Applied Comfort NYWC Series Скачать руководство пользователя страница 5

5

802961 Rev. 00  

START-UP CHECKLIST

Note: Once the unit is installed, it should be checked for 
proper function by qualified service personnel before turning 
it over to the User. 

x

Circuit breakers, wire size, and electrical 
connections tight and correct 

x

Filter clean and properly in place 

x

Condenser air inlet and outlet free of obstructions 
and short-circuiting of condenser air  

x

Unit operate for 20 minutes to prove stability 

x

Controls operation OK 

x

Unit installed in compliance with all codes and 
ordinances 

x

All panels in place and secured with required 
fasteners 

x

Mylar overlay applied to cover up touch pad for 24 
Volt Remote Thermostat installations. 

x

Work area clean and free of debris 

x

Owner or operator instructed on control operation 
and routine maintenance. 

USER CONTROLS - GENERAL

The NYWC series is available with advanced-function 
electronic controls with membrane switch type keypad, or, 
with conventional knob-actuated electromechanical controls. 

ELECTRONIC CONTROLS

The chassis incorporating electronic controls factory-shipped 
with an active keypad control and display mounted directly 
to the control panel. The unit functions are controlled by the 
user by pressing the keys on the keypad, and reading the 
display. However, the unit also has the latent ability to be 
field-converted by qualified service personnel for use with a 
field-supplied 24 volt AC wall thermostat. These 
instructions will address both unit-mounted control 
operation, and remote 24 volt AC wall thermostat operation.  

CONTROL AT THE UNIT, KEYPAD/DISPLAY 

THE KEYPAD CONTROL 

Become familiar with the keypad keys as shown in Figure 1. 

Display 

Red light emitting diodes (LEDs) display the actual 

 

temperature of the air entering the unit at floor level. The 
display can also be used to indicate the desired set point 
temperature for room comfort. It is important to remember 
that the temperature displayed is the temperature sensed at 

the unit’s indoor air inlet and can be significantly different 
from the bulk room temperature at a distance from the unit. 

On/Off Key 

Each press of the key toggles the unit from an OFF state to 
an ON state or from an ON state to an OFF state. Heating 
and cooling functions, as well as the display, and all 
indicating LEDs except for the fan indicators, are enabled or 
disabled with this key.  When toggled OFF, the control 
preserves only two modes active; fan-only, and room freeze 
protection. 

Fan Key 

Each press of the Fan Key cycles the fan through three 
modes of operation; Low Speed, High Speed and Auto. 
Small LEDs will indicate the mode. The On/Off key need 
not be ON to operate the fan and set fan speeds. Auto Mode 
will cycle the fan on and off, and determine the fan speed, in 
conjunction with the heating or cooling demand. 

Warmer Key 

Pressing the Warmer Key will cause the display to show the 
set point temperature for 3 seconds, and then increases room 
temperature by 1 degree for every subsequent press of the 
key. 

Cooler Key 

Pressing the Cooler Key will cause the display to show set 
point temperature for 3 seconds, and then decreases room 
temperature by 1 degree for every subsequent press of the 
key 

°F/°C Key 

This key toggles the display between Fahrenheit and Celsius 
temperature modes, and affects all displayed temperatures. 

Heat Key 

The Heat Key toggles the unit in and out of heating mode for 
every press of the key, provided the On/Off Key is ON. 

Cool Key 

The Cool Key toggles the unit in and out of cooling  mode 
for every press of the key, provided the On/Off Key is ON. 

Содержание NYWC Series

Страница 1: ...PACKAGED TERMINAL AIR CONDITIONERS Hydronic or Steam Heating and Cooling Unit INSTALLATION OPERATION MANUAL IMPORTANT READ AND SAVE THESE INSTRUCTIONS INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC NEC AND LOCAL ELECTRICAL CODES ...

Страница 2: ...ting coil and evaporator coil at least annually or more often as dictated by the severity of the particulates and pollutants circulating in the outdoor and indoor operating environments One suggested method is as follows Unimpeded Outdoor Airflow Do not block off the outside air flow to the unit The condenser air inlet and outlet must be free of obstructions and of any external influence that woul...

Страница 3: ...lt units are furnished with a NEMA 5 15P or 5 20P non locking plug as applicable The respective plug will require a NEMA 5 15R or 5 20R receptacle to be field provided All 277 Volt units are furnished with a NEMA 7 20P 20 Amp non locking plug and hence will require a NEMA 7 20R receptacle to be field provided Note 277 Volt units are considered to be permanently connected per the National Electrica...

Страница 4: ...not be used connect the ends blue orange of the aquastat leads together to permanently complete the aquastat circuit 6 If the unit is equipped with mechanical knob controls and touchpad this variation cannot be adapted to work with a remote thermostat Locate the 24 VAC aquatsat output connector beneath the control box A mating connector and 6 feet of wire leads are supplied to connect to an aquast...

Страница 5: ...ing diodes LEDs display the actual temperature of the air entering the unit at floor level The display can also be used to indicate the desired set point temperature for room comfort It is important to remember that the temperature displayed is the temperature sensed at the unit s indoor air inlet and can be significantly different from the bulk room temperature at a distance from the unit On Off ...

Страница 6: ...LL THERMOSTAT CONVERSION TO 24V REMOTE THERMOSTAT Except for the wall thermostat and thermostat cable everything is included with the unit to field convert a keypad operated unit to 24 Volt AC wall thermostat operation by qualified service personnel Specific conversion instructions are detailed on the wiring diagram affixed to each particular unit to be converted Conversion involves accessing the ...

Страница 7: ... a random 5 to 15 second delay before the electronic control powers up The keypad will be totally disabled once the DIP switch has been set for remote mode The unit will obey the commands from the thermostat only The thermostat will automatically maintain the temperature in the room based on the setting pre set by the user If the thermostat has only single fan speed capability a decision will need...

Страница 8: ...own for any reason a 3 minute time delay will elapse before the compressor is allowed to re start This prevents compressor overload during re start due to unequal system refrigerant pressures Indoor Coil Freeze Protection Control of frost on the evaporator coil due to low indoor loads or cold outdoor ambient temperatures is provided The protection remains active when the unit is OFF for either key...

Страница 9: ...screws with washers in Standard Position see Fig 1 This allows a wide range of thermostat rotation representing a range of temperatures between approximately 18 C and 29 C 65ºF and 85ºF The left screw in Standard Position can be removed and re inserted in four alternate holes moving in a clockwise direction in order to reduce the maximum allowable set point temperature for heating Similarly the ri...

Отзывы: