background image

 

COMPONENTS 

1.  Wall Sleeve & Outdoor 

Grille 

The wall sleeve is to be built into 
the wall during construction. The 
wall sleeve is used for all wall 
thicknesses from 2” through 13” 
maximum. For a 13” deep wall the 
outdoor louvers will have to be 
mounted flush with the outside wall 
surface.  For walls thicker than 13”, 
a cabinet extension is required.  
For installation of wall sleeve 
extensions, see instructions 
packed with the extensions. 
The wall sleeve must penetrate 
into the room by a fixed distance in 
order for the downflow room 
cabinet apparatus to function 
properly. Therefore set the sleeve 
in the wall so that 1” of the sleeve 
protrudes into the room. This is 
necessary in order to obtain the 
10” distance between the front 
panel and the inside wall face as 
shown in Figures 1 and 2, once the 
plenum and side ducts are added. 
After installation of the wall sleeve, 
the sleeve should be thoroughly 
cleaned. The room-side portion of 
the cabinet should be carefully 
protected during the construction 
period to prevent scratching of the 
paint. 

IMPORTANT: 

The heating/cooling unit must not 
be used for temporary heating or 
cooling during the building’s 
construction stage. 

2. Heating/Cooling Chassis 

This chassis includes all cooling 
components, air moving 
components and controls, except 
for the 24-volt room thermostat. 

3.  Power Supply Cord & Plug 

A power supply cord with 30 Amp 
or 50 Amp male plugs (as 

applicable) extends from the left 
side of the control section located 
on the right hand side of the unit.  
This cord is to be attached to a 
field – supplied receptacle 
mounted in the factory – supplied 
junction box mounted in the sub 
base located under the unit. The 
sub base is sized to fill the gap 
between the finished floor and the 
room cabinet when the wall sleeve 
is installed 4” above the finished 
floor as shown in Figure 1.  
If the maximum fuse or circuit 
breaker listed on the unit rating 
plate is 30.0 Amps or less, then a 
NEMA 6-30R receptacle is used. If 
the marked maximum fuse or 
circuit breaker rating exceeds 30.0 
Amps, then a NEMA 6-50R 
receptacle must be used. The 
cover plate is supplied with the sub 
base. 

4.  Plenum / Vertical Ducts 

The plenum is a horizontal duct 
that attaches by screws to the top 
panel of the chassis, once the 
chassis is fully inserted and drawn 
up tightly in the wall sleeve. The 
plenum collects the air as it exits 
from the top of the chassis, and 
turns the air in a right hand and left 
hand direction.  When the air 
reaches the ends of the plenum, it 
is directed downward into the 
vertical side ducts where it flows 
toward the floor. Air duct outlet 
collars are provided on the side 
ducts.  
The left and right vertical side ducts 
are fully insulated and connect to 
the underside of the plenum using 
the sheet metal screws provided. 
Ensure the duct collars on the side 
ducts are facing away from the 
chassis so air will be directed out 
the left and right sides of the room 
enclosure apparatus.  

5. Ducting 

The vertical side ducts come 
complete with a duct collar on the 
lower outboard side, to accept 6” 
wide by 8” high lateral flanking 
duct. The unit must be ducted out 
both sides. The interior of the 
flanking duct must be insulated 
with a minimum of ½” thick 
fiberglass duct liner, suitable for the 
air velocities involved. The outlet 
vents should be located on the top 
of the distribution ductwork facing 
up.  

6. Duct Sizing 

The ducts must be sized for a 
maximum pressure drop of 0.20” of 
water column at 400 CFM total 
airflow directed out both sides of 
the unit. This will ensure that 
adequate airflow will result when 
the unit is operating at the factory – 
set indoor blower speeds for the 
particular heating and cooling 
capacity of the unit. There is no 
minimum pressure drop so large or 
short ducts are not a problem.  
Size the duct for the anticipated 
fraction of 400 CFM pertaining to 
that branch. In other words, if 40% 
airflow is desired out of the left side 
and 60% out the left, then size the 
duct as follows: 
40/100 X 400 = 160 CFM at .20” 
w.c. maximum, out the right side. 
60/100 X 400 = 240 CFM at .20” 
w.c. maximum, out the left side. 
Or, design both ducts for 240 CFM 
at .2” w.c. maximum and use 
dampers or the right side outlet 
grilles to throttle the flow down to 
160 CFM in the right side branch. 
The .20” w.c. pressure drop should 
also include the air resistance 
through the outlet vents calculated 
at the predicted CFM exiting out 
each vent. 

Содержание SD

Страница 1: ...ACKAGED TERMINAL AIR CONDITIONERS Heating and Cooling Unit Cooling Only Unit INSTALLATION OPERATION MANUAL Effective February 1985 Revision Date April 2009 This manual supersedes all previous issues 801108 REV 01 APR 2009 ...

Страница 2: ...es 9 If The Unit Doesn t Work 9 PREVENTIVE MAINTENANCE 9 Before Each Heating and Cooling Season 9 WARNING SAFETY HAZARD THE SD SERIES UNITS MUST BE USED FOR DUCTED APPLICATIONS ONLY FREE AIR DISCHARGE APPLICATIONS REQUIRE THE SU SERIES WHICH IS A SPECIALLY CONFIGURED UNIT SIMILAR IN APPEARANCE BUT WHICH INCORPORATES A DISCHARGE GRILLE AND OTHER SAFETY FEATURES REQUIRED FOR FREE AIR DISCHARGE APPLI...

Страница 3: ...r plate is supplied with the sub base 4 Plenum Vertical Ducts The plenum is a horizontal duct that attaches by screws to the top panel of the chassis once the chassis is fully inserted and drawn up tightly in the wall sleeve The plenum collects the air as it exits from the top of the chassis and turns the air in a right hand and left hand direction When the air reaches the ends of the plenum it is...

Страница 4: ...3 ...

Страница 5: ...4 ...

Страница 6: ...ting exceeds 30 0 Amps then a NEMA 6 50R receptacle must be used The cover plate is supplied with the sub base 9 Plenum Vertical Ducts The plenum is a horizontal duct that attaches by screws to the top panel of the chassis once the chassis is fully inserted and drawn up tightly in the wall sleeve The plenum collects the air as it exits from the top of the chassis and turns the air in a right hand ...

Страница 7: ...installation Electrical entrance must be between the concrete wall sleeve and sub base Detailed instructions follow A New Masonry Wall 1 From the architect s drawings determine the position of each unit and mark the centerline of the cabinet wall sleeve Also mark the location of the high voltage receptacle enclosure and the area of entrance for the low voltage wiring Low voltage wiring exits throu...

Страница 8: ... Position the chassis in the cabinet and slide into place Keep the chassis level and square to prevent binding The chassis must be pushed into the cabinet until the draw bolts screws in the chassis side panels can engage the threaded clip in the sleeve Alternate turning the two draw bolts until the chassis is drawn snugly into the sleeve Do not over tighten the draw bolts NOTE When handling the ch...

Страница 9: ...rt No 18BK23Y 024 Heating and cooling will be cycled on as dictated by the setting of the wall thermostat In this mode the room side fan will run at factory predetermined speeds for heating and cooling IMPORTANT The factory set indoor fan speeds must not be changed The product safety certification relies on fan speeds being coordinated with specific heater sizes The indoor fan will be off when nei...

Страница 10: ...ged 4 If unit is calling for cooling check to see if outside condenser fan is running 5 Is cooling being demanded at a very low outdoor temperature The unit is designed to discontinue cooling operation at low outdoor temperatures where air conditioning is not typically required If after checking the above your unit is still not operating call in competent service personnel ATTENTION When in coolin...

Отзывы: