background image

5

This is intended to help protect the compressor from short cycling. 
Some newer compressors already have a time delay built in and 
do not require this feature. Your compressor manufacturer can tell 
you if the lockout feature is already present in their system. When 
the thermostat compressor time delay occurs it will fl ash the 

Snowfl ake

 and 

Flame icons

 for about fi ve minutes.

3.  

Select Temperature Display Adjustment 3 LO to 3 HI

 – 

Allows you to adjust the room temperature display up to 3° higher 
or lower. Your thermostat was accurately calibrated at the factory 
but you have the option to change the display temperature to match 
other temperature measuring devices. The current or adjusted room 
temperature will be displayed on the left side of the display.

4.  Press RUN to exit the menu and return to normal operation.

FIGURE 5 – Thermostat buttons, display and switches

CONFIGURATION MENU

The confi guration menu allows you to set certain thermostat operating 
characteristics to your system or personal requirements.

Press RUN to make sure the thermostat is in the run program mode, 
then press PRGM and RUN at the same time to enter the confi guration 
menu. The display will show the fi rst item in the confi guration menu.

The confi guration menu chart summarizes the confi guration options. 
An explanation of each option follows.

Press HOLD to change to the next menu item or press TIME to go 
backwards to the previous item in the menu. To exit the menu and return 
to the program operation, press RUN. If no keys are pressed within 
fi fteen minutes, the thermostat will revert to normal operation.

1.  

Select Fast or Slow Cycling

 – In the run mode, if the setpoint 

temperature is manually raised by 3°F (2°C) or more above the actual 
temperature with the TEMPERATURE UP key, and the fast second 
stage feature is enabled (FA on), the second stage will energize 
immediately. With FA off, second stage will not energize until the 
setpoint temperature is 1°F or more beyond actual temperature for 
more than ten minutes.

2.  

Select Compressor Lockout CL OFF or ON

 – Selecting CL ON 

will cause the thermostat to wait 5 minutes before turning on the 
compressor if the heating and cooling system loses power. It will 
also wait 5 minutes minimum between cooling and heating cycles. 

OPERATING FEATURES

Now that you are familiar with the thermostat buttons and display, 
read the following information to learn about the many features of 
the thermostat.

•  

SIMULTANEOUS HEATING/COOLING PROGRAM STORAGE

 – 

When programming, you can enter both your heating and cooling 
programs at the same time. There is no need to reprogram the 
thermostat at the beginning of each season.

•  

TEMPERATURE OVERRIDE

 – Press 

 or 

 until the 

display shows the temperature you want. The thermostat will 
override current programming and keep the room temperature at 
the selected temperature until the next program period begins. 
Then the thermostat will automatically revert to the program.

•  

HOLD TEMPERATURE

 – The thermostat can hold any 

temperature within its range for an indefi nite period, without 
reverting to the programmed temperature. Press HOLD button. 
HOLD will be displayed. Then choose the desired temperature 
by pressing 

 or 

. The thermostat will hold the room 

temperature at the selected setting until you press the RUN button 
to start program operation again.

•  

PROGRESSIVE RECOVERY

 – Progressive Recovery causes the 

thermostat to start heating or cooling early to make the room 
temperature reach the program setpoint at the time you specify. 
Heating will start 5 minutes early for every 1° of temperature 
required to reach setpoint.

  

Example:

 You select Progressive Recovery and have your 

heating programmed to 65° at night and 70° at 7 AM. If the 
room temperature is 65° the difference between 65° and 70° is 
5°. Allowing 5 minutes per degree the thermostat setpoint will 
change to 70° at 6:35 AM. Cooling allows more time per degree 
because it takes longer to reach temperature.

•  

°F/°C CONVERTIBILITY

 – The factory default setting is 

Fahrenheit. Clipping W904 jumper on the circuit board (see 

Figure 1

) will alter this feature to display Celsius temperature.

CONFIGURATION MENU

Step

Press Button(s)

Displayed 

(Factory Default)

Press 

 or 

 

to select:

Comments

1

PRGM

 and 

RUN

FA (ON)

OFF

Select fast (ON) or slow (OFF) Second Stage Heat

2

  HOLD*

CL (OFF)

ON

Select compressor lockout OFF or ON

3

  HOLD*

0 HI (0)

3 LO to 3 HI

Select temperature display adjustment higher or lower

4

RUN

Returns to normal operation

*Press 

HOLD

 to advance to next item or 

TIME

 to move backwards to previous item.

Содержание 8265

Страница 1: ...questions please call Research Products Corporation at 800 334 6011 Electric or cordless drill with 3 16 inch drill bit if needed Flat blade screwdriver Wire cutter stripper Level THERMOSTAT DETAILS W905 Clip for Slow Cycle instead of Fast Cycle W904 Clip for Celsius instead of Fahrenheit W903 Clip to Disable Progressive Recovery Feature Mounting hole W906 for Emergency Heat Second Stage Fan Contr...

Страница 2: ...his thermostat is factory set to the B position This will accommodate the majority of heat pump applications which require the changeover relay to be energized in HEAT If the heat pump being installed with this thermostat requires an O terminal to energize the changeover relay in COOL the O B switch must be moved to the O position Take care when securing and routing wires so they do not short to a...

Страница 3: ... Damage to equipment will occur when power is restored NOTE The accessory relay scheme is required when safety circuits exist in both systems NOTE See Note Jumper required to use a single Aux Heat for both Second Stage Heat and Emergency FIGURE 2 Typical wiring diagram for single transformer systems ATTACH THERMOSTAT BASE TO WALL 1 Remove the packing material from the thermostat Gently pull the co...

Страница 4: ... should stop operating To prevent compressor and or property damage if the outdoor temperature is below 50 F DO NOT operate the cooling system CAUTION COOLING SYSTEM 1 Move SYSTEM switch to COOL position 2 Press to adjust thermostat setting below room temperature The blower should come on immediately on high speed followed by cold air circulation 3 Press to adjust temperature setting above room te...

Страница 5: ...ating and cooling system loses power It will also wait 5 minutes minimum between cooling and heating cycles OPERATING FEATURES Now that you are familiar with the thermostat buttons and display read the following information to learn about the many features of the thermostat SIMULTANEOUS HEATING COOLING PROGRAM STORAGE When programming you can enter both your heating and cooling programs at the sam...

Страница 6: ...ing start time and temperature Use the table on page 7 to plan your program time periods and the temperatures you want during each period You may also want to look at the sample program table to get an idea of how the thermostat can be programmed ENTER HEATING PROGRAM 1 Move the SYSTEM switch to HEAT 2 Press PRGM once MO TU WE TH FR indicating weekday program will appear in the display Also displa...

Страница 7: ...e display or causes erratic thermostat operation you can reset the thermostat by pressing and TIME at the same time This also resets the factory defaults If the thermostat has power has been reset and still does not function correctly contact your heating cooling service person or place of purchase BATTERIES For optimum performance we recommend replacing batteries once a year with fresh AAA Energi...

Страница 8: ...he cycle time clip Jumper W 905 as mentioned in the instructions for Hydronic Heating Systems It is not possible to shorten the cycle time If an acceptable cycle rate is not achieved as received or by clipping W 905 contact a local service person for additional suggestions Thermostat Setting and Thermostat Thermometer Disagree Thermostat thermometer setting requires adjustment The thermometer can ...

Отзывы: