SETUP & TESTING

INSTALLER SYSTEM TEST

WI-FI SETUP

The Installer Test can be accessed from 
the Installer Menu . All equipment outputs 
that are configured in the installer settings 
can be turned on and off for testing 
equipment . Minimum on and off times are 
not enforced while in this mode .

For detailed instructions for connecting the thermostat to a Wi-Fi network and registering it  

to an Aprilaire account, refer to the Wi-Fi Quick Start Guide included in the box.

QUICK REFERENCE TO CONTROLS & DISPLAY

HOME SCREEN

MAIN MENU

NOTE:

 SCREEN BRIGHTENS AFTER FIRST TOUCH .

OUTDOOR 

TEMPERATURE 

& HUMIDITY  

(IF INSTALLED)

SET SCREEN 

BRIGHTNESS 

AND SCREEN 

SAVER

HEATING AND 

COOLING 

EQUIPMENT 

STATUS

SET DATE & TIME

HOLD MENU 

& STATUS

CONNECT TO 

WI-FI NETWORKS

SYSTEM MODE 

SELECTION

SET SCHEDULE

DETAILED 

EQUIPMENT STATUS

HEAT BLAST MODE & 

STATUS (IF INSTALLED)

WEATHER FORECAST 

& ALLERGY REPORT

VIEW CONTRACTOR 

INFORMATION OR 

ACCESS INSTALLER 

MENU WITH  

10 SECOND PRESS 

& HOLD

ACTIVE ALERTS & 

ALERT SETTINGS

SET VACATION 

HOLDS

CURRENT SCREEN 

RELATED HELP

MAIN MENU 

HUMIDIFIER AND 

OR DEHUMIDIFIER 

INDOOR AIR 

QUALITY SCREEN 

& SIMPLE STATUS

AIR CLEANING 

INDOOR AIR 

QUALITY SCREEN 

& SIMPLE STATUS

COOL SETTING

CURRENT DATE AND TIME 

(AUTOMATICALLY UPDATED IF 

CONNECTED TO INTERNET)

WI-FI INDICATOR 

(STROBES IN 

SETUP MODE)

FRESH AIR INDOOR 

AIR QUALITY 

SCREEN & SIMPLE 

STATUS

TEMPERATURE 

SCALE, LOCKOUTS, 

AWAY MODE 

SETTING  

(IF ENABLED)

AWAY MODE & 

STATUS (IF INSTALLED)

FAN MODE 

SELECTION

CLEAN DISPLAY 

(TOUCHSCREEN 

IS OFF FOR  

30 SECONDS)

ROOM TEMPERATURE 

& HUMIDITY

HEAT SETTING

THERMOSTAT NAME

System setting

Description

Factory default setting (bold)  

and setting range

Enable Low Vent 

Temperature Limit

Enables low ventilation temperature lockout limit . (Only 

available if Outdoor Sensor is set to Installed .)

No

Yes 

Low Vent Temperature 

Limit

Sets low ventilation temperature lockout limit . (Only available 

if Enable Low Vent Temperature Limit is set to Yes .)

10°F (-12°C)

-10°F to 40°F (-24°C to 6°C)

HVAC Fan with Vent 

Selects if ventilation forces the fan on . (Yes with high and low 

limits is only available if Outdoor Sensor is set to Installed .)

Yes

Yes with high and low limits

No

Enable High Mixing 

Temperature

Enables high mixing temperature . (Only available is HVAC Fan 

with Vent is set to Yes with high and low limits .)

No

Yes

High Mixing 

Temperature

Sets the high mixing temperature . (Only available if Enable 

High Mixing Temperature is set to Yes .)

80°F or (26°C)

60°F to 105°F (14°C to 41°C)

Enable Low Mixing 

Temperature

Enables low mixing temperature . (Only available is HVAC Fan 

with Vent is set to Yes with high and low limits .)

No

Yes

Low Mixing 

Temperature

Sets the Low mixing temperature . (Only available if Enable 

Low Mixing Temperature is set to Yes .)

40°F (6°C)

0°F to 50°F (-18°C to 12°C)

Fresh Air Service 

Reminder

The period for displaying the “SERVICE FRESH AIR” message .

OFF

1 to 12 months or “OFF” to disable

English

 17

16 

English

Содержание 8920W

Страница 1: ...bles 10 12 General system settings table 10 Thermostat system settings table 11 12 Indoor Air Quality system settings tables 13 16 Humidifier system settings table 13 14 Dehumidifier system settings table 14 Air cleaning system settings table 15 Fresh air system settings table 15 16 Installer system test 16 Wi Fi setup 16 Quick reference to controls display 17 18 Thermostat features 18 Troubleshoo...

Страница 2: ...perature sensor should be mounted On an interior wall in a frequently occupied space Approximately 5 above floor At least 18 from outside wall Using less than 300 of wire Do not mount remote sensor Behind doors in corners or other dead air spaces In direct sunlight near lighting fixtures or other appliances that give off heat On an outside or unconditioned area wall In the flow of a supply registe...

Страница 3: ...2 sensor to the ODT terminals and enabling the outdoor sensor in the installer setup menu When an outdoor sensor is installed the features below will be enabled In heat pump mode the outdoor temperature sensor can be used to efficiently utilize an air source heat pump When the outdoor temperature is less than the Low Balance Point the heat pump will be locked out and only auxiliary heating will be...

Страница 4: ...OLING LOCATE SENSOR IN SHADED AREA CONVENTIONAL HEAT COOL TWO TRANSFORMER REMOVE JUMPER HEATING TRANSFORMER COOLING TRANSFORMER C R W W2 B Y Y2 O G L RH RC C 3 EQ HP HC G Y3 Y2 Y W3 W2 W TRANSFORMER THERMOSTAT 1 2 2nd COOLING 1st COOLING FAN 1st HEATING 2nd HEATING 3rd HEATING 3rd COOLING 1 R and C can be powered from the HVAC equipment transformer or any other constantly powered 24VAC source 1 RE...

Страница 5: ...FAULT DETECT REVERSING VALVE REVERSING VALVE 2nd HEATING 1st HEATING FAN 1st COMPRESSOR 2nd COMPRESSOR 2 1 1 R and C can be powered from the HVAC equipment transformer or any other constantly powered 24VAC source INDOOR AIR QUALITY WIRING DIAGRAMS INDOOR AIR QUALITY WIRING WITH SEPARATE TRANSFORMERS INDOOR AIR QUALITY WIRING WITH A SINGLE TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER VNT DH HUM ...

Страница 6: ...compressor stages Heat Pump mode only One Two Number of Auxiliary Heat Stages Select number of auxiliary heat stages Heat Pump mode only One Two Number of Stages of Heat Select number of heat stages Heat Cool mode only One Two Three Number of Stages of Cool Select number of cool stages Heat Cool mode only One Two Three Remote Temperature Sensor Installed Select if the remote sensor is attached and...

Страница 7: ...ettings are only present dependent upon the value of other settings The use of an outdoor temperature sensor recommended enables additional Indoor Air Quality functionality Please refer to the Model 8920W Owner s Manual for further information about thermostat features Note Refer to manuals for humidifier dehumidifier air cleaner and ventilation products for recommended installation and operation ...

Страница 8: ...y default setting bold and setting range Fresh Air Vent Installed Selects if ventilation is installed If set to No no other ventilation settings will be available No Yes Display Button Note only available if Fresh Air Installed is set to No Yes No Fresh Air Setup Type Selects if ventilation is configured through the Code setup or Comfort Comfort setup has more lockout options Code setting ensures ...

Страница 9: ...MPERATURE SCALE LOCKOUTS AWAY MODE SETTING IF ENABLED AWAY MODE STATUS IF INSTALLED FAN MODE SELECTION CLEAN DISPLAY TOUCHSCREEN IS OFF FOR 30 SECONDS ROOM TEMPERATURE HUMIDITY HEAT SETTING THERMOSTAT NAME System setting Description Factory default setting bold and setting range Enable Low Vent Temperature Limit Enables low ventilation temperature lockout limit Only available if Outdoor Sensor is ...

Страница 10: ...ting Equipment Type to make sure it is set to match the installed heating cooling equipment HEATING IS NOT DISPLAYED Check Installer Setting Control Setup is set correctly Change the System Mode to Heat and set the temperature level above the current room temperature COOLING IS NOT DISPLAYED Check Installer Setting Control Setup is set correctly Change the System Mode to Cool and set the temperatu...

Страница 11: ... to 50 R H Dehumidification 40 to 90 R H SPECIFICATIONS Electrical Operating voltage 24VAC 18 30VAC Current Maximum 2 5A total 1 0A single output Maximum surge current 5A Environment Temperature shipping 30 to 150 F 34 to 65 C Temperature thermostat operating 32 to 120 F 0 to 48 C Temperature equipment control module operating 32 to 158 F 0 to 70 C Relative humidity Operating 5 to 90 R H non conde...

Отзывы: