A relative minimum pump speed can be allocated to the 
output R1 via the adjustment channel

 nMN.

N-.

Pump speed control
Adjustment range: 30 ... 100
in steps of 5 %
Factory setting: 100

.OTE

When a load which is not speed-controlled is 
used, the value must be set to 100 % in order to 
deactivate pump speed control.

Minimum pump speed

Maximum store temperature 

Once  the  adjusted  maximum  temperature  is  exceeded, 
the solar pump is switched off and further loading of the 
store is prevented to reduce scald risk or system damage. 
A fixed hysteresis of 2 K [4 °Ra] is set for the maximum 
store temperature.
When the temperature at sensor 2 exceeds the adjusted 
maximum  store  temperature,  the 

symbol  is  shown  on 

the display.

S MX

:  

Maximum store temp. 
Adjustment range: 
4 ... 95 °C [40 ... 200 °F]
Arr 3:
4 ... 90 °C [40 ... 190 °F]
in steps of 1 K [2 °Ra]
Factory setting: 85 °C [186 °F]

.OTE

 

If  the  collector  cooling  or  the  system  cooling 
function is activated, the adjusted store tempe-
rature may be overridden. In order to prevent 
system damage, the controller is also equipped 
with an integrated store emergency shutdown if 
the store reaches 95 °C [200 °F].

Collector temperature limitation
Emergency shutdown of the collector

Store emergency shutdown option

If the adjusted collector emergency shutdown temperature 

EM

 is exceeded, the controller switches off the solar pump 

(R1)  in  order  to  protect  the  system  against  overheating 
(collector  emergency  shutdown).  A  hysteresis  of  10  K 
[20  °Ra]  is  set  for  the  collector  temperature  limitation. 
While the collector is in emergency shutdown,   (flashing) 
is shown on the display.

This  option  is  used  for  activating  the  integrated  store 
emergency  shutdown  for  an  upper  store  sensor.  If  the 
temperature at the reference sensor (S3) exceeds 95 °C, 
the store will be blocked and loading will be stopped until 
the temperature falls below 90 °C.

EM

:

Collector temperature limitation 
Adjustment range:
80 ... 200 °C [170 ... 390 °F]
in steps of 1 K [2 °Ra]
Factory setting: 130 °C [270 °F]

OSEM

:

Store emergency shutdown 
option
Adjustment range: ON / OFF
Factory setting: OFF

.OTE

If  the  drainback  option 

/$"

  is  activated, 

the  adjustment  range  of 

EM 

is  changed  to 

80 ... 120°C [170 ... 250 °F]. The factory setting 
in that case is 95 °C [200 °F].

WARNING!

Danger of injury and system da-
mage through pressure surges!

If water is used as a heat transfer 
medium in a pressure-less system, 
the water will start boiling at 100 °C 
[212 °F].

 

Î

If a pressure-less drainback 
system is used with water as a 
heat transfer medium, do not 
adjust the collector tempera-
ture limitation EM to more 

THANª#;ª&=

Содержание DeltaSol BS/4

Страница 1: ...n 11201745 11201745 DeltaSol BS 4 version 2 Mounting Connection Operation Application examples Thanks for buying this product Read this manual carefully to get the best perfomance from this unit Delta...

Страница 2: ...y possibly life threatening injury can occur ATTENTION means that damage to the appliance can occur CE Declaration of conformity The product complies with the relevant direc tives and is therefore lab...

Страница 3: ...l data OUSING plastic PC ABS and PMMA 0ROTECTION TYPE IP 20 EN 60529 MBIENT TEMP 0 40 C 32 104 F 3IZE 172 110 47 mm 6 8 4 3 1 9 OUNTING wall mounting mounting into patch panels is possible ISPLAY Syst...

Страница 4: ...with lower fastening screw and tighten Complete wiring connections in accordance with termi nal allocations see chap 1 2 Electrical connection Place the cover back onto the housing Fasten the cover by...

Страница 5: ...f and the corresponding screws The controller is equipped with 2 semiconductor relays to which loads such as pumps valves etc can be connected s Relay 1 18 conductor R1 17 neutral conductor N 13 groun...

Страница 6: ...18 COL x Temperature collector S1 18 TST x Temperature store S2 18 S3 x Temperature sensor 3 S3 18 TSTT x Temperatur store at the top S3 18 S4 x Temperature sensor 4 S4 18 TR x Temperature return sens...

Страница 7: ...ure difference 20 0 K 40 0 Ra 22 DTCF x Cooling switch off temperature difference 15 0 K 30 0 Ra 22 OSTC x Option store cooling OFF 23 OHOL x Option holiday cooling OFF 23 THOL x Holiday cooling tempe...

Страница 8: ...ess 18 COL x Temperature collector S1 18 TSTB x Temperature store 1 base S2 18 TSTT x Temperature store 1 at the top S3 18 TDIS s Thermal disinfection temperature S3 18 S4 x Temperature sensor 4 S4 18...

Страница 9: ...ending time 19 00 24 TCRU x OTC runtime 30 s 24 TCIN x OTC standstill interval 30 min 24 OHQM x Option heat quantity measurement OFF 24 FMAX x Maximum flow 6 0 l 24 MEDT x Antifreeze type 1 24 MED x...

Страница 10: ...0 200 0 F in steps of 0 5 K 1 0 Ra Factory setting 45 0 C 120 0 F T T T Thermostat switch on time Adjustment range 00 00 23 45 Factory setting 00 00 T T T Thermostat switch off time Adjustment range 0...

Страница 11: ...ng the afterheating Reference sensor for the thermal disinfection is S3 To activate the function select On in the OTD channel For thermal disinfection the temperature in the upper DHW store zone has t...

Страница 12: ...l Page COL x Temperature collector S1 18 TST x Temperature store S2 18 S3 x Temperature sensor 3 S3 18 TSTT x Temperatur store at the top S3 18 S4 x Temperature sensor 4 S4 18 TR x Temperature return...

Страница 13: ...OFF 21 EM x Emergency temperature collector 130 C 270 F 21 CMX s Maximum collector temperature 110 C 230 F 22 OCN x Option minimum limitation OFF 23 CMN x Minimum collector temperature 10 C 50 F 23 OC...

Страница 14: ...ring normal operation only the display channels are shown Scroll through the display channels by pressing buttons 1 and 2 CCESSING THE ADJUSTMENT CHANNELS Scroll down in the display menu and press but...

Страница 15: ...or fault sensor symbol is flashing quickly LASHING CODES LED flashing codes System screen flashing codes Pump Store with heat exchanger Afterheating with burner symbol Temperature sensor Collector wit...

Страница 16: ...ons 1 and 2 Save the adjustment by pressing button 3 again The symbol stops flashing Press button 1 or 2 to switch to the next or previous channel 1 2 3 OK The three pushbuttons of the BS 4 controller...

Страница 17: ...ypical settings to suit the selected system layout The settings made in the commissioning menu can be changed later on in the corresponding adjustment channels Additional functions and options can of...

Страница 18: ...Arr 1 and 3 only s S4 temperature sensor 4 3 3 Sensor temperatures Display range 40 260 C 40 500 F Indication of return temperature If heat quantity measurement is active the temperature at sensor 4 i...

Страница 19: ...quantity can be set back to 0 As soon as one of the display channels of the heat quantity is selected the symbol is permanently shown on the display Press button 3 for about 2 seconds in order to acc...

Страница 20: ...ump speed increases by one step 10 If the difference increases by the adjustable rise value the pump speed increases by 10 respectively until the maximum pump speed of 100 is reached The response of t...

Страница 21: ...re limitation Emergency shutdown of the collector Store emergency shutdown option If the adjusted collector emergency shutdown temperature EM is exceeded the controller switches off the solar pump R1...

Страница 22: ...hot days If the store temperature is higher than the maximum store temperature S MX and the switch on temperature difference DTCO is reached the solar system remains activated Solar loading is contin...

Страница 23: ...w 5 C 40 F in order to protect the store from frost damage 2 Antifreeze temperature Adjustment range 40 0 10 0 C 40 0 50 0 F in steps of 0 5 K 1 Ra Factory setting 4 0 C 40 0 F Store cooling function...

Страница 24: ...m speed nMN If the collector sensor is defective or the collector is blocked this function is suppressed or switched off EAT QUANTITY MEASUREMENT If OHQM is activated the heat quantity gained can be c...

Страница 25: ...l initiate the filling of the system when solar loading begins If the drainback option is activated the pump will operate at 100 speed for the adjusted filling time T in order to fill the system with...

Страница 26: ...selection Selection dE En Fr Factory setting En HE pump control Adjustment range ON OFF Factory setting OFF 5NIT In this adjustment channel the display unit for temperatures and temperature difference...

Страница 27: ...8 888 8 Cable broken Check cable Short circuit Check cable Disconnected Pt1000 temperature sen sors can be checked with an ohmmeter In the following table the resistance values with the corresponding...

Страница 28: ...exchanger blocked yes no Clean it Heat exchanger too small yes Replace with correctly sized one no Plausibility control of the option tube col lector special function Change Ton and Toff correspondin...

Страница 29: ...yes no Does the pump start up in manual operation yes There is no current check fuses replace them and check power supply The adjusted temperature difference for starting the pump is to high choose a...

Страница 30: ...s and from a larger distance An additional power supply is not required Large Display GA3 The Large Display GA3 is designed for simple connection to controllers via theVBus It is used for visualizing...

Страница 31: ...VBus of the controller and issues an optical signal via a red LED if a failure has occurred The AM1 also has a potential free relayoutput which can e g be connected to a building management system BM...

Страница 32: ...s espe cially applies for copies translations microfilms and the storage into electronic systems Editor Apricus Australia Pty Ltd Important notice The texts and drawings in this manual are correct to...

Отзывы: