INSTALLATION

INSTALLATION

EQUIPMENT CONTROL MODULE WIRING

Wire specifications:

18-24 gauge thermostat wire

Installation notes:

•   Ensure power at the HVAC equipment is off . 
•   Loosen screw terminals, insert stripped wire 

and re-tighten .

•   Use zip tie to route wiring through the wiring 

channels .

– Connection to terminal 1 at thermostat

– Connection to terminal 2 at thermostat

– Connection to terminal 3 at thermostat

RAT 

– Return air temperature sensor (optional)

LAT 

– Leaving air temperature sensor (optional)

ODT 

– Outdoor temperature sensor (included)

C

 – 24VAC common

R

 – 24VAC

RC

 – 24VAC cooling

RH

 – 24VAC heating

W

 – First stage heat (conventional)/auxiliary (heat pump)

W2

 – Second stage heat (conventional)/ auxiliary (heat 

pump)

W3/B

 – Third stage heat (conventional)/reversing valve 

(heat pump)

Y

 – First stage cooling (conventional)/first stage compressor 

(heat pump)

Y2

 – Second stage cooling (conventional)/second stage 

compressor (heat pump) .

Y3/0

 – Third stage cooling (conventional)/reversing valve 

(heat pump)

G

 – Fan

L

 – System fault indicator (heat pump only) (optional)

C

EQ

 – 24VAC common from heat pump for system fault 

indicator (optional)

HUM

 – Humidifier

DHno & DHcom

 – Normally open dehumidifier control

DHnc & DHcom

 – Normally closed dehumidifier control

VENT

 – Ventilation

EAC

 – Electronic Air Cleaner

OUTDOOR TEMPERATURE SENSOR (INCLUDED)

OPTIONAL WIRELESS OUTDOOR TEMPERATURE AND HUMIDITY SENSOR

Outdoor temperature can be measured by installing an 8052 sensor to the ODT terminals and enabling the outdoor 
sensor in the installer setup menu . When an outdoor sensor is installed, the features below will be enabled .

In heat pump mode the outdoor temperature sensor can be used to efficiently utilize an air source heat pump:

•  When the outdoor temperature is less than the Low Balance Point, the heat pump will be locked out and only 

auxiliary heating will be used to provide heating . 

•  When the outdoor temperature is higher than the High Balance Point, the auxiliary heating will be locked out and 

only the heat pump will be used to provide heating .

Indoor Air Quality functions can use the outdoor temperature sensor to:

•  Control humidification setpoint based on outdoor temperature to prevent condensation
•  Lock out humidification for temperatures over 60°F or below -30°F .
•  Lock out ventilation based on high and/or low outdoor temperatures .
•  Display outdoor temperature on thermostat .

Outdoor temperature sensor should  

be mounted:

•  On side of building out of direct sunlight 

(north side recommended) .

•  Above snow line .
•  At least 3’ away from exhaust vents and 

condensing lines .

•  Using less than 300’ of wire .
•  Do not route wires along 120 VAC lines .

For installations where it is difficult to wire the included 8052 outdoor temperature sensor, a Model 8056 wireless 
outdoor sensor can be used . The Model 8056 module has two radio units, one that is placed on the equipment control 
module as shown below, and a second radio that is placed outside . See the Model 8056 Installation Instructions for 
detailed directions regarding installation .

Outdoor Sensor

English

 5

4 

English

Содержание 8920W

Страница 1: ...bles 10 12 General system settings table 10 Thermostat system settings table 11 12 Indoor Air Quality system settings tables 13 16 Humidifier system settings table 13 14 Dehumidifier system settings table 14 Air cleaning system settings table 15 Fresh air system settings table 15 16 Installer system test 16 Wi Fi setup 16 Quick reference to controls display 17 18 Thermostat features 18 Troubleshoo...

Страница 2: ...perature sensor should be mounted On an interior wall in a frequently occupied space Approximately 5 above floor At least 18 from outside wall Using less than 300 of wire Do not mount remote sensor Behind doors in corners or other dead air spaces In direct sunlight near lighting fixtures or other appliances that give off heat On an outside or unconditioned area wall In the flow of a supply registe...

Страница 3: ...2 sensor to the ODT terminals and enabling the outdoor sensor in the installer setup menu When an outdoor sensor is installed the features below will be enabled In heat pump mode the outdoor temperature sensor can be used to efficiently utilize an air source heat pump When the outdoor temperature is less than the Low Balance Point the heat pump will be locked out and only auxiliary heating will be...

Страница 4: ...OLING LOCATE SENSOR IN SHADED AREA CONVENTIONAL HEAT COOL TWO TRANSFORMER REMOVE JUMPER HEATING TRANSFORMER COOLING TRANSFORMER C R W W2 B Y Y2 O G L RH RC C 3 EQ HP HC G Y3 Y2 Y W3 W2 W TRANSFORMER THERMOSTAT 1 2 2nd COOLING 1st COOLING FAN 1st HEATING 2nd HEATING 3rd HEATING 3rd COOLING 1 R and C can be powered from the HVAC equipment transformer or any other constantly powered 24VAC source 1 RE...

Страница 5: ...FAULT DETECT REVERSING VALVE REVERSING VALVE 2nd HEATING 1st HEATING FAN 1st COMPRESSOR 2nd COMPRESSOR 2 1 1 R and C can be powered from the HVAC equipment transformer or any other constantly powered 24VAC source INDOOR AIR QUALITY WIRING DIAGRAMS INDOOR AIR QUALITY WIRING WITH SEPARATE TRANSFORMERS INDOOR AIR QUALITY WIRING WITH A SINGLE TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER VNT DH HUM ...

Страница 6: ...compressor stages Heat Pump mode only One Two Number of Auxiliary Heat Stages Select number of auxiliary heat stages Heat Pump mode only One Two Number of Stages of Heat Select number of heat stages Heat Cool mode only One Two Three Number of Stages of Cool Select number of cool stages Heat Cool mode only One Two Three Remote Temperature Sensor Installed Select if the remote sensor is attached and...

Страница 7: ...ettings are only present dependent upon the value of other settings The use of an outdoor temperature sensor recommended enables additional Indoor Air Quality functionality Please refer to the Model 8920W Owner s Manual for further information about thermostat features Note Refer to manuals for humidifier dehumidifier air cleaner and ventilation products for recommended installation and operation ...

Страница 8: ...y default setting bold and setting range Fresh Air Vent Installed Selects if ventilation is installed If set to No no other ventilation settings will be available No Yes Display Button Note only available if Fresh Air Installed is set to No Yes No Fresh Air Setup Type Selects if ventilation is configured through the Code setup or Comfort Comfort setup has more lockout options Code setting ensures ...

Страница 9: ...MPERATURE SCALE LOCKOUTS AWAY MODE SETTING IF ENABLED AWAY MODE STATUS IF INSTALLED FAN MODE SELECTION CLEAN DISPLAY TOUCHSCREEN IS OFF FOR 30 SECONDS ROOM TEMPERATURE HUMIDITY HEAT SETTING THERMOSTAT NAME System setting Description Factory default setting bold and setting range Enable Low Vent Temperature Limit Enables low ventilation temperature lockout limit Only available if Outdoor Sensor is ...

Страница 10: ...ting Equipment Type to make sure it is set to match the installed heating cooling equipment HEATING IS NOT DISPLAYED Check Installer Setting Control Setup is set correctly Change the System Mode to Heat and set the temperature level above the current room temperature COOLING IS NOT DISPLAYED Check Installer Setting Control Setup is set correctly Change the System Mode to Cool and set the temperatu...

Страница 11: ... to 50 R H Dehumidification 40 to 90 R H SPECIFICATIONS Electrical Operating voltage 24VAC 18 30VAC Current Maximum 2 5A total 1 0A single output Maximum surge current 5A Environment Temperature shipping 30 to 150 F 34 to 65 C Temperature thermostat operating 32 to 120 F 0 to 48 C Temperature equipment control module operating 32 to 158 F 0 to 70 C Relative humidity Operating 5 to 90 R H non conde...

Отзывы: