10K manual
Issue 1.0, 31st July 2019
Page 27
Register Name
Description
Units
Range
40004
Latched Alarms
(read-only)
Latched alarm requires
Aqualeak 10K to be reset
once alarm is cleared.
Note
: Set with DIP SW1;
this register is read-only.
0 = Disabled
1 = Enabled
Default: Disabled
0-65535
40005
Silence Audible
Alarm
Indicates whether or not
the audible alarm sounds
when the Aqualeak 10K
goes into alarm state
0 = Disabled
1 = Enabled
Default: Disabled
0-65535
40006
Reset Alarm
Resets the Aqualeak 10K
after an alarm state.
Alternatively, press and
hold the front panel’s
Test/Reset button for 3
seconds.
0 = Disabled (do not
reset alarm)
1 = Enabled (reset
alarm)
Default: 0 (Disabled)
0-65535
40007
Sample Size
Number of samples taken
to calculate the leak
location
0 = Set to default value
4 = Minimum
25 = Maximum
Default: 12
0-65535
40008
Resistance per
Foot
Milliohms of resistance of
installed leak detection
cable.
This value is set here and
can also be read through
register 30008.
2000
–
3500 milliOhms/
foot
or
3500
–
4240 milliOhms/
foot*
*to convert this value
to Ohms/foot, divide
the number by 1000
0-65535
40009
AC Rejection
Frequency
Used by ADC to reject AC
powerline frequencies.
Needed only if the
Aqualeak10K is running on
24 VAC power.
0 = 60Hz
1 = 50Hz
Default: 1 (50Hz)
0-65535
40010
Spare
Not used.
0-65535
40011
Spare
Not used.
0-65535
40012
Spare
Not used.
0-65535
40013
Spare
Not used.
0-65535
40014
Spare
Not used.
0-65535
40015
Spare
Not used.
0-65535
40016
Leak Alarm Delay Amount of time that
passes between leak
detection and alarm
notification.
5
–
990 seconds
Default: 10 seconds
0-65535
40017
Contamination
Alarm Delay
Amount of time that
passes between cable
contamination detection
and alarm notification.
5
–
990 seconds
Default: 120 seconds
0-65535