Aprilaire 8120X Скачать руководство пользователя страница 4

7

6

MOUNTING THE CONTROLLER TO THE RETURN DUCTWORK

NOTE:

 Mount the controller to the return ductwork at a location where the temperature 

and humidity in the duct is most representative of the home . Keep the controller at least 6" 
upstream from the point where the fresh air duct enters the return duct, and 6" upstream from 
a humidifier outlet .

Sheet Metal Installation
1. 

Remove the wall plate from the control and put the rest of the control in a safe location until 
after wiring is completed .

2. 

Mark the location of the wall plate sensor hole on the duct . Use a step-drill bit to create a 5/8" 
( .625") hole for the sensor .

3. 

Center the sensor hole in the wall plate over the hole in the duct, level the wall plate and mark 
the locations of the two mounting slots . Drill a small pilot hole using a #36 ( .106") or smaller 
drill bit at the two mounting locations .

4. 

Use the supplied #8 standard hex head sheet metal screws to mount the wall plate to the duct .

FRESH 

AIR DUCT

FRESH AIR DUCT

WALL PLATE

#8 HEX HEAD

SCREWS

5/8" DIA

HOLE

PILOT HOLES FOR SCREWS

6" MIN

90-2269

Duct Board Installation
1. 

Take out the duct board mounting bracket, remove the wall plate from the control and put the 
rest of the control in a safe location until after wiring is completed .

2. 

Cut a 5 .75" x 5 .25" rectangular opening in the return plenum . Save the piece cut out to 
insulate the duct board bracket around the controller . The display of the control will run 
parallel with the long dimension . DO NOT MOUNT THE CONTROL IN A POSITION WHERE IT IS 
FACING DOWN .

3. 

Use the supplied #8 x 1/2" type 25 pan head screws to mount the control wall plate to the 
duct board mounting bracket .

4. 

Place the bracket in the cut out and seal in place using metal foil tape and/or mastic .

5. 

Insulate the duct board bracket around the wall plate using the plug cut out of the duct board .

RETURN DUCT

FRESH AIR DUCT

6" MIN

5-1/4"

5-3/4"

DUCT BOARD 

RETURN PLENUM

WALL PLATE

#8 PAN HEAD

TYPE 25 SCREW

DUCT

BOARD

BRACKET

USE CUT-OUT INSULATION

TO INSULATE DUCT BOARD

BRACKET AROUND CONTROLLER

MOUNT VENT CONTROLLER

SIDE AND TOP ONLY

90-2264

FRESH AIR DUCT

WALL PLATE

#8 HEX HEAD

SCREWS

5/8" DIA

HOLE

PILOT HOLES FOR SCREWS

6" MIN

Содержание 8120X

Страница 1: ...MIN HR CODE Model 8120X Digital Ventilation Controller Installation and Operation Manual...

Страница 2: ...equence of Operation Comfort Setting 19 Limited Warranty 20 WARNINGS AND CAUTIONS WARNING 120 volts can cause serious injury from electric shock Disconnect electrical power to the HVAC system before p...

Страница 3: ...tilation with high indoor RH is important mount the control to the return duct and mount the outdoor temperature sensor as shown on pages 6 9 If humidity limits will not be used then the control can b...

Страница 4: ...PLATE 8 HEX HEAD SCREWS 5 8 DIA HOLE PILOT HOLES FOR SCREWS 6 MIN 90 2269 Duct Board Installation 1 Take out the duct board mounting bracket remove the wall plate from the control and put the rest of...

Страница 5: ...rest of the control in a safe location until after wiring is complete 2 Use spacers or brackets to mount the controller to an inside wall surface or return plenum duct surface that is at room temperat...

Страница 6: ...damper in Model 8126X installations or to the Model 8140NC Fresh Air Ventilator and wire according to FIGURE 3 or FIGURE 4 MODEL 8120X DIGITAL VENTILATION CONTROL R C Y W G R C Y W G THERMOSTAT WIRE...

Страница 7: ...2266 OPERATION The display will appear faint normally the first press of any button will turn on the display at full power Use for Rater Inspector Verification Press and hold for 5 seconds to enter T...

Страница 8: ...rflow delivered during ventilation HP F CODE NO OF BEDROOMS HIGH OFF 85 F 105 F Ventilation high temperature limit Ventilation is limited when the outdoor temperature exceeds the setting Turn OFF if n...

Страница 9: ...ps below the setting ventilation will not occur When all Set Up Menu options have been entered the control will display donE TEST MODE After wiring and set up have been completed Test Mode can be used...

Страница 10: ...starts again it will sample the air temperature and if in range will meet the set amount of ventilation during the four hour cycle period For example if the Vent Time was set to 25 minutes per hour an...

Страница 11: ...ULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED THIS LIMITED WARRANTY IS VOID IF DEFECT S RESULT FROM FAILURE TO HAVE THIS UNIT INSTALLED...

Отзывы: