Page - 27
MODEL
HEAT EXCHANGER TYPE
FLOW RATES
MINIMUM
MAXIMUM
TC500
Titanium Tube-in-Tube
20 GPM (75.7 L/min)
45 GPM (170 L/min)
TC1000
Titanium ThermoLink
®
30 GPM (113.6 L/min)
70 GPM (265 L/min)
TC1500
Titanium ThermoLink
®
30 GPM (113.6 L/min)
70 GPM (265 L/min)
PLEASE NOTE -
If minimum flow rates are not met, heat pump performance is reduced and performance will
suffer. Internal safety devices may deactivate the heat pump with the following errors:
l
HIGH PRESSURE FAULT
l
HP5 SYSTEM LOCKOUT
l
LOW PRESSURE FAULT
l
LP5 SYSTEM LOCKOUT
l
Operate water filtration devices per manufacturer's specifications. Dirty filters can cause a reduction of water flow
to the heat pump. An increase of 7-10 psi (48 to 69 kPa) higher than the clean filter pressure typically reduces
flow rates. This requires the filter to be cleaned or back-washed.
l
Keep baskets free of debris. A large quantity of debris in the pump and skimmer baskets can reduce water flow.
l
Check for improper valve settings. A partially closed valve after the filter, or a full-open bypass around the heat
pump, will cause insufficient water flow through the heat pump.
l
The maximum static pressure (or operating pressure) is 50 psi (345 kPa). These specifications relate to the heat
pump only.
l
Code-specified whole system turnover rates must be satisfied.
2.6 Adjusting Water Flow Using ΔT (Delta-T)
The Delta-T is the temperature difference between the water temperatures entering and leaving the heat pump.
The equipment can be fine-tuned for maximum performance by balancing water flow rates to maintain an
ideal ∆T.
The adjustment procedure must be completed with the unit in heating mode.
l
Installed temperature ports are required to perform the following procedures.
l
These ports are typically located on the pool in and pool out water lines approximately six inches away from the
heat pump.
PLEASE NOTE -
l
The installation of temperature ports is required for all commercial applications.
l
The installation of temperature ports is strongly recommended for residential installations.
n
Temperature Port Kit (# STK0096)
2
-
M
ai
nt
ena
nc
e
Содержание HeatWave SuperQuiet SQ120R
Страница 2: ......
Страница 11: ...Page 8 1 Operation ...
Страница 13: ...Page 10 1 Operation ...
Страница 17: ...Page 14 Set Efficiency Mode to 24 Hour 1 Operation ...
Страница 18: ...Page 15 Set Efficiency Mode to Filtration Schedule 1 Operation ...
Страница 19: ...Page 16 1 Operation ...
Страница 21: ...Page 18 Configure for Call mode 1 Operation ...
Страница 22: ...Page 19 Configure for Flex mode 1 Operation ...
Страница 53: ...Page 50 Model Number Example 4 Appendix ...
Страница 58: ......