Page - 4
1.1 Positioning Equipment
Controlling Irrigation and Rainwater Runoff
l
Irrigation water may damage heat pump components. Direct irrigation water away from the heat pump.
l
The heat pump will withstand normal rainfall. Do not allow a roof slope to direct rainwater onto the heat pump.
Have a gutter installed on the roof edge to direct this water away from the heat pump. Or install the heat pump in
another location.
Mounting Pad Requirements
l
The heat pump's base must be installed on a flat and level surface that completely supports the
entire base.
l
Build the heat pump pad out of concrete or other code-approved material.
l
Confirm the pad can support the weight of the heat pump.
l
Elevate the pad enough to allow for drainage.
l
Make sure the pad is flat and level.
l
Have the pad support the
entire heat pump base in all directions.
l
Do not install the heat pump on soil or grass.
l
Do not allow the heat pump base to touch the building's foundation.
l
Do not place the heat pump directly on a concrete floor. This can cause noise to be transmitted to an occupied
space. If necessary install vibration dampers between the heat pump base and floor.
l
Equipment pad must meet all requirements of authorities having code-related jurisdiction.
Anchoring to Pad
l
Follow all applicable local, state, and national requirements regarding wind load anchoring.
l
The shipping brackets used to secure the heat pump to the pallet are approved mounting (hurricane) brackets.
They should be used to anchor the heat pump to the pad.
l
If needed, contact AquaCal
®
to obtain anchoring kit information. Please have the heat pump model number and
serial number when requesting support.
Identifying Model Specifications
1.2 Clearances
l
Locate the heat pump at least 24 inches (61 cm) away from the wall. And provide a minimum 24 inches (61 cm)
between heat pumps. This will allow for rear plumbing access and electrical connections.
l
Do not stack heat pumps on top of each other. Use approved racks when stacking equipment.
l
Only rack equipment two units high.
l
Equipment rack must meet all requirements of authorities having code-related jurisdiction.
l
Avoid storing chemical containers near the heat pump. The chemicals can cause equipment damage.
l
Avoid placing objects near or on top of the heat pump. This includes shrubbery and lawn furniture. These objects
will hinder maintenance access.
1
-
Ins
ta
ll
at
ion
Содержание AutoPilot SP05
Страница 2: ......
Страница 9: ...Page 5 Water Source Top View Water Source Side View 1 Installation...
Страница 10: ...Page 6 1 3 Dimensions Water Source WS03 WS05 Water Source WS10 1 Installation...
Страница 31: ...Page 27 Configure Call Flex Enter Installer Menus then proceed 1 Installation...
Страница 32: ...Page 28 1 Installation...
Страница 36: ...Page 32 1 Installation...
Страница 39: ...Page 35 1 Installation...
Страница 43: ...Page 39 1 Installation...
Страница 44: ...Page 40 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation...
Страница 48: ...Page 44 1 Installation...
Страница 50: ...Page 46 1 Installation...
Страница 53: ...Page 49 1 Installation...
Страница 56: ...Page 52 1 Installation...
Страница 58: ...Page 54 1 Installation...
Страница 61: ...Page 57 1 Installation...
Страница 63: ...Page 59 1 Installation...
Страница 83: ...Page 79 l Follow all National Electric Codes NEC and or State and Local guidelines 3 Appendix...
Страница 84: ...Page 80 3 8 Schematics Some schematics have been provided in the appendix of this manual 3 Appendix...
Страница 88: ......
Страница 89: ......