Environmental Monitoring System (EMS-5 / 10) Instruction Manual
14
3.2.2
Sensor Connections
Figure 5:
Sensor Cable Connection to Interface Board
A.
Sensor Cable (SCY) using LC10C and End of Line
Figure 6:
Sensor Cable Connection using Leader Cable (LC10C)
Connect the Sensor Cable using LC10C and End of Line as follows:
1.
Ensure that the unit is powered OFF.
Connect the
leader cable
into the
sensor
input terminals
on the
interface board
. Do
not connect the green or white cores
(
2.
When connecting the leader cable to its
respective sensor input terminals, ensure
that the factory-issued
terminating resistor
is removed. Retain all resistors for future
fault finding/testing.
3.
Plug the opposite end of the
leader cable
into the
sensor cable
4.
Once all sensor cables are connected, plug
the
End of Line (EOL) terminator
into the
end of the last run of the
sensor cable
.
Cable Connection
Leader Cable
Sensor Cable
EOL Terminator
Motherboard
Interface Board
(5 or 10 zone)
For unpopulated zones,
leave resistor terminated
in zone plug. Remove
resistor on populated
zones.
Belden 9534 EIA RS-232 Multicore
Cable (4 Core, 24 AWG, 0.2 mm²)
Green and white
cores not used