Press

for Pass Code screen:

Default Pass Code:

1 2 3 4

Change digit

Move between digits

Accept

An incorrect Pass Code will return the display

to the Pass Code entry screen

Three incorrect attempts will lock access for

three minutes

6. Enter Pass Code to Access Engineering Menu

7. Find Detectors

60 seconds

Press

to enable ‘Found’ Detectors at any point

during 60s countdown

Any unused Detector channels are switched off

Press

to re-scan if number is incorrect

This will be the number

of Detectors found

‘Find’ is automatically displayed the first time this process is run. ‘Find’ can also be accessed

in the System Controller settings menu. Find must be performed when adding or removing a

detector to an already ‘Found’ system.

8

Содержание SA7100-100APO

Страница 1: ...Apollo Intelligent Auto Aligning Beam Detector User Guide EN...

Страница 2: ...h a minimum distance of 0 5m from Detector and Reflector to ceiling Mount Detector and Reflector directly opposite each other Do NOT position Detector where personnel or objects can enter the beam pat...

Страница 3: ...2 Fitting the Product 3 Clip PCB into base Insert Detector cable LED indicator must face downward...

Страница 4: ...3 Wiring Diagram 4 It is possible to wire either one or two detectors onto one controller Refer to section 4 Address Settings for further information on how to select addresses for each detector...

Страница 5: ...abled panel The reference table can be viewed below addresses 127 254 relate only to Soteria When only one detector is connected it will appear on the address set on the DIP switch When there are two...

Страница 6: ...6...

Страница 7: ...The symbol in this guide is used to represent the number of the Detector currently selected 1 or 2 5 Apply power Commissioned system Detectors have been found but the selected Detector is not aligned...

Страница 8: ...Engineering Menu 7 Find Detectors 60 seconds Press to enable Found Detectors at any point during 60s countdown Any unused Detector channels are switched off Press to re scan if number is incorrect Thi...

Страница 9: ...ign Laser targeting and Home so it is recommended to leave the system set to Hi A if the current is available 8 Select Power Mode 9 Select Detector Select Detector to be accessed All Detectors need to...

Страница 10: ...Press or to turn off the LASER and return to the Settings menu Refer to Additional Detector Information for troubleshooting if LASER is not visible LASER RADIATION AVOID DIRECT EYE EXPOSURE POWER OUT...

Страница 11: ...S 01 is displayed uncover the Reflector and leave uncovered then press Repeat Steps 8 to 12 for any other Detectors found during the Find process 13 Set 0 100 Calibrate 14 System is Aligned Green LED...

Страница 12: ...The System Controller will signal Fault back to the Fire Control Panel after the delay to fault has expired 10s default Detector Fire LED Test Detector will signal Fire System Controller will stay Nor...

Страница 13: ...wn keys Press to accept setting EN Approved Sensitivity Ranges Analogue value 48 will be transmitted when the signal strength falls below a certain value this value is based on being 2 3 between 100 a...

Страница 14: ...l be transmitted if test successful 2 Alarm LED 2 Illuminate red fire LED on controller and detector Analogue Value Name Description 0 Microprocessor fault Internal communications fault within control...

Страница 15: ...uld take place on that Detector The system should be isolated from the Fire Control Panel before cleaning takes place After cleaning verify that the system is operating normally If the Signal Strength...

Страница 16: ...og entries Press tick when prompted by SurE To access the event log press tick on the Event Logger icon when the relevant detector is highlighted Event Code Event Number 01 is the most recent event 02...

Страница 17: ...ed prior to the most recent power cycle Duration of event will be displayed if the event is still occurring or if a power cycle occurred while the event was in progress or if there is no duration asso...

Страница 18: ...d allows the user to move the beam 1 Start Auto Alignment and press after two seconds to exit this will maximise infrared power 2 Select Hand alignment 3 Use to steer the beam until the signal strengt...

Страница 19: ...is pointing use Home Position to automatically steer the infrared beam to approximately the centre of its range of movement Press or to exit this function This will take up to 3 minutes to complete W...

Страница 20: ...technical assistance E 26 Internal controller fault Refer to manufacturer for technical assistance E 30 Isolator Active Isolator within the controller has activated Amber fault LEDs will also flash E...

Страница 21: ...Detector and Reflector 8 100 m Maximum angular misalignment of Detector 0 3 Deg Maximum angular misalignment of Reflector 5 Deg Maximum angular movement of Detector head 3 5 Deg Optical wavelength 850...

Страница 22: ...municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For...