Operating Instructions

Condensation

All heat pump pool heaters will have
condensation. It is typical to have as
much as 6-8 gallons of condensation or
water per hour, during a warm, humid
day. Do not mistake this for a leak.
If you are not sure the water is a leak or is
condensation, there are two ways to
check this. First, use a pool test strip to
see if there is any chlorine or bromine in
the water. If there is, contact the factory
for service. Second, you can turn off the
heater, leave the filter pump running and
see if the water stops. If you do not see
additional water, then the original water
was condensation.

Pool Blankets

A pool blanket has been proven to
greatly reduce the heat loss in the pool
and will save as much as 50% - 60% in
your heating bills. During the start of
the swimming season and the end of
the season the heater may not be able
to maintain your desired temperature
without the use of the pool blanket.

Seasonal Shutdowns

At the end of your swimming season
you may have freezing weather
conditions. The unions (provided) must
be disconnected to drain any water in
the pipes. Failure to do so may cause
the heat exchanger to expand and
crack. This will void your warranty.
If you live in an area that does not have
freezing weather conditions but are
subject to extended periods of non-use,
allow the filtration system to continue to
run water through the heater. Or you
can drain the unit of all water.

Pool Openings

If at the end of the previous season you
disconnected the unions, be sure to
connect them before you turn on the
filtration system. Once the pool has
been cleaned and the unit has been
checked for leaks, turn the power on
the heater and set the thermostat to
the desired temperature. 

Note:

It may take up to three days to

reach the desired temperature during the
opening of the swimming season. Without
a pool blanket, it may take even longer
and may not reach the desired
temperature until later in the season.

Weather Conditions

Weather conditions play a big part in the
operation of the heater. Low outside
ambient temperature, high winds, low
relative humidity, and a large amount of
shading on the pool will all have an effect
on how much time it takes to heat the
pool and how much time it might need to
maintain the desired temperature. Once
the outside ambient temperature drops
below 50ºF (38°F for h/c units), the heater
may not operate.

Troubleshooting
Guide 

If the heater is not operating during the
initial start-up, check to see if it has been
installed properly, per this owner’s
manual. Make sure the breaker has been
sized properly. The following are
conditions to check before calling
AquaPRO

®

Systems for a service:

Diagnostics

ALL MODELS (except PRO1100)

The display located on the heat pump
has diagnostic codes, which help
explain any reason for the heater not
to be operating properly. The following
are the diagnostic codes and the
reasons for them appearing:

FLO: This code means “Pressure Switch”
or water pressure switch. This means
there is not enough water flow to
activate the water pressure switch. The
cause could be from a clogged filter or a
manual by-pass is in the wrong position
and is not allowing water into the heater.
Once the filter has been cleaned or the
by-pass has been changed to allow water
to flow through the heater, the FLO
display will go away and the water
temperature will appear on the display.

HP: This code means “High Pressure” or
high pressure switch. Either there is low
water flow or high ambient temperature
or both. Again, the filter could be
clogged and not allowing enough water
flow to pass through the heat exchanger
and allow the heat to be taken away fast
enough, or a by-pass is not in the proper
position. Once the filter has been
cleaned or the by-pass has been re-
positioned, the display should return to
the temperature of the water. 

LP: This code means “Low Pressure” or low
pressure switch. Either the outside
ambient temperature is below 50°F (38°F

for h/c units), which is too low for the
heater to operate, or the unit is low on
refrigerant. Once the outside temperature
has risen above 60ºF, and the LP code
remains, call the factory for repair.

PSd: This code means there is a pool sensor
defect. Please call AquaPRO

®

Systems to

arrange service for the heat pump.

DSd: This code means there is a defrost
sensor defect. Please call AquaPRO

®

Systems to arrange service for the heat
pump.

LP3: This is like the “LP” described
above, however the unit has shut down
because this fault has happened 3 times
within a 24 hour time period. If the
ambient temperature is below 50°F
(38°F for h/c units), the problem will
most likely persist until the ambient air
temperature rises above 50°F. Pressing
any of the buttons on the front control
panel will restore the unit to its normal
operating mode. If the ambient air
temperature is not the issue and the
heat pump continues to display “LP” or
“LP3”, please call AquaPRO

®

Systems to

arrange service for the heat pump.

HP3: This is like the “HP” described above,
however the unit has shut down because
this fault has happened 3 times within a
24 hour time period. Please check your
pool’s plumbing, valves and pump / filter
system for blockages or flow restrictions,
as this is most likely the cause for the fault.
Pressing any of the buttons on the front
control panel will restore the unit to its
normal operating mode. If your pump and
filter system is working normally and
there are no flow restrictions and the heat
pump continues to display “HP” or “HP3”,
please call AquaPRO

®

Systems to arrange

service for the heat pump. Please note,
AquaPRO

®

Systems will not be responsible

for non-warranted service calls.

MODELS: PRO1300h/c and
PRO1300h/c TCE

COL: This code reminds you that the
unit is running in the cooling mode.

HOT: This means the pool temperature
has increased by 2° while the unit is
operating in the “COL” mode. This is
only a warning that the unit is having
difficulty cooling the pool to the
desired temperature. The “HOT”
message will remain until either the
pool drops to the desired temperature
or the set “COL” temperature is raised
above the pool’s current temperature.

Application

Guidelines

(cont.)

Phone: (877)-278-2797

10

www.aquaprosystems.com

Содержание PRO1100

Страница 1: ... PARA PISCINAS PRO1100 PRO1100e PRO1300 PRO1300h c PRO1100e TCE PRO1300 TCE PRO1300h c TCE 101 Production Drive Harrison OH 45030 877 278 2797 fax 877 289 2963 cs aquaprosystems com www aquaprosystems com OWNER S MANUAL MANUAL DEL USUARIO ...

Страница 2: ... ...

Страница 3: ...micals known to the State of California to cause cancer and birth defects or other reproductive harm Wash hands after handling GENERAL SAFETY INFORMATION The water in a pool or tub should never exceed 104ºF 40ºC A water temperature in excess of 104ºF is considered unsafe for all persons Lower water temperatures are recommended for extended use exceeding 10 15 minutes and young children Excessive w...

Страница 4: ...tant watering directly on the unit can void your warranty Condensation drain holes are provided in all units for adequate removal of condensation and rainwater ALL UNITS WILL HAVE CONDENSATION THIS SHOULD NOT BE MISTAKEN FOR A LEAK IN THE UNIT Plumbing Where freezing weather is encountered the detachable connection union provided must be installed immediately adjacent to the heater to facilitate s...

Страница 5: ...Memory Retention If the power is removed from the unit it retains the last set point displayed Connecting to a Remote System All Units Except Pro1100 This Pool Heater is compatible with all known remote systems in the industry The following models diagrams show how to connect all of the remote systems to the Electronic Temp Controller For 2 wire remotes 1 Bring up POL setting and arrow temperature...

Страница 6: ...ting the knob during this cycle may reset the time delay causing the unit to wait an additional five minutes prior to startup Water Temperature Set Point Temperature set point range is 45 F to 107 F Rotating the thermostat knob clockwise will increase the temperature set point while rotating counterclockwise will decrease the temperature set point A floating thermometer may be placed in the pool o...

Страница 7: ...ck Black Red H C F Red Blue FAN Black Black White PRO1100e and PRO1300 Phone 877 278 2797 5 www aquaprosystems com To Remote System If Applicable Figure 6 PRO1300h c wiring diagram Water Sensor Defrost Sensor High Pressure Switch Closed OK Opened High Pressure Low Pressure Switch Closed OK Opened Low Pressure Flow Switch Closed Flow Opened No Flow Red Black MY TECH PH 111A Brown Brown White FAN SP...

Страница 8: ...the TCE will always run the heat pump for 15 minutes every 4 hours to determine if more heat is needed to maintain the pool s desired temperature even if all of the available run time was used in previous cycles This provides a couple of added benefits Pools will lose most of their heat at night if left uncovered however since the unit is checking for and adding heat when needed it prevents long r...

Страница 9: ... of checking if heat is needed every 4 hours It will do this by running the pump and filter system for 15 minutes If heat is needed it will continue to run until the pool has reached the set temperature If no heat is needed the system will turn off and continue checking for heat every 4 hours This provides a couple of added benefits Pools will lose most of their heat at night if left uncovered how...

Страница 10: ...aporator coil Selecting Functionality of Unit This unit is capable of operating as a Time Clock Override or as the Time Clock Eliminator If you already have a time clock on your swimming pool and would like to maintain its normal operation with the added benefit of a heat pump time clock override please review the section for the Time Clock Override If you do not own a time clock for your pool sys...

Страница 11: ... a time clock please refer back to the Time Clock Eliminator section The pump must be connected to the heat pump and also the time clock for the Time Clock Override feature to work correctly See the optional TCO wiring schematic for electrical connections This unit is prepared at the factory with the FIL mode set to the off position You will need to set the heat pump s hours of run time in the FIL...

Страница 12: ...ans there is not enough water flow to activate the water pressure switch The cause could be from a clogged filter or a manual by pass is in the wrong position and is not allowing water into the heater Once the filter has been cleaned or the by pass has been changed to allow water to flow through the heater the FLO display will go away and the water temperature will appear on the display HP This co...

Страница 13: ...ke sure the outside ambient temperature is higher than 50ºF 38 F for h c units Make sure the 5 minute time delay has passed FOR TCE UNITS Make sure time setting in FIL mode is not set to OFF Unit is running but not heating Check the air coming out of the top of the unit It should be approximately 8ºF 15ºF lower than the surrounding ambient air temperature If not call AquaPRO Systems for service Un...

Страница 14: ...EXCLUSIVE REMEDY AND ANY LIABILITY FOR ANY AND ALL INDIRECT OR CONSEQUENTIAL DAMAGES OR EXPENSES WHATSOEVER IS EXCLUDED Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusions or limitations of incidental or consequential damages so the above limitations might not apply to you This limited warranty gives you specific legal rights and you may also h...

Страница 15: ...ºC 98 6ºF Los síntomas de hipertermia incluyen mareos desmayos adormecimiento letargo y un aumento de la temperatura interna del cuerpo Los efectos de la hipertermia incluyen desconocimiento del peligro inminente falta de percepción del calor falta de reconocimiento de la necesidad de salir de la piscina o de la tina incapacidad física para salir de la piscina o de la tina daño al feto en mujeres ...

Страница 16: ...ad cuando sea necesario La unidad debería colocarse sobre una superficie sólida y nivelada con un mínimo de 91 5 cm x 91 5 cm 36 in x 36 in para un drenaje adecuado Asegúrese de que no haya ningún regador rociando agua directamente en la unidad Aunque las bombas de calor están diseñadas para entornos al aire libre no están concebidas para tener regadores de agua rociándolas constantemente NOTA Est...

Страница 17: ...go del punto de ajuste es apagado OFF y de 16 38 C 61 F a 104 F Si presiona los botones de flecha ARRIBA o flecha ABAJO esto le indicará al control que muestre el punto de ajuste actual Si mantiene presionado el botón ARRIBA o ABAJO permitirá desplazar los valores del punto de ajuste hasta alcanzar el punto de ajuste deseado Una vez que haya alcanzado el nuevo punto de ajuste suelte el botón ARRIB...

Страница 18: ...o No gire la perilla del termostato durante este tiempo de retardo Si gira la perilla durante este ciclo se podría reiniciar el tiempo de retardo provocando que la unidad demore cinco minutos adicionales antes de comenzar a funcionar Punto de ajuste de la temperatura del agua El rango del punto de ajuste de la temperatura es de 7ºC a 42ºC 45ºF a 107ºF Si gira la perilla del termostato hacia la der...

Страница 19: ...oto si aplica PRO1100e and PRO1300 PRO1300 PRO1100e PRO1300h c PRO1100 PRO1300h c TCE PRO1300 TCE PRO1100e TCE Figura 6 PRO1300h c diagrama de cableado Sensor de agua Sensor de descongelado Interruptor de alta presión Cerrado OK Abierto Alta presión Interruptor de baja presión Cerrado OK Abierto Baja presión Interruptor de flujo Cerrado Flujo Abierto No hay flujo Roja Negro MY TECH PH 111A Castaño...

Страница 20: ... calentador pondrá en funcionamiento el sistema a diario y por el tiempo de funcionamiento que usted ha seleccionado La secuencia de tiempo empieza al momento de arranque inicial Si la piscina se encuentra a la temperatura de funcionamiento deseada o por encima de la misma el calentador pondrá en funcionamiento el sistema por las horas deseadas cada día y distribuirá el tiempo igualmente en 6 perí...

Страница 21: ...ado Azul Gris 12V CA Azul Rojo Azul Transformador 12 24V CA Negro Amarillo Amarillo 24V CA COMPRESOR R S C Bobina del interruptor automático del compresor de 24V CA Condensador de func L1 L2 Negro Negro Amarillo Negro Negro Rojo H C F Rojo Axul VENTILADOR Negro Negro Blanco 24V CA Bobina del interruptor automático de la bomba de piscina L4 Bomba de la piscina L3 To Remote System If Applicable Inte...

Страница 22: ...de calefacción Si desea el modo de enfriamiento presione el botón SET configuración hasta que se muestre la pantalla H C Luego presione los botones de las flechas hasta que aparezca COL en la pantalla Esto hace que la unidad se coloque en modo de enfriamiento El punto de ajuste de la temperatura del agua será la temperatura del agua a la que la unidad está enfriando el agua Cuando la unidad está e...

Страница 23: ...6 períodos Esto permite un mejor funcionamiento del filtro y le permite al calentador de ajustar la temperatura del agua 6 veces al día Si la piscina necesita calor el calentador sigue operando el sistema hasta que alcance la temperatura deseada Si el tiempo de funcionamiento excede el tiempo de funcionamiento de un período el tiempo en exceso viene sustraído del los tiempo s de funcionamiento sig...

Страница 24: ...rriba y abajo ajuste las horas a 2 El rango de horas es de off apagado a 2 3 4 hasta 23 horas a on encendido Cuando se selecciona 2 la bomba de calor trabaja por 20 minutos cada 4 horas controlando si hace falta calor La unidad viene de fábrica con el modo FIL apagado OFF Pautas de aplicación todos los modelos Mantenimiento Todas las bombas de calor están diseñadas para uso en espacios exteriores ...

Страница 25: ...aja o interruptor de presión baja O bien la temperatura ambiente exterior es demasiado baja para que el calentador funcione o la unidad tiene poco refrigerante O bien la temperatura exterior está por debajo de 10ºC 50ºF 3 C 38 F para las unidades h c que es demasiado baja para que la calefacción funcione o el nivel de refrigerante de la unidad está bajo Cuando la temperatura exterior haya aumentad...

Страница 26: ...ese de que el ajuste de tiempo esté en el modo FIL y no en OFF La unidad está funcionando pero no calienta Verifique el aire que sale de la parte superior de la unidad Debería tener aproximadamente de 13ºC a 9ºC 8ºF a 15ºF menos que la temperatura del aire ambiente del entorno Si no es así llame a AquaPRO Systems para solicitar servicio La unidad no enfría PARA UNIDADES h c Asegúrese de que P S es...

Страница 27: ... A 1 UN AÑO A PARTIR DE LA FECHA DE COMPRA ÉSTE ES EL RECURSO EXCLUSIVO Y SE EXCLUYE CUALQUIER RESPONSABILIDAD POR TODO Y CUALQUIER DAÑO INDIRECTO O CONSECUENTE O GASTOS AFINES Algunos estados no permiten limitaciones sobre la duración de las garantías implícitas o no permiten la exclusión ni la limitación de daños incidentales o consecuentes por lo tanto es posible que las limitaciones anteriores...

Страница 28: ...Manual de Instrucciones Notes Notas ...

Отзывы: