18
Output
220V(option)
230V(default)
240V(option)
50HZ(default)
60HZ(option)
Battery
1.Lead
acid battery(default)
2.Lithium(option)
3.No Bat: no battery(option)
4.User: (option)
4.1. If “User-Defined” is selected, Bulk
charging voltage and Floating charging
voltage, setting range: 48.0V to 60V,
Increment of each click is 0.1V.
4.2. if you have a lithium battery, you can
choose this option.
4.3.if the BMS communication is
connected between the inverter and the
lithium battery, the display battery icon will
display “USER”.
Battery
1.Low Vol Disconnect:
Setting voltage point back to utility source
when selecting “Solar” or “Battery”.
setting range :44.0V to 51V, Increment of
each click is 0.1V.
2.
Shutdown Vol
Setting range is from 42.0V to 48.0V.
Increment of each click is 0.1V.
3.
High Vol Reconnect:
Setting voltage point back to battery mode
when selecting “Solar” or “Battery” .setting
range: 48.0V to 58V, Increment of each
click is 0.1V.