background image

UNBOXING

•  When unboxing the output module you will find the unit and its lid.
•  This comes with pre-formed mounting holes to drill out and mount the backbox.
•  Securing screws are supplied for the lid.
•  A resistor pack is supplied for the monitored load connection (10KΩ  R      ).

For more information, please refer to the user manual. Available on apollo-fire.co.uk 

IMPORTANT TO CONSIDER

When mounting a wireless device, a comprehensive radio survey 
should have been carried out to establish the location that provides
the best coverage and optimum reach. Taking into consideration the building 
structure and materials, the survey identifies the wireless infrastructure
required and product locations for optimum performance, identifying
any factor that could prevent radio integrity.

Avoid fixing or mounting the unit close to the following: 
• Equipment that utilises large electrical currents
• Large metal objects or structures 
• Fluorescent lighting fittings 
• Metal ceiling structures 
• IT cabling.

Keep 2 meters minimum spacing between other wireless equipment
in the area to avoid signal interference.

EN54 approved environmental temperature range is -10°C to +55°C

INSIDE THE BOX

• 1 x Output Module 

• 2 x CR123A batteries

• 4 x Securing screws 

• 1 x Resistor pack 

• 1 x Quick start guide

MOUNTING STEPS

The Output Module is designed to meet IP65 rating, suitable for external mounting. 

Proceed as follows to complete the device installation. 

Remove the lid from the backbox, removing the screws 

on the corners.

1

3

2

4

BATTERY

COMPARTMENTS

• Remove the appropriate knock-out on the underside or lower

rear of the casing, install the M16/20 IP-rated gland. 

• Note: pay attention to avoid damages to the PCB, while

removing the knock-out, or remove it before starting.

• Ensure the switch on the PCB is in position ON.

• Fit the 2x CR123A batteries ensuring you have checked

they are the correct way round observing the polarity 

indications on the PCB.

• The LED will signal 4 times red.

• Move the switch on the PCB to position 1. The LED will blink

few seconds green and then signal alternatively green/red 

4 times. 

LED

DIP 

SWITCH

ON     1  

• To retain IP-rating, please ensure you use the outer holes

on the casing.

• Using a pencil, mark through the outer holes on the desired

surface you will attach the unit to.

• Using a suitable-sized drill bit (6 mm) drill the marked screw

points on your chosen surface.

• Ensure you use the correct fixings for the type of surface 

you are mounting to.

• Screw the backbox to the desired surface using all fixing holes

and appropriate-sized roundhead screws (not countersunk).

EOL

RW1700-052APO

REACH Output Module

QUICK START GUIDE

+

-

+

-

RW1700-052APO

Scan QR code

for full user manual

Apollo Fire Detectors Ltd. 36 Brookside Road, Havant, Hampshire, United Kingdom, PO9 1JR
T: +44 (0)23 9244 2706 - E: techsales@apollo-fire.com - W: www.apollo-fire.co.uk

RW_QSG_MODULE_OUTPUT_REV_A.1

THE BOX

Product Part Number

Product Description

RW1700-052APO

REACH Output Module

Отзывы: