Aprilaire 8120X Скачать руководство пользователя страница 8

15

14

SET UP MENU

NOTICE

Before setting up the control for use, the amount of ventilation air being delivered (CFM) by 
the installed ventilation system must be measured.

1

  Hold for 5 seconds, 

then release .

2

  

Throughout the Set Up Menu, the   and   buttons are used to change values, the 

Select

 button 

is used enter the value and move on to the next Set Up Menu item .

Menu Item

Values   

Description

HP  

HC  

HP or HC

HP

 if wiring to a heat pump .

HC

 if wiring to furnace and AC .

CODE

# BEDROOMS         

HIGH

1 – 10

Number of bedrooms

 – used to calculate required 

continuous ventilation rate .

COMFORT 

HOUSE (FT

2

)  

LOW

500 – 7500 ft2

Square footage

 – used to calculate required continuous 

ventilation rate .

MEAS     

REQ’D CONT

 CFM 

FAN

30 – 250 CFM

Measured

 outdoor 

airflow

 delivered during ventilation .

HP  

°F

CODE NO.OF BEDROOMS 

HIGH

OFF, 85°F – 105°F

Ventilation high temperature limit.

 Ventilation is limited 

when the outdoor temperature exceeds the setting . Turn 

OFF if no high limit is desired .

HP

°F

COMFORT   HOUSE (FT

2

LOW

OFF, -10°F – 40°F

Ventilation low temperature limit.

 Ventilation is limited 

when the outdoor temperature falls below the setting . 

Turn OFF if no low limit is desired .

MEAS   REQ’D CONT CFM

FAN

On, “bLnd”, OFF

ON

 HVAC fan turns on whenever ventilation occurs .

bLnd

 (blend) HVAC fan turns on with ventilation only 

when the outdoor temperature is outside a set range .

OFF

 HVAC fan is not turned on with ventilation .

HP  

°F

MEAS    REQ’D CONT CFM

FAN

CODE    # BEDROOMS     

HIGH

OFF, 60°F to 5°F 

less than Vent . 

High Temp . Limit

Only available when 

bLnd

 is selected . When the outdoor 

temperature is above the setting, the HVAC fan will be 

turned on to mix (blend) outdoor air with indoor air for 

tempering .

Содержание 8120X

Страница 1: ...MIN HR CODE Model 8120X Digital Ventilation Controller Installation and Operation Manual...

Страница 2: ...equence of Operation Comfort Setting 19 Limited Warranty 20 WARNINGS AND CAUTIONS WARNING 120 volts can cause serious injury from electric shock Disconnect electrical power to the HVAC system before p...

Страница 3: ...tilation with high indoor RH is important mount the control to the return duct and mount the outdoor temperature sensor as shown on pages 6 9 If humidity limits will not be used then the control can b...

Страница 4: ...PLATE 8 HEX HEAD SCREWS 5 8 DIA HOLE PILOT HOLES FOR SCREWS 6 MIN 90 2269 Duct Board Installation 1 Take out the duct board mounting bracket remove the wall plate from the control and put the rest of...

Страница 5: ...rest of the control in a safe location until after wiring is complete 2 Use spacers or brackets to mount the controller to an inside wall surface or return plenum duct surface that is at room temperat...

Страница 6: ...damper in Model 8126X installations or to the Model 8140NC Fresh Air Ventilator and wire according to FIGURE 3 or FIGURE 4 MODEL 8120X DIGITAL VENTILATION CONTROL R C Y W G R C Y W G THERMOSTAT WIRE...

Страница 7: ...2266 OPERATION The display will appear faint normally the first press of any button will turn on the display at full power Use for Rater Inspector Verification Press and hold for 5 seconds to enter T...

Страница 8: ...rflow delivered during ventilation HP F CODE NO OF BEDROOMS HIGH OFF 85 F 105 F Ventilation high temperature limit Ventilation is limited when the outdoor temperature exceeds the setting Turn OFF if n...

Страница 9: ...ps below the setting ventilation will not occur When all Set Up Menu options have been entered the control will display donE TEST MODE After wiring and set up have been completed Test Mode can be used...

Страница 10: ...starts again it will sample the air temperature and if in range will meet the set amount of ventilation during the four hour cycle period For example if the Vent Time was set to 25 minutes per hour an...

Страница 11: ...ULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED THIS LIMITED WARRANTY IS VOID IF DEFECT S RESULT FROM FAILURE TO HAVE THIS UNIT INSTALLED...

Отзывы: