATER CHEMISTRY STANDARDS*

9

6

USER LOCK CODE OPTION [ULC]:

Heat pumps are shipped from the factory with the [ULC] option disabled. En-

abling the [ULC] function permits the heat pump owner to restrict access to the 

unit’s controls. With the [ULC] function enabled, unless the correct ULC code 

number is entered, changes to Level-1 programming are not possible. (I.e.: Alter-

ing temperature set points, Pool/Spa selection, C/F display changes, etc., will not 

be possible). The [ULC] option can be thought of as an electronic lockable cover 

for the controls. 

A.   SELECTING ULC OPTION:

1)  Press either the UP or DOWN ARROW keys; if “LOC” is momentarily dis-

played followed by “0”, the ULC feature is enabled. If “0” displays proceed 

to “6)” of this section; otherwise, see number “2,” below.

2)  Simultaneously press and hold both the [UP ARROW] and [DOWN ARROW] 

keys until [CF1] (Celsius / Fahrenheit) code appears.

3)  Press the [POOL/SPA] key once to display [ULC].

4)  With [ULC] displayed, pressing either the Up or Down Arrow key will display 

either “1” or “0”. Selecting “0” will allow the keypad to remain unlocked. 

Selecting “1” will enable the User Lock Code option. Then, to enter a lock 

code number, press the [POOL/SPA] key once to display [ELC] (Enter Lock 

Code).

5)  With [ELC] displayed, use the Up or Down arrow keys to select a lock code. 

The code can be any number from “00” to “99”. The factory set lock code is 

“0”. Not pressing any buttons for 15-seconds will allow the controller to save 

the selection and return to the normal operating mode. Pressing the {POOL/

SPA] key will also save the selection, and will step the controller to the next 

menu parameter: [CFO] (Call Flex Options).

6)  Once the ULC option has been enabled, pressing any key will momentarily 

display “LOC” followed by “0” (prompting the entry of the correct lock code 

number). To gain access to the controller:

a.   Using the [UP ARROW] key, scroll to the correct lock code number, 

then;

b.  Press  the  [POOL/SPA]  key…  Current  water  temperature  will  be  dis-

played… Control setting can now be viewed or changed as desired.

c.   After a period of approximately four (4) minutes, during which time no 

buttons have been pressed, the controller will automatically return to the 

locked mode. Provided ULC selection is set to “1,” the controller will 

always fail-safe in the locked mode.

Содержание AT115

Страница 1: ...______ SERIAL_____________________________________________________ PURCHASE DATE_ ___________________________________________ INSTALLING CONTRACTOR____________________________________ POOL SPA HEAT PU...

Страница 2: ......

Страница 3: ...erved Except for a few minor owner capable maintenance items explained later in this manual repair and service of your heat pump must be performed only by licensed service personnel If you suspect you...

Страница 4: ...e power supply panel and the disconnect switch located near the heat pump are both turned ON Is the code FLO displayed If so check to be sure that the circulating pump is operating and the filter is c...

Страница 5: ...he desired water temperature for the POOL and or SPA 3 To Begin Heating A Verify MODE is set to HEAT HEA then depending on which body of water is to be heated use the POOL SPAselector key to select PO...

Страница 6: ...operation whenever the actual displayed water temperature falls below the desired set point after an initial time delay of 4 minutes the unit will begin heating THE HEATER CONTROLLER HAS AN ANTI SHOR...

Страница 7: ...heated is different Your heat pump comes equipped with two thermo stats One thermostat is for the pool and the other is for the spa Simply position the pool and spa isolation valves as directed by you...

Страница 8: ...10 Operational Programming Codes FLO No Water Flow Detected This code appears whenever the circulating pump is off or when the heater is not receiving correct water flow OFF System is Off This code a...

Страница 9: ...MENDED WATER CHEMISTRY STANDARDS 9 6 USER LOCK CODE OPTION ULC Heat pumps are shipped from the factory with the ULC option disabled En abling the ULC function permits the heat pump owner to restrict a...

Страница 10: ...nu ously until the desired water temperature is attained This may take several hours to several days depending upon the size of the pool or spa and weather conditions If a time clock or similar device...

Отзывы: