Aprilaire 1750 Скачать руководство пользователя страница 16

10007791   10.07
B2204536A

DEHUMIDIFIER SEQUENCE OF OPERATION

IF THE DEHUMIDIFIER IS NOT WIRED TO THE HVAC EQUIPMENT, THE DEHUMIDIFIER WILL SAMPLE AT THE END OF THE 
CYCLE PERIOD.

With 4 minutes left in the Cycle Period, the dehumidifier will turn on the dehumidifier blower for 3 minutes. During this time the
temperature and relative humidity are measured and the dewpoint is calculated. If the dewpoint is higher than the setting at the
Control Knob then the dehumidifier compressor will turn on and the dehumidifier will run until it reaches set point.

After reaching the set point, the dehumidifier will not sample again until the end of the next Sample Period.

For example, if the Sample Period is set for 1 hour, the dehumidifier will sample at the end of the hour. Once the dehumidifier
reaches set point and shuts off, the dehumidifier will not sample again until the end of the next hour. 

IF THE DEHUMIDIFIER IS WIRED INTO THE HVAC EQUIPMENT, THE DEHUMIDIFIER WILL SAMPLE THE FIRST TIME THE HVAC
EQUIPMENT RUNS IN THE CYCLE PERIOD OR AT THE END OF THE CYCLE PERIOD IF THE HVAC EQUIPMENT DOES NOT RUN.

For example, if the Cycle Period is set to 1 hour and the air conditioner starts 15 minutes into that hour, the dehumidifier will
sample when the air conditioner starts. Once the dehumidifier begins dehumidifying, it will run until set point is reached. If the
dehumidifier samples and determines that dehumidification is not needed, it will not sample again until the next Cycle Period.

DAMPER SEQUENCE OF OPERATION

In the Central/Zoned installation 4 motorized dampers are used to control the airflow through the dehumidifier. The dampers are
energized when the HVAC equipment is running. This means that when the HVAC equipment is running, the dampers are in the
central position. When the HVAC equipment is not running, the dampers are in the zoned position.

VENTILATION OR AIR CYCLING SEQUENCE OF OPERATION

If the dehumidifier is providing outdoor air ventilation or air cycling, it is monitoring the HVAC equipment to provide the amount
of HVAC fan run time that has been set by the Cycle Time during the Cycle Period. 

If an outdoor air damper has not been installed then the dehumidifier is providing air cycling. The dehumidifier will monitor the
HVAC system and if the system has not run for the specified Cycle Time within the Cycle Period, the dehumidifier will energize
the HVAC fan through the G terminal to provide the desired amount of fan run time. 

For example, if the Cycle Time is set for 10 minutes and the Cycle Period is set for 1 hour then the dehumidifier will provide 
10 minutes of air cycling or outdoor air ventilation. If the HVAC system runs for 5 minutes during this hour then the dehumidifier
will energize the fan for an additional 5 minutes. 

If an outdoor air damper has been installed, then the Aprilaire dehumidifier is providing outdoor air ventilation. The dehumidifier
will open the outdoor air damper whenever the HVAC system is running, up to the amount of time specified by the Cycle Time.
The dehumidifier will energize the HVAC fan and open the outdoor air damper to provide the desired ventilation time if the HVAC
system has not run for the specified Cycle Time. During ventilation, the dehumidifier blower will operate and the unit will
dehumidify if necessary.

If an Outdoor Temperature Sensor has been installed, then the dehumidifier will use the outdoor temperature to determine if the
outdoor air damper is to be opened. If the outdoor temperature is above 100°F the damper will not open. If the temperature is
between 20°F and 0°F the damper will only open with a heat call. If the outdoor temperature is below 0°F, the damper will not
open. If the Outdoor Temperature Sensor is not installed then the temperature is not considered in opening the damper. 

RESEARCH PRODUCTS CORPORATION

P.O. BOX 1467 • MADISON, WI 53701-1467 • PHONE: 800/334-6011 • FAX: 608/257-4357 • 

www.aprilairecontractor.com

Содержание 1750

Страница 1: ...rcuit is required for proper operation of the dehumidifier If a dedicated circuit is not available do not install unit Dehumidifier must be plugged in directly to an outlet Do not use an extension cord 4 For protection of the compressor unit must be transported and installed in an upright position If the unit was shipped or stored on its side a 24 hour settling period is required before running th...

Страница 2: ...in ventilation feature is designed to be able to meet ASHRAE 62 2 Standard for Ventilation See Ventilation page 10 for more details on this feature LOCATION NOTES Design Airflow 1750 275 CFM 0 6 in w c 1770 500 CFM 0 6 in w c Filter MERV 8 Filter Cabinet Insulation 1 foil faced EPS insulation Inlet Air Operating Conditions 40 F to 105 F Ambient Air Operating Conditions 40 F to 150 F This product m...

Страница 3: ...The duct should be capable of handling at least 2 w c pressure All joints and seams must be sealed Design airflow for the 1750 is 275 CFM 0 6 w c for the 1770 it is 500 CFM 0 8 w c This is equivalent to approximately 70 ft for the 1750 or 100 ft for the 1770 of 8 duct on the inlet and outlet side of the dehumidifier Elbows turns and the static pressure of the HVAC equipment will affect the airflow...

Страница 4: ...hin the home As shown in Figure 3 below air is pulled from the return duct dehumidifed and returned to the supply duct 1 Backflow Damper Duct Work Thermostat Wire REQUIRED COMPONENTS OPTIONAL COMPONENTS 6506 Ventilation Damper 24 VAC Transformer 10 VA minimum for Ventilation Damper 8052 Outdoor Temperature Sensor Float Switch Model 70 Living Space Control 6 MIN RETURN AIRFLOW SUPPLY AIRFLOW 6 MIN ...

Страница 5: ... SETUP ON B CONVERTIBLE HVAC FAN WHL HOUSE VENT AUTO A OFF Standard Air Cycling Ventilation OFF OFF OFF See pages 10 11 See pages 10 11 See pages 10 11 OFF OFF OFF OFF ON OFF Standard Air Cycling Ventilation OFF See pages 10 11 See pages 10 11 ON See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 Standard Air Cycling Ventilation OFF See pages 10...

Страница 6: ... Trap included REQUIRED COMPONENTS OPTIONAL COMPONENTS Duct Work 24 VAC Transformer 10 VA minimum for Ventilation Damper Thermostat Wire 6506 Ventilation Damper 8052 Outdoor Temperature Sensor Grilles Normally Closed Condensate Overflow Safety Switch Model 70 Living Space Control RETURN AIRFLOW OPTIONAL OUTDOOR AIR INTAKE AIR CLEANER COOLING COIL TO SUPPLY GRILLE OR TO UNCONDITIONED SPACE HVAC UNI...

Страница 7: ...EM SETUP ON B CONVERTIBLE HVAC FAN WHL HOUSE VENT AUTO A OFF Standard Air Cycling Ventilation OFF OFF OFF See pages 10 11 See pages 10 11 See pages 10 11 ON ON ON OFF ON OFF Standard Air Cycling Ventilation OFF See pages 10 11 See pages 10 11 ON See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 Standard Air Cycling Ventilation OFF See pages 10 ...

Страница 8: ...8 N C Dampers 2 6608 N O Dampers and a 24 VAC Transformer 2 Running Constant fan on will prevent proper function in this mode 2 6508 Normally Closed Power Open Damper 2 6608 Normally Open Power Closed Damper Duct Work 24 VAC Transformer 40 VA minimum Thermostat Wire REQUIRED COMPONENTS OPTIONAL COMPONENTS 6506 Ventilation Damper 24 VAC Transformer 10 VA minimum for Ventilation Damper 8052 Outdoor ...

Страница 9: ... MIN 1 HOUR CYCLE PERIOD 4 3 2 1 ON VENT TIMED HVAC FAN SYSTEM SETUP ON B CONVERTIBLE HVAC FAN WHL HOUSE VENT AUTO A OFF Standard Air Cycling Ventilation OFF OFF OFF OFF OFF OFF ON ON ON OFF ON OFF Standard Air Cycling Ventilation OFF See pages 10 11 See pages 10 11 ON See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 OFF See pages 10 11 See pages 10 11 Standard Air Cycling Venti...

Страница 10: ...UTO A OFF 90 969 shown set to 30 minutes VENTILATION AIR CYCLING SETTINGS The Aprilaire Dehumidifier has the option to monitor HVAC heating cooling and fan calls to assure the HVAC fan has operated a predetermined amount of time each 1 2 1 2 or 3 hours The dehumidifier can also open a normally closed damper in an outdoor air intake to ventilate during this predetermined amount of time This feature...

Страница 11: ...o be combined with the fan cycling feature from the dehumidifier provided the outside air temperature is in the acceptable range 0 100 F This will allow the homeowner to receive the proper ventilation year round Note The dehumidifier can control the HVAC fan to provide fan cycling regardless of whether or not an outdoor ventilation duct is installed NORTH EAST OR WEST SIDE OF HOME OUTDOOR TEMPERAT...

Страница 12: ... B The CYCLE TIME dial determines how long during every Cycle Period the damper will open and ventilation will occur The dial can be adjusted from OFF to between 1 to 60 minutes see Figure 14 This will give outdoor air ventilation and HVAC fan operation from 1 to 60 minutes every Cycle Period C Refer to Table 3 to determine the Cycle Time setting based on airflow delivered and airflow required The...

Страница 13: ...osed CONVERTIBLE position This is used for zoned dehumidification The damper DEH terminals are actuated when the HVAC equipment is making a call for heat cool or fan and the dehumidifier is making an internal blower call for air sampling or dehumidification WHL HOUSE position This is used for central dehumidification The damper DEH terminals are actuated any time the dehumidifier is making an inte...

Страница 14: ...s running but no airflow Normally Open Damper was used instead of Normally Closed Damper in backflow Damper needs to be switched Total HVAC system static is higher than 0 8 w c Dehumidifier not adequately dehumidifying Unit will need time to dry materials in home before effectively changing RH Too little airflow through dehumidifier Total HVAC system static is higher than 0 8 w c Compressor is not...

Страница 15: ...h East or West side of the house Not in direct sunlight If the outdoor temperature is below 0 F or above 100 F the damper will remain closed If using the outdoor temperature sensor verify that it is reporting an accurate resistance Remove the Outdoor Temperature Sensor leads from ODT Sensor terminals and check the resistance Compare the reading with the resistance shown in Table 4 The HVAC fan tur...

Страница 16: ...NTILATION OR AIR CYCLING SEQUENCE OF OPERATION If the dehumidifier is providing outdoor air ventilation or air cycling it is monitoring the HVAC equipment to provide the amount of HVAC fan run time that has been set by the Cycle Time during the Cycle Period If an outdoor air damper has not been installed then the dehumidifier is providing air cycling The dehumidifier will monitor the HVAC system a...

Отзывы: