Once all the electrical connections have been made, carry out the initial operation tests, adjust the motor run timer
09
for a period of
4-5 seconds more than the real gate opening time; the dwell timer
08
, and the leaf closure delay
07
(Pic. 10)
In order to set automatic or semiautomatic operation, flick the Dip-switch B:
-
Automatic Operation
: with dip-switch lever No. 3 in the
ON
position, once the opening pulse has been given (contact 4 and 8 on the
Elpro 13 CEI programmer terminal box), the gate opens and dwells for the time set by the potentiometer 08, then closes automatically.
-
Semiautomatic Operation
: with dip-switch lever No. 3 in the
OFF
position, once the opening pulse has been given, the gate opens,
while a closing pulse must be given in order to close in (contact 5 and 8 on the Elpro 13 CEI programmer terminal box).
-
Radio Contact
: contact 7 and 8 on the Elpro 13 CEI electronic programmer terminal box (Pic. 10), the automation reverses the movement
that it is carrying out upon every pulse from the keyswitch, the transmitter or the wall push buttons (it is advisable to read the instructions
leaflet enclosed with the electronic programmer carefully).
WARNING: If the electric motors have insufficient drive power due to shortage of electric current, add two 12
µ
F capacitors (one for
each electric motor), connecting them in parallel to the individual electric motor phases.
13
CEI
FOR SWING GATES - SINGLE-PHASE
Drwg. No.
2014
230 V - 25 W max
FLASHING LAMP
COMMON
COMMON
ELECTRIC MOTORS
SINGLE-PHASE
230 V SINGLE-PHASE
SUPPLY VOLTAGE
CAPACITORS
CUT OFF SWITCH
BY COVER KNOB
1 Amp. FUSE:
24 V OUTPUT
TERMINALS 12 - 13
LEAF DELAY
TIMER
CLOSE
DWELL TIME
MOTOR RUN
TIME OPEN
& CLOSE
ON TO “0” THE DELAY
IS OUT OF SERVICE
MICROPROCESSOR
DIP-SWITCH
TERMINALS FOR THE
CONNECTION OF THE
PUSH BUTTONS PULIN 3
RADIO CONTROL
PLUG-IN CARD SUPPORT
24 V OUTPUT
1
°
CHANNEL
ON
OFF
N.W.: THIS PANEL IS TESTED TO OPERATE GATES ONLY THROUGH FADINI
ACCESSORIES. NO GUARANTEE FOR ACCESSORIES OF OTHER MAKE OR
SPECIAL APPLICATIONS.
PEDESTRIAN MODE
ONE PULSE OPENS
ONE GATE LEAF ONLY
PULSE TWICE
CONSECUTIVELY TO OPEN
BOTH GATE LEAFS
ALL OPERATIONS
OPEN, CLOSE & REVERSE
RADIO CONTACT
N. W.: for special applications, ie. to switch on lights - CCTV etc…, SOLID
STATE RELAYS are recommended to be used only.
Standard relays would affect the micro-processor.
12,5
µ
F
12,5
µ
F
B
Should more pairs of photocells be required
than the recommended quantity
, fit an
auxiliary transformer outside the control box.
LED 1: LIGHTS UP WHEN THE CARD IS POWERED
LED 2: SWITCHES OFF WHEN THERE IS AN OBSTACLE IN FRONT
OF THE PHOTOCELLS
LED 3: OPEN. LIGHTS UP UPON OPENING PULSE
LED 4: CLOSE. LIGHTS UP UPON CLOSE PULSE
LED 5: STOP, SWITCHES OFF UPON STOP PULSE
LED 6: RADIO, LIGHTS UP UPON EVERY RADIO PULSE
OPEN SWITCH N.O. CONT
ACT
COMMON
N.C. CONT
ACT
.
PHOTOCELLS
CLOSE SWITCH N.O. CONT
ACT
STOP SWITCH N.C. CONT
ACT
RADIO CONT
ACT N.O.
COMMON
VOL
TAGE OUTPUT
ELECTRIC LOCK SUPPL
Y
24 V - 3 W max. INDICA
TOR
24 V
ac OUTPUT
Max. permitted load:
2 pairs photocells
1 radio receiver
-PHOTOCELLS 2
nd
P
A
IR-
INSIDE PHOTOCELLS N.C. contact. If
obstructed, they prevent the gates from
opening, reverse gate direction during
close cycle.
+
7
8
9
+
+
FADINI
26
27
28
3
4
7
8
ON
1 2
4
3
5 6 7 8
1
2
3
4
5
6
M1
16
25
24
23
22
21
20
19
18
17
M2
5 Amp.
FUSE
4
3
2
1
13
12
11
10
9
8
7
6
5
5 Amp.
FUSE
630 mA
FUSE
F4
F2
F3
F1
630 mA
FUSE
FLASHING
LAMP
F5
0
Содержание 280/700 STRONG
Страница 1: ...G B INSTALLATION MANUAL...