Section 1

Safety Information

These are the original instructions. Please read this entire manual before operating this equipment. Pay attention to all 

danger, warning, and caution statements in this manual. Failure to do so could result in serious personal injury or damage to 

the equipment.
Make sure that the protection provided by this equipment is not impaired. DO NOT use or install this equipment in any 

manner other than that specified in the installation manual.

1.1 Potential Hazards:

Read all labels and tags attached to the system. Personal injury or damage to the system could occur if not observed.

Waste electrical and electronic equipment (WEEE). This symbol 
indicates that you should not discard wasted electrical or electronic 
equipment (WEEE) in the trash. For proper disposal, contact your local 
recycling/reuse or hazardous waste center.

This symbol indicates not to store any combustible or flammable 
material close to the system.

Hg

This symbol indicates there is Mercury present.

This symbol indicates that the contents of the transport package are 
fragile and the package should be handled with care.

This is the safety alert symbol. Obey all safety messages that follow 
this symbol to avoid potential injury. When on the equipment, refer to 
the Operational and Maintenance manual for additional safety 
information.

This symbol indicates safety glasses with side protection is required for 
protection against UV exposure.

This symbol indicates a risk of electrical shock and/or electrocution 
exists.

This symbol indicates gloves must be worn.

This symbol indicates the marked equipment may contain a 
component that can eject forcibly. Obey all procedures to safely 
depressurize.

This symbol indicates safety boots must be worn.

This symbol indicates the system is under pressure.

This symbol indicates the operator must read all available 
documentation to perform required procedures.

UV

This symbol indicates there is a potential UV hazard. Proper protection 
must be worn.

Cu

This symbol indicates the plumber must use copper piping.

This symbol indicates the marked item could be hot and should not be 
touched without care.

This symbol indicates that the system should only be connected to a 
properly grounded, grounding-type controller receptacle that is 
protected by a Ground Fault Circuit Interrupter (GFCI).

This symbol indicates there is a potential for VERY hot water when 
flow is started.

1.2 Safety Precautions:

D A N G E R

  •

Electric Shock:

 To avoid possible electric shock, special care should be taken since water is present near the electrical equipment. Unless a 

situation is encountered that is explicitly addressed by the provided maintenance and troubleshooting sections, DO NOT attempt repairs yourself, 
refer to an authorized service facility.

  •

GROUNDING: 

This product must be grounded. If it should malfunction or breakdown, grounding provides a path of least resistance for electric 

current to reduce the risk of electrical shock. This system is equipped with a cord having an equipment-grounding conductor and a grounding plug. 
The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances. 
Improper connection of the equipment-grounding conductor can result in a risk of electrocution. Check with a qualified electrician or service 
personnel if you are in doubt as to whether the outlet is properly grounded. DO NOT modify the plug provided with this system – if it does not fit in 
the outlet, have a proper outlet installed by a qualified electrician. DO NOT use any type of adapter with this system.

  •

GROUND FAULT CIRCUIT INTERRUPTER PROTECTION

: To comply with the National Electrical Code (NFPA 70) and to provide additional 

protection from the risk of electric shock, this system should only be connected to a properly grounded, grounding-type controller receptacle that is 
protected by a Ground Fault Circuit Interrupter (GFCI) or to a residual current device (RCD) having a rated residual operating current not exceeding 
30 mA. Inspect operation of GFCI as per manufacturer’s suggested maintenance schedule.

  •

DO NOT operate the disinfection system if it has a damaged cord or plug, if it is malfunctioning or if it has been dropped or damaged in any manner.

  •

DO NOT use this disinfection system for other than intended use (potable water applications). The use of attachments not recommended or sold by 
the manufacturer / distributor may cause an unsafe condition.

  •

DO NOT install this disinfection system where it will be exposed to the weather or to temperatures below freezing.

  •

DO NOT store this disinfection system where it will be exposed to the weather.

  •

DO NOT store this disinfection system where it will be exposed to temperatures below freezing unless all water has been drained from it and the 
water supply has been disconnected.

Failure to follow these instructions will result in serious injury or death.

Safety Information

3

Содержание SC200-A

Страница 1: ...Owner s Manual Powered by Models SC200 A SC410 A 520192 R_RevK...

Страница 2: ...should you insist on genuine factory supplied VIQUA replacement lamps Use of widely available non genuine replacement lamps has been shown to damage the control module of VIQUA UV disinfection equipme...

Страница 3: ...l for VERY hot water when flow is started 1 2 Safety Precautions DANGER Electric Shock To avoid possible electric shock special care should be taken since water is present near the electrical equipmen...

Страница 4: ...n avoid inhalation or ingestion of the debris and avoid exposure to eyes and skin Never use a vacuum cleaner to clean up a broken lamp as this may scatter the spilled mercury Obey local regulations an...

Страница 5: ...1 O ring 410867 Used on all systems 2 214 fused quartz sleeves with fire polished ends QS 001 SC200 A QSO 410 SC410 A 3 Retaining Nut RN 001 Used on all systems 4 Hard glass coated Sterilume HO UV la...

Страница 6: ...5 micron sediment filter must precede the disinfection system Ideally the disinfection system should be the last treatment the water receives before it reaches the faucet Procedure 1 The use of a by...

Страница 7: ...nection point to prevent any water from potentially leaking onto the controller by means of a leak at a connection point or a sweating system Make sure you allow for a drip loop as shown in Figure 5 o...

Страница 8: ...2 1 2 2 2 Shut off the water supply Close each faucet 3 1 2 Remove filter cartridge s 4 Household 5 25 Bleach Solution BLEACH x2 2 Pour 2 cups of household bleach solution into the filter housing s No...

Страница 9: ...main power source and allow the unit to cool for 10 minutes 3 1 2 Remove the lamp connector by squeezing the plastic locking tabs on the side of the connector 4 Hg UV Remove the lamp in upward directi...

Страница 10: ...then replace the sleeve 6 Reinstall the quartz sleeve in the chamber allowing the sleeve to protrude an equal distance at both ends of the chamber Slide supplied O rings onto each end of the quartz sl...

Страница 11: ...refer to Section 4 1 5 1 3 Resetting Lamp Life Refer to Section 4 1 Note Even though the alarm on the system can be deferred for a period of time it is important to address each and every alarm condit...

Страница 12: ...system must have a bacterial free distribution system to work effectively Refer to Section 3 1 Possible break through of sediment through pre filter Have source water tested for turbidity may need st...

Страница 13: ...1 MNPT 3 4 FNPT Combo 3 4 FNPT 1 MNPT Shipping Weight 5 1 kg 11 3 lbs 6 8 kg 15 0 lbs Electrical Voltage 100 240 V 50 60Hz 100 240 V 50 60Hz Max Current 1 5 Amp 1 5 Amp Power Consumption 35 W 60 W La...

Страница 14: ...rdware Components VIQUA warrants the electrical controller and hardware components to be free from defects in material and workmanship for a period of three 3 years from the date of purchase During th...

Страница 15: ...Supporter par Mod les SC200 A SC410 A Manuel d utilisation Supporter par 520192 R_RevK...

Страница 16: ...ine VIQUA Il a t d montr que l utilisation de lampes de rechange qui ne sont pas d origine et largement disponibles endommage le module du dispositif de commande du syst me de d sinfection par UV VIQU...

Страница 17: ...nnect une prise correctement mise la terre prot g e par un disjoncteur de fuite de terre DFT Ce symbole indique qu il y a un risque potentiel d eau TR S chaude lorsque l coulement commence DANGER Le n...

Страница 18: ...mercure Si la lampe se brise vitez d inhaler ou d ing rer des d bris ou m me d exposer vos yeux et votre peau N utilisez jamais d aspirateur pour nettoyer une lampe bris e car cela pourrait r pandre l...

Страница 19: ...0867 Utilis sur tous les syst mes 2 manchons en quartz fondu 214 avec extr mit s polies au feu QS 001 SC200 A QSO 410 SC410 A 3 crou de blocage RN 001 Utilis sur tous les syst mes 4 Lampes UV en verre...

Страница 20: ...e de d sinfection devrait tre le dernier traitement re u par l eau avant qu elle arrive au robinet Proc dure 1 L utilisation d un ensemble de d rivation est recommand e dans le cas o le syst me n cess...

Страница 21: ...tif de commande 5 Installez la lampe UV Consultez la Section 4 1 6 Lorsque tous les raccords de plomberie sont termin s tournez lentement l alimentation en eau et v rifiez les fuites ventuelles La cau...

Страница 22: ...ra nera l oxydation de ces contaminants et pourrait n cessiter le rin age r p t du r servoir d eau chaude Cette ventualit doit tre trait e ind pendamment selon la proc dure de d marrage pour tout autr...

Страница 23: ...mplacement de la lampe UV 1 Couper la canalisation d eau vers la chambre et rel cher la pression du syst me avant de proc der l entretien 2 0 30 15 45 10 min D brancher la source d alimentation princi...

Страница 24: ...age inf rieur le ressort flottant et le joint torique 3 1 2 D poser l crou de blocage sup rieur et le joint torique 4 D poser le manchon de quartz 5 Mild Acid Nettoyer le manchon en quartz avec un chi...

Страница 25: ...teur consultez la Section 4 1 5 1 3 R initialisation de la dur e de vie de la lampe Consultez la Section 4 1 Remarque m me si l alarme du syst me peut tre report e pendant un certain temps il est impo...

Страница 26: ...st en place recherchez des coupures ou usures nettoyez le joint torique humidifiez le l eau lubrifiant et reposez le remplacez le si n cessaire 410867 Condensation sur la chambre UV caus e par une hum...

Страница 27: ...Courant max 1 5 amp res 1 5 amp res Consommation lectrique 35 W 60 W Watts de la lampe 25 W 45 W Pression maximale de fonctionnement 125 psi 861 kPa 125 psi 861 kPa Pression minimale de fonctionnemen...

Страница 28: ...VIQUA garantit les composants mat riels et lectriques dispositif de commande contre tout d faut de mati re et de main d uvre pour une dur e de trois 3 ann es compter de la date d achat Dans cette p ri...

Страница 29: ...Desarrollado por Modelos SC200 A SC410 A Manual del propietario Desarrollado por 520192 R_RevK...

Страница 30: ...eposici n VIQUA originales de f brica Se ha demostrado que el uso de las l mparas de reposici n no originales disponibles ampliamente en el mercado da a el m dulo de control del equipo de desinfecci n...

Страница 31: ...UY caliente cuando se inicie el flujo PELIGRO El incumplimiento de estas instrucciones puede ocasionar lesiones graves o la muerte Descarga el ctrica Para evitar posibles descargas el ctricas se deben...

Страница 32: ...ercurio En caso de rotura evite inhalar o ingerir los restos y evite la exposici n de ojos y piel Nunca utilice una aspiradora para limpiar una l mpara rota ya que podr a dispersar el mercurio vertido...

Страница 33: ...go QS 001 SC200 A QSO 410 SC410 A 3 Tuerca de retenci n RN 001 Se utiliza en todos los sistemas 4 L mparas UV Sterilume HO revestido de cristal duro para una vida til prolongada y de calidad constante...

Страница 34: ...i n deber a ser el ltimo tratamiento que reciba el agua antes de llegar al grifo Procedimiento 1 Se recomienda el uso de un conjunto de desv o en el caso de que el sistema requiera mantenimiento fuera...

Страница 35: ...sulte Secci n 4 1 6 Cuando se hayan realizado todas las conexiones de tuber as conecte el suministro de agua lentamente y compruebe si hay fugas La causa m s probable de fugas est en la junta t rica E...

Страница 36: ...a la oxidaci n de dichos contaminantes y es posible que sea necesaria una limpieza repetida del tanque de agua caliente Esta eventualidad se debe tratar de forma independiente bajo el procedimiento de...

Страница 37: ...y libere la presi n del sistema antes de realizar el servicio 2 0 30 15 45 10 min Desconecte la fuente de alimentaci n principal y deje que la unidad se enfr e durante 10 minutos Desconecte la fuente...

Страница 38: ...junta t rica de la parte inferior 3 1 2 Quite la tuerca de retenci n y la junta t rica de la parte superior 4 Quite la vaina tubular de cuarzo 5 Mild Acid Limpie la vaina tubular de cuarzo con un tra...

Страница 39: ...onsulte la Secci n 4 1 5 1 3 Reinicio de la vida de la l mpara Consulte Secci n 4 1 Nota Aunque la alarma del sistema se puede aplazar durante un per odo de tiempo es importante que se responda a toda...

Страница 40: ...retenci n o el sensor UV Aseg rese de que la junta t rica est en su sitio compruebe si hay cortes o abrasiones l mpiela humed zcala con agua o lubricante y vuelva a instalarla o sustit yala si es nec...

Страница 41: ...ltaje 100 240 V 50 60 Hz 100 240 V 50 60 Hz Corriente m xima 1 5 Amp 1 5 Amp Consumo de energ a 35 W 60 W Vatios de la l mpara 25 W 45 W Presi n m xima de funcionamiento 125 psi 861 kPa 125 psi 861 kP...

Страница 42: ...ponentes el ctricos controlador y de hardware estar n libres de defectos de material y mano de obra durante un per odo de tres 3 a os desde la fecha de compra Durante este per odo VIQUA reparar o reem...

Страница 43: ...43 Esta p gina est en blanco de forma intencional...