Environmental Monitoring System (EMS-5 / 10) Instruction Manual
8
2.1
Technical Specifications
Master Panel
Specification
Notes
Dimensions
335 x 270 x 110 mm
Millimetres
. Width x Height x Depth
Weight
4.5 KG
Kilograms
Supply Voltage
80
–
264 VAC
Volts / Alternating Current
. 50/60 Hz
frequency
Motherboard Output Relay
Voltage Rating
250 VAC
Motherboard Output Relay
Current Rating
8 A
Amps
. Maximum into resistive load.
Relay Minimum Load
10 mA
Milliamps
. At 5 VDC (Volts / Direct Current)
Detection Response Time
1 second
Ingress Protection (IP) Code
IP51 (dust protected
and dripping water)
Ingress Protection to IEC 60529. Holes
drilled during installation may affect unit IP
Alarm (Audible)
85 dB
Decibels
. Within 0.6 m range
Alarm (Visible)
Via LED panel
Input channels
5 or 10
Leader Cable
Belden 9534
Variable length
Operating Temperature
0 to +50°C
Degrees Centigrade. Ambient temperature
Operating Humidity
10 to 95%
Relative humidity (non-condensing) at 45°C
Operating Altitude
0 to 3,000 m
Metres
Storage Temperature
-20 to +70°C
Sensor Cable Length (per
input channel)
100m (or maximum 20
probes)
Use recommended yellow Sensor Cable.
Also requires End of Line (EOL) terminator
Table 1:
EMS-5 / 10 Technical Specifications