The included drain trap must be
installed to the dehumidifier. Use
PVC primer and cement to
connect the trap to the drain
outlet on the dehumidifier. The
drain outlet is located near the
On/Off toggle switch.

Note

orientation of trap prior to
cementing.

The high side of the

trap mates with the dehumidifier. The adjustable legs on
the dehumidifier must be disengaged approximately 1

7

8

to accommodate the trap. Loosen nuts before adjusting.
Complete the assembly by piping the trap to a drain. The
trap must be primed with water prior to start-up.

If the dehumidifier is installed in an attic or in an area
where flooding is a potential problem, it should be
installed in a secondary drain pan with a float switch. See
page 12 for float switch wiring.

If hanging the unit, use two unistruts to support the base
on the outside edges of the feet locations. There must
be at least 20” of clearance in front of one of the filter
access doors to allow removal of the filter.

3

DRAIN LINE

HANGING

DUCTING

The Aprilaire Dehumidifier is supplied with two
8” round collars. These are packaged with a drain
trap inside the unit behind the filter access panel.
Secure the collars with Four (4) 1-inch sheet metal
screws (not included). UL approved 8” diameter,
insulated flexible duct is recommended for all
connections. Rigid metal duct may also be used. The
duct should be capable of handling at least 2” w.c.
pressure. All joints and seams must be sealed.

Design airflow for the 1750 is 275 CFM @ 0.6” w.c.,
for the 1770 it is 500 CFM @ 0.8” w.c. This is
equivalent to approximately 70 ft. for the 1750 or
100 ft for the 1770 of 8” duct on the inlet and outlet
side of the dehumidifier. Elbows, turns and the static
pressure of the HVAC equipment will affect the
airflow through the dehumidifier.

For optimal moisture removal, airflow should be at or above
275 CFM for the 1750, 500 CFM for the 1770.

The total static pressure across the 1750 must not exceed 0.8”
w.c., 1.5” w.c. for the 1770. Check all pressures with the HVAC
fan on.

• The outlet from the dehumidifier to the HVAC supply duct must be

located at least 6” downstream of the cooling coil to prevent air from
pulling moisture from the coil.

• If connected to HVAC ductwork, the dehumidifier inlet must be located

at least 6” upstream of the HVAC system air cleaner. This will prevent
any trapped particulates from being drawn into the dehumidifier.

• If UV Germicidal lamps are installed in the HVAC system, use

appropriate methods to protect the flexible duct from the UV light.

• To further reduce any sound that may be created by air movement,

install at least 5 feet of acoustical flexible duct on the outlet and inlet
of the dehumidifier.

2

1

/

2

1

/

2

Drain Outlet

Drain Trap 

High Side

Low Side 

FIGURE 1

90-961

3“ MIN

CLEARANCE FOR

ACCESS PANEL

20” MINUMUM

CLEARANCE FOR FILTER

(EITHER SIDE)

6" MIN CLEARANCE
FOR ACCESS PANEL

FILTER

TOP VIEW

FIGURE 2

90-970

Содержание 1750

Страница 1: ...rcuit is required for proper operation of the dehumidifier If a dedicated circuit is not available do not install unit Dehumidifier must be plugged in directly to an outlet Do not use an extension cord 4 For protection of the compressor unit must be transported and installed in an upright position If the unit was shipped or stored on its side a 24 hour settling period is required before running th...

Страница 2: ...in ventilation feature is designed to be able to meet ASHRAE 62 2 Standard for Ventilation See Ventilation page 10 for more details on this feature LOCATION NOTES Design Airflow 1750 275 CFM 0 6 in w c 1770 500 CFM 0 6 in w c Filter MERV 8 Filter Cabinet Insulation 1 foil faced EPS insulation Inlet Air Operating Conditions 40 F to 105 F Ambient Air Operating Conditions 40 F to 150 F This product m...

Страница 3: ...The duct should be capable of handling at least 2 w c pressure All joints and seams must be sealed Design airflow for the 1750 is 275 CFM 0 6 w c for the 1770 it is 500 CFM 0 8 w c This is equivalent to approximately 70 ft for the 1750 or 100 ft for the 1770 of 8 duct on the inlet and outlet side of the dehumidifier Elbows turns and the static pressure of the HVAC equipment will affect the airflow...

Страница 4: ...hin the home As shown in Figure 3 below air is pulled from the return duct dehumidifed and returned to the supply duct 1 Backflow Damper Duct Work Thermostat Wire REQUIRED COMPONENTS OPTIONAL COMPONENTS 6506 Ventilation Damper 24 VAC Transformer 10 VA minimum for Ventilation Damper 8052 Outdoor Temperature Sensor Float Switch Model 70 Living Space Control 6 MIN RETURN AIRFLOW SUPPLY AIRFLOW 6 MIN ...

Страница 5: ... SETUP ON B CONVERTIBLE HVAC FAN WHL HOUSE VENT AUTO A OFF Standard Air Cycling Ventilation OFF OFF OFF See pages 10 11 See pages 10 11 See pages 10 11 OFF OFF OFF OFF ON OFF Standard Air Cycling Ventilation OFF See pages 10 11 See pages 10 11 ON See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 Standard Air Cycling Ventilation OFF See pages 10...

Страница 6: ... Trap included REQUIRED COMPONENTS OPTIONAL COMPONENTS Duct Work 24 VAC Transformer 10 VA minimum for Ventilation Damper Thermostat Wire 6506 Ventilation Damper 8052 Outdoor Temperature Sensor Grilles Normally Closed Condensate Overflow Safety Switch Model 70 Living Space Control RETURN AIRFLOW OPTIONAL OUTDOOR AIR INTAKE AIR CLEANER COOLING COIL TO SUPPLY GRILLE OR TO UNCONDITIONED SPACE HVAC UNI...

Страница 7: ...EM SETUP ON B CONVERTIBLE HVAC FAN WHL HOUSE VENT AUTO A OFF Standard Air Cycling Ventilation OFF OFF OFF See pages 10 11 See pages 10 11 See pages 10 11 ON ON ON OFF ON OFF Standard Air Cycling Ventilation OFF See pages 10 11 See pages 10 11 ON See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 Standard Air Cycling Ventilation OFF See pages 10 ...

Страница 8: ...8 N C Dampers 2 6608 N O Dampers and a 24 VAC Transformer 2 Running Constant fan on will prevent proper function in this mode 2 6508 Normally Closed Power Open Damper 2 6608 Normally Open Power Closed Damper Duct Work 24 VAC Transformer 40 VA minimum Thermostat Wire REQUIRED COMPONENTS OPTIONAL COMPONENTS 6506 Ventilation Damper 24 VAC Transformer 10 VA minimum for Ventilation Damper 8052 Outdoor ...

Страница 9: ... MIN 1 HOUR CYCLE PERIOD 4 3 2 1 ON VENT TIMED HVAC FAN SYSTEM SETUP ON B CONVERTIBLE HVAC FAN WHL HOUSE VENT AUTO A OFF Standard Air Cycling Ventilation OFF OFF OFF OFF OFF OFF ON ON ON OFF ON OFF Standard Air Cycling Ventilation OFF See pages 10 11 See pages 10 11 ON See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 Standard Air Cycling Venti...

Страница 10: ...UTO A OFF 90 969 shown set to 30 minutes VENTILATION AIR CYCLING SETTINGS The Aprilaire Dehumidifier has the option to monitor HVAC heating cooling and fan calls to assure the HVAC fan has operated a predetermined amount of time each 1 2 1 2 or 3 hours The dehumidifier can also open a normally closed damper in an outdoor air intake to ventilate during this predetermined amount of time This feature...

Страница 11: ...o be combined with the fan cycling feature from the dehumidifier provided the outside air temperature is in the acceptable range 0 100 F This will allow the homeowner to receive the proper ventilation year round Note The dehumidifier can control the HVAC fan to provide fan cycling regardless of whether or not an outdoor ventilation duct is installed NORTH EAST OR WEST SIDE OF HOME OUTDOOR TEMPERAT...

Страница 12: ... B The CYCLE TIME dial determines how long during every Cycle Period the damper will open and ventilation will occur The dial can be adjusted from OFF to between 1 to 60 minutes see Figure 14 This will give outdoor air ventilation and HVAC fan operation from 1 to 60 minutes every Cycle Period C Refer to Table 3 to determine the Cycle Time setting based on airflow delivered and airflow required The...

Страница 13: ...osed CONVERTIBLE position This is used for zoned dehumidification The damper DEH terminals are actuated when the HVAC equipment is making a call for heat cool or fan and the dehumidifier is making an internal blower call for air sampling or dehumidification WHL HOUSE position This is used for central dehumidification The damper DEH terminals are actuated any time the dehumidifier is making an inte...

Страница 14: ...s running but no airflow Normally Open Damper was used instead of Normally Closed Damper in backflow Damper needs to be switched Total HVAC system static is higher than 0 8 w c Dehumidifier not adequately dehumidifying Unit will need time to dry materials in home before effectively changing RH Too little airflow through dehumidifier Total HVAC system static is higher than 0 8 w c Compressor is not...

Страница 15: ...h East or West side of the house Not in direct sunlight If the outdoor temperature is below 0 F or above 100 F the damper will remain closed If using the outdoor temperature sensor verify that it is reporting an accurate resistance Remove the Outdoor Temperature Sensor leads from ODT Sensor terminals and check the resistance Compare the reading with the resistance shown in Table 4 The HVAC fan tur...

Страница 16: ...NTILATION OR AIR CYCLING SEQUENCE OF OPERATION If the dehumidifier is providing outdoor air ventilation or air cycling it is monitoring the HVAC equipment to provide the amount of HVAC fan run time that has been set by the Cycle Time during the Cycle Period If an outdoor air damper has not been installed then the dehumidifier is providing air cycling The dehumidifier will monitor the HVAC system a...

Отзывы: