background image

Copyright© 2016 Aqua Logic, Inc.   Effective date of 1/2016  

 

 

CHILLER CONTROL PROGRAMMING 

 

Step 

Enunciator 

Description 

Display 

F or C 

Fahrenheit or Celsius 

S1 (Blinking) 

Setpoint Temperature 

S1

   

77

 

DIF (Blinking) 

Differential Temperature 

DIF      

1

 

C1 or H1 

Cooling or Heating Mode 

C1 

 

Liquid Crystal Display (LCD) 

 

The LCD display provides a constant readout of the sensor temperature and indicates if the output relay is energized.  When the

 S1

 

enunciator is constantly Illuminated during operation, the relay is energized.  the display is also used in conjunction with the keypad to 
allow the user to adjust the set point temperature, differential and heating /cooling modes. 
 

Programming Steps and Display 

The control can be programmed in four simple steps using the LCD display and the three keys on the face of the control.  (See photo 
for display and keys.) 

 
1.  To start programming, press the

 SET

 key once to access the Fahrenheit/Celsius mode.  The display will show the current status, 

either 

F

 for degrees Fahrenheit or

 C

 for degrees Celsius. Then press either the up 

 

arrow or down

 

 

arrow key to toggle between 

the 

F

 or

 C

 designation. 

2.  Press the

 SET

 key again to access the set point temperature.  The LCD will display the current set point temperature and the set 

point enunciator will be blinking on and off to indicate that the control is in the set point mode. Then press either the up 

 key to 

increase or down 

 key to decrease the set point to the desired temperature. 

3.  Press the SET key again to access the differential.  The LCD will display the current differential and the 

DIF 

enunciator will be 

blinking on and off to indicate that the control is in the differential mode. Then press either up 

 key to increase or the down 

 key 

to decrease the differential to the desired setting (minimum 1°F, maximum 30°F). 

4.  Press the

 SET

 key again to access the heating mode.  The LCD will display the current mode, 

C1

 for chiller mode. Press the 

SET

 

key once more and programming is complete.  Controller 

MUST

 in the

 C1 

mode for correct operation. 

 

Controller will automatically drop out of “program mode” and return to “operating mode” 30 seconds after last key press.

 

Troubleshooting Controller Error Messages: 

 

Display Messages 

 

E1

 - Appears when the up 

 or down 

key is pressed when not in the programming mode.  

To correct:

  If the E1 message appears even when no keys are being pressed, replace the control. 

 

E2

 - Appears if the control settings are not properly stored in memory.  

To correct:  

Check all settings and correct if necessary. 

 

EP 

- Appears when the probe and or flow switch is open , shorted or sensing a temperature that is out of range. 

To correct:

  Check to see if the sensed temperature is out of range. If not , check for probe damage by comparing it to a known ambient 

temperature between  -30°F and 220°F. Replace the probe is necessary. Also check for proper water flow through heater. If water flow is correct, 
flow switch. 

 

EE

 - Appears if the EEPROM data has been corrupted.  

To correct: 

 This condition cannot be field repaired. Replace the control. 

 

CL 

- Appears if calibration mode has been entered. 

To correct: 

 Remove power to the control for least five seconds. Reapply power. If the

 CL

 message still appears, replace the control 

 
 

Содержание DS-10-WCMD

Страница 1: ...__________ Installation and Maintenance Manual For Delta Star Water cooled Marine Duty In Line Water Chillers Models DS 4 WCMD thru DS 10 WCMD DS 9 WCMD shown Use Quick Install page for easy setup Aqu...

Страница 2: ...components to assemble equipment that will operate faithfully for years You can call us or visit us on the web for technical assistance before and after the sale We are committed to making sure that y...

Страница 3: ...repair if necessary Be sure that the water flow through your Aqua Logic Chiller goes into the water inlet bottom and out the top to prevent potential damage see illustration If you use flexible hose t...

Страница 4: ...er fittings for leaks Apply electrical power to the chiller Adjust the controller to the desired water temperature See Operation and Programming Important Regulate condenser water until pressure on th...

Страница 5: ...ss the differential The LCD will display the current differential and the DIF enunciator will be blinking on and off to indicate that the control is in the differential mode Then press either up key t...

Страница 6: ...a temperature controller on the lights to shut them off and to sound off an alarm if water temperature rises more than 5 F above the Chiller set point Keep a spare pump on hand in case your primary p...

Страница 7: ...anics slime Remove power from the Chiller Wear protective eyewear clothing and gloves Mix a solution of 1 part unscented chlorine bleach to 4 parts water For a Delta Star Chiller use a small pump pail...

Страница 8: ...4050 115 7 2 R 134A 10 20 3 5 23 x 14 x 14 75 DS 5 WCMD 1 2 6000 115 9 5 R 134A 12 25 3 5 1 1 24 x 16 x 16 125 DS 6 WCMD 1 2 6000 230 4 8 R 134A 12 25 3 5 1 1 24 x 16 x 16 125 DS 7 WCMD 3 4 9500 115 1...

Страница 9: ...or maintenance by user or their agent Damage caused due to misapplication of product Damage caused by corrosion abuse accident alteration or improper use Damage caused by flood fire earthquake tornado...

Отзывы: