• Refit the lid to the backbox, using the supplied screws. 

.

6

5

+

Unsupervised relay

switch output

WIRING EXAMPLE FOR THE RELAY SWITCH OUTPUT 

• Ensure the device connected to the unit is not drawing 

more than 2 A at 30V (no 220 VAC). Drawing too much 

current through the output relay or connecting mains

voltage could possibly damage the unit and void warranty.

Note: install a properly fire-rated cable (according 

to national code of practice) between the third-party 

device and the output module.

R

EOL

Supervised relay switch 

output (needs polarised load)

V

EXTERNAL

DEVICE

-     +

- +

-     +

- +

port B

input

port A

output

power supply

V

+

External

device

R

EOL

WIRING EXAMPLE FOR 100MA/12 VDC OR 50 MA/24 

VDC EXTERNAL DEVICE DRIVING CAPABILITY 

• The 10KΩ R        resistor monitors whether the cable

has been damaged or the connection is no longer available.

• If you fail to install these resistors correctly the device will

not operate as intended. 

-     +

- +

R

EOL

R

EOL 

10 KΩ

external

device

-     +

- +

EOL

R

EOL 

10 KΩ

RW1700-052APO

REACH Output Module

QUICK START GUIDE

Apollo Fire Detectors Ltd. 36 Brookside Road, Havant, Hampshire, United Kingdom, PO9 1JR
T: +44 (0)23 9244 2706 - E: techsales@apollo-fire.com - W: www.apollo-fire.co.uk

RW_QSG_MODULE_OUTPUT_REV_A.1