Serie

TE

HP & 

TE

HPS

TE/HP

TE/HPS

XTE/HP & 

XTE/HPS

ESPAÑOL

Manual de Instalación, 

Operación & Mantenimiento

Dispositivo Protector contra Sobretensiones en DC

V

Riesgo en la conexión y puesta a tierra

Verifique que el conductor de neutro en la acometida del equipo 

está conectado a tierra de acuerdo con el Código Eléctrico 
Nacional (NEC

®

) y todos los códigos aplicables.

Verifique que el terminal de neutro (XO) al lado secundario de los 

transformadores de distribución está aterrizado con el sistema de 
puesta a tierra de acuerdo con el NEC

®

 y todos los códigos aplicables.

Durante la instalación en un sistema eléctrico el DPS no debe ser 
energizado hasta que el sistema eléctrico esté completamente 
instalado, inspeccionado y probado. Todos los conductores 
deben estar conectados incluyendo el neutro (de ser requerido). 

El voltaje nominal del DPS y el sistema debe ser verificado antes 

de energizar el DPS.

El incumplimiento de estas indicaciones puede conducir de modo 
anormal altos voltajes en el DPS. Esto puede hacer que el DPS 
falle. La garantía es anulada si el DPS es instalado incorrectamente 

La Seguridad Primero - Voltaje Peligroso y Riesgo de Choque Eléctrico

PRECAUCION – IMPORTANTE – POR FAVOR LEA ESTE DOCUMENTO

• Sólo Electricistas calificados autorizados podrían instalar o dar servicio a un DPS

• Existe un nivel de voltaje peligroso dentro del DPS
• Un DPS nunca debe ser instalado y revisado cuando esté energizado ó durante 

 tormentas eléctricas

• Tomar precauciones de seguridad adecuadas incluyendo Equipo de Protección Personal
• El no seguir las siguientes instrucciones puede causar la muerte, serias lesiones,  

• 

y/o el daño de equipo

• Este manual debe ser leído completamente antes de la instalación

y/o si el conductor neutro en el equipo de la acometida o aguas 
debajo de los sistemas tomados separadamente no está 
conectado a la puesta a tierra conforme al NEC

®

.

No haga pruebas de sobretensión (Hi-pot) a los DPSs

Cualquier prueba en fábrica o en sitio del equipo de distribución de 
potencia que exceda el voltaje normal de operación como pruebas 
de aislamiento de alto potencial, o cualquier otra prueba donde 
los componentes de supresión vayan a ser sometidos a un voltaje 
más alto que su Voltaje nominal Máximo Continuo de operación 
(MCOV) se deben llevar a cabo con el DPS desconectado de la 
fuente de energía. Para sistemas de 4 hilos, la conexión de neutro 
en el DPS también debe ser desconectada antes desarrollar la 
prueba de alto potencial y luego reconecte después de terminada 
la prueba.

El no desconectar el DPS y los componentes asociados durante 
pruebas de elevado voltaje dañarán el DPS y anulará la garantía.

Содержание TE/1HP

Страница 1: ... Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if Safety First Hazardous Voltage Shock Hazard WARNING IMPORTANT PLEASE READ WARNING Only qualified licensed electricians should install or service SPDs Hazardous voltages exist within SPDs SPDs should never be installe...

Страница 2: ...h ground Then they reset automatically and wait for the next surge This is similar to the pressure relief valve on a water heater pressure goes up valve opens to relieve pressure and then resets In an electrical system an SPD senses overvoltage shorts temporarily sending energy to ground and then resets SPDs are capable of repeating this function thousands of times Precautionary Statement Regardin...

Страница 3: ... Phase B ORNG Neutral WHT Phase C BLK Ground GRN V V Neutral WHT Hot BLK Ground GRN Phase A BLK Phase C BLK Phase B BLK Ground GRN V Phase A BLK Phase C BLK Ground GRN V TE Transient Eliminator Listed Type 2 SPD in NEMA 1 3R 04 12 enclosure XTE Transient Eliminator Recognized Type 4 SPD on backplane for installation within gear in Type 2 installation display on 6 cable Common North American System...

Страница 4: ...to keep leads short and straight As distribution gear becomes larger shorter leads are more difficult to accomplish When longer leads are unavoidable gently twist leads together one to two twists per foot or tie wrap leads together Tip surges create magnetic fields per the right hand rule When current goes in direction of thumb magnetic field is in direction of curl of fingers As surge current goe...

Страница 5: ...ems neutral to ground bonding Main Bonding Jumper must be installed per the NEC Failure to do so WILL damage SPDs Internal Mounting of XR and XW Component SPD XTE versions of the HP and HPS families are essentially TE HPSs without enclosures XTE HPs and XTE HPSs are intended for installation within host electrical equipment having suitable enclosures The experienced integrator will appreciate the ...

Страница 6: ...stallation 3 Remove power for panel Confirm panel is deenergized 4 Identify connection breaker location and SPD location 5 Make sure leads are short Reducing inches matter Pretend that connector leads cost you 1000 foot to make leads short 6 Remove an appropriately sized knockout from panel Create an appropriately sized hole in the SPD enclosure 7 Mount SPD 8 Connect conductors as appropriate shor...

Страница 7: ...BLK Phase B ORNG Neutral WHT Phase C BLK Ground GRN V TE 51HP TE 61HP TE 91HP CORNER GROUND DELTA B grounded 2 Hots 1 Grnd Phase A BLK Phase C BLK Ground GRN V TE 5HP TE 9HP Phase A BLK Phase C BLK Phase B BLK Ground GRN V DELTA HRG WYE 3 Hots 1 Grnd TE 2HP TE 4HP TE 7HP TE 8HP WYE 3 Hots 1 Neu 1 Grnd Phase A BLK Phase B BLK Neutral WHT Phase C BLK Ground GRN A C N V B ...

Страница 8: ...ons consider asking the Authority Having Jurisdiction AHJ Some AHJ s appreciate SPD safety benefits on smoke detectors medical equipment security equipment etc Similarly some AHJ s appreciate the financial distress of failed microelectronic loads Depending on situation anAHJ might approve the lesser of two evils OPERATION Control and Diagnostic Panel All indicators and controls are located on the ...

Страница 9: ...n 6 Form C Set 2 Form C Set 1 1 Normally Closed 2 Common 3 Normally Open 4 Normally Closed 5 Common 6 Normally Open 7 Connected to Pin 4 8 Connected to Pin 5 9 Connected to Pin 6 1 2 3 4 5 6 7 8 9 Form C Set 2 Form C Set 1 Dry Contact Option Two sets of Form C dry contacts are included with the Dry Contact option Dry Contacts change state during inoperative conditions including loss of power Any s...

Страница 10: ...hstand severe duty However there are various electrical anomalies that SPDs cannot protect against These are generally Sustained Overvoltages also known as Temporary Overvoltages TOVs In this context Sustained Overvoltages may be only a few cycles Failed SPDs tend to be symptoms not root causes A failed SPD should be treated as a canary in the coalmine suggesting further investigation as there may...

Страница 11: ...11 Figure 9 MODULE REMOVAL REPLACEMENT ...

Страница 12: ...12 Figure 10 TROUBLESHOOTING FLOWCHART ...

Страница 13: ...e estas indicaciones puede conducir de modo anormal altos voltajes en el DPS Esto puede hacer que el DPS falle La garantía es anulada si el DPS es instalado incorrectamente LaSeguridadPrimero VoltajePeligrosoyRiesgodeChoqueEléctrico PRECAUCION IMPORTANTE POR FAVOR LEA ESTE DOCUMENTO Sólo Electricistas calificados autorizados podrían instalar o dar servicio a un DPS Existe un nivel de voltaje pelig...

Страница 14: ... momentáneo para redireccionar la energía dañina del sobrevoltaje a la puesta a tierra Ellos reinician automáticamente y esperan el siguiente sobrevoltaje Esto es similar a la válvula de alivio de presión sobre un calentador de agua la presión sube la válvula abre para relevar la presión y luego reinicia En un sistema eléctrico el DPS detecta un sobrevoltaje cortos temporales envían energía a la p...

Страница 15: ...N V V Neutral WHT Hot BLK Ground GRN Phase A BLK Phase C BLK Phase B BLK Ground GRN V Phase A BLK Phase C BLK Ground GRN V TE DPS Listado Tipo 2 en NEMA 1 3R 04 12 XTE DPS reconozido Tipo 4 instalado en placa demetal para Sistemas más comunes en Norte América 1 240 120V Split Phase 1Ø 3W Grnd Fig 1 2 208Y 120V Wye 3Ø 4W Grnd Fig 2 3 240 120V High Leg Delta B High Fig 3 4 480Y 277V Wye 3Ø 4W Grnd F...

Страница 16: ...argo entorche con cuidado los conductores juntándolos una a dos vueltas por pie 30 cms o utilice amarras bridas plásticas para juntar los cables TIP las sobretensiones crean campos magnéticos según la regla de la mano derecha Cuando la corriente entra en la dirección de pulgar el campo magnético está en la dirección que cierran los dedos De la manera como la corriente de la sobretensión va al DPS ...

Страница 17: ...e tierra un conductor aislado para el sistema de puesta a tierra debe ir dentro del ducto y el tamaño de acuerdo con el NEC Se debe mantener una adecuada continuidad eléctrica en todas las conexiones de circuito No use bujes aislados para interrumpir el recorrido un ducto metálico No se recomienda a una tierra aislada separada para el DPS Las conexiones adecuadas de equipos al sistema de puesta a ...

Страница 18: ... DPS tiene contacto seco Monitoreo Remoto o Remote Display antes de planificar su instalación 3 Desconecte la alimentación para el panel Confirmar el panel se desactiva 4 Identificar la conexión localización del interruptor y la ubicación del DPS 5 Asegúrese de que los cables son cortos 6 Remueva apropiadamente los orificias del panel Abra unos orificios de adecuado tamaño el el encapsulado del DP...

Страница 19: ...nd Phase A BLK Phase B ORNG Neutral WHT Phase C BLK Ground GRN V TE 51HP TE 61HP TE 91HP CORNER GROUND DELTA B grounded 2 Hots 1 Grnd Phase A BLK Phase C BLK Ground GRN V TE 5HP TE 9HP Phase A BLK Phase C BLK Phase B BLK Ground GRN V DELTA HRG WYE 3 Hots 1 Grnd TE 2HP TE 4HP TE 7HP TE 8HP WYE 3 Hots 1 Neu 1 Grnd Phase A BLK Phase B BLK Neutral WHT Phase C BLK Ground GRN A C N V B ...

Страница 20: ...s indicadores y los controles están situados en la parte frontal de diagnóstico panel Cada fase cuenta con un indicador LED verde LEDs verdes indicar que funciona correctamente Si una condición inoperativa llegara a ocurrir en el HPS el verde LED s se apagará Si una condición inoperante se produjera en la HP la incorporada en el alarma sonará y el Servicio de LED rojo se encenderá Esto indica que ...

Страница 21: ...ador a cero 0 MUESTRA DE DIAGNÓSTICO Phase B Phase C Service Phase A Advanced Protection Technologies Test Count Reset Silence Surge Counter Phase C Service Phase B Phase A Surge Counter Advanced Protection Technologies Silence Test Count Reset Figura 5 DIGRAMA PARA PINES EN LOS CONTACTOS SECOS Usado el conector DB 9 Por favor tenga en cuenta Los contactos Secos son diseñados para bajo voltaje o s...

Страница 22: ...o Por favor póngase en contacto con nosotros para cualquier situación relacionada con el servicio Queremos estar atentos a cualquier problema La Calidad de los DPSs debe soportar un régimen severo e intenta proteger su carga hasta fallar Hay anomalías eléctricas contra las cuales DPSs no puede proteger Estas son generalmente Sobretensiones sostenidas también conocidas como Sobretensiones Temporale...

Страница 23: ...Figura 9 REEMPLAZO DEL MODULO 11 ...

Страница 24: ...cta Posible fallas en la tarjeta de diagnóstico llamar APT Están los modules en cortos Reemplace el módulo malo fusible u otro módulo en la fase Adecuada Operación Reemplace fusible Energize el DPS y verifique adecuada operación DPS no operá correctamente Posible mal funcionamiento en la tarjeta de diagnóstico llamar APT Desconecte los cables del neutro blanco del terminal PCB y revise los módulos...