background image

3

802961 Rev. 00  

Reducing Load 

To reduce the cooling load, draw drapes or blinds in the 
summer, to reflect direct rays from the sun. 

To reduce the cooling and heating load, keep windows and 
doors closed when operating the unit. 

WALL SLEEVE CABINET INSTALLATION:

Install the wall sleeve cabinet in strict accordance with the 
wall sleeve installation instructions, which are supplied with 
the wall sleeve. 

ELECTRICAL WIRING AND RECEPTACLE

WIRE SIZING 

A single outlet branch circuit from the main electrical panel 
to the receptacle in the wall sleeve should be used.  Wire 
sizing shall be in accordance with the minimum circuit 
ampacity as declared on the unit Rating Plate for the specific 
chassis. Wire sizing must also take into account any distance 
from fuse box to receptacle to prevent excessive voltage 
drops in undersized wires. 

IMPORTANT:

 Low voltage to the unit will cause 

compressor starting problems and decrease the performance 
and reliability of the compressor. 

BRANCH CIRCUIT PROTECTION 

The Current Rating of branch circuit protection using a Time 
Delay Fuse or HACR circuit breaker should also be as 
declared on the unit Rating Plate, for the specific chassis 
being installed. 

PLUG AND RECEPTACLE 

All 230-208 Volt units are furnished with a NEMA 6-20P, 
20 Amp non-locking plug, and hence will require a NEMA 
6-20R receptacle to be field-provided. 

All 115 Volt units are furnished with a NEMA 5-15P, or 5-
20P non-locking plug as applicable. The respective plug will 
require a NEMA 5-15R or 5-20R receptacle to be field-
provided. 

All 277 Volt units are furnished with a NEMA 7-20P, 20 
Amp non-locking plug, and hence will require a NEMA 7-
20R receptacle to be field-provided. 

Note: 277 Volt units are considered to be permanently 
connected, per the National Electrical Code. The plug and 
cord are considered to be a “connector of convenience” in 
order to facilitate easy removal of the chassis for servicing. 
The plug and cord are suitably protected when using the 
non-optional 277 volt sub-base. 

230-208 and 115 volt units are true “cord connected units”, 
and are provided with a service cord of the LCDI (Leakage 
Current Detection Interrupter) type, intended to be plugged 
in to a wall receptacle. The LCDI cord is capable of 
detecting some of the common faults experienced with aging 
power cords, and when those faults are detected, interrupts 
power to the cord before a hazardous condition can evolve. 
The LCDI service cord, with its bulky plug head and 
inherent mechanical protection, is not intended to be plugged 
into a receptacle in a subbase. 

WARNING:

 To avoid property damage, bodily injury or 

death, the unit must be used on a grounded power supply 
only. The unit will be grounded through the service cord 
plug and matching receptacle as long as the branch circuit 
remains grounded. 

DO NOT: 

x

Change the length of the service cord. 

x

Bend the connector blades or otherwise alter 
service cord plug configuration. 

x

Use extension cords. 

Содержание NYWC Series

Страница 1: ...PACKAGED TERMINAL AIR CONDITIONERS Hydronic or Steam Heating and Cooling Unit INSTALLATION OPERATION MANUAL IMPORTANT READ AND SAVE THESE INSTRUCTIONS INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC NEC AND LOCAL ELECTRICAL CODES ...

Страница 2: ...ting coil and evaporator coil at least annually or more often as dictated by the severity of the particulates and pollutants circulating in the outdoor and indoor operating environments One suggested method is as follows Unimpeded Outdoor Airflow Do not block off the outside air flow to the unit The condenser air inlet and outlet must be free of obstructions and of any external influence that woul...

Страница 3: ...lt units are furnished with a NEMA 5 15P or 5 20P non locking plug as applicable The respective plug will require a NEMA 5 15R or 5 20R receptacle to be field provided All 277 Volt units are furnished with a NEMA 7 20P 20 Amp non locking plug and hence will require a NEMA 7 20R receptacle to be field provided Note 277 Volt units are considered to be permanently connected per the National Electrica...

Страница 4: ...not be used connect the ends blue orange of the aquastat leads together to permanently complete the aquastat circuit 6 If the unit is equipped with mechanical knob controls and touchpad this variation cannot be adapted to work with a remote thermostat Locate the 24 VAC aquatsat output connector beneath the control box A mating connector and 6 feet of wire leads are supplied to connect to an aquast...

Страница 5: ...ing diodes LEDs display the actual temperature of the air entering the unit at floor level The display can also be used to indicate the desired set point temperature for room comfort It is important to remember that the temperature displayed is the temperature sensed at the unit s indoor air inlet and can be significantly different from the bulk room temperature at a distance from the unit On Off ...

Страница 6: ...LL THERMOSTAT CONVERSION TO 24V REMOTE THERMOSTAT Except for the wall thermostat and thermostat cable everything is included with the unit to field convert a keypad operated unit to 24 Volt AC wall thermostat operation by qualified service personnel Specific conversion instructions are detailed on the wiring diagram affixed to each particular unit to be converted Conversion involves accessing the ...

Страница 7: ... a random 5 to 15 second delay before the electronic control powers up The keypad will be totally disabled once the DIP switch has been set for remote mode The unit will obey the commands from the thermostat only The thermostat will automatically maintain the temperature in the room based on the setting pre set by the user If the thermostat has only single fan speed capability a decision will need...

Страница 8: ...own for any reason a 3 minute time delay will elapse before the compressor is allowed to re start This prevents compressor overload during re start due to unequal system refrigerant pressures Indoor Coil Freeze Protection Control of frost on the evaporator coil due to low indoor loads or cold outdoor ambient temperatures is provided The protection remains active when the unit is OFF for either key...

Страница 9: ...screws with washers in Standard Position see Fig 1 This allows a wide range of thermostat rotation representing a range of temperatures between approximately 18 C and 29 C 65ºF and 85ºF The left screw in Standard Position can be removed and re inserted in four alternate holes moving in a clockwise direction in order to reduce the maximum allowable set point temperature for heating Similarly the ri...

Отзывы: