Technical Data

Operating voltage 

18–28V DC

Maximum Loop Current Consumption at 24V

 

Switch-on surge 

1.2mA for <1 sec

 Quiescent 

330

μ

A

 Sounder 

operated 

5mA

 

Sounder Beacon Operated: 92/100dB(A)  8/9mA

Sound output 

100dB(A)

IP rating - Type A 

21C

IP rating - Type B 

66C

For sound pressure levels measured to EN54–3 see document PP2203 and for isolator operation 

information see document PP2090, both available on request.

IP rating

To maintain the integrity of the enclosure it is essential that suitable IP rated cable glands be 

used.

Individual Address Setting

The address of the Multi-tone Open-area Alarm Devices is set using seven segments of the 

eight-segment DIL switch. The eighth seg ment is used to adjust the volume output. Segments 

1-7 of the switch are set to “0” (ON) or “1”, using a small screwdriver or similar tool. A complete 

list of address settings is shown below. 

 

 

DIL switch 

 

DIL switch 

 

DIL switch 

 

DIL switch 

 

DIL switch

  setting 

 setting 

  setting 

 setting 

 setting

 

addr 

1234567 addr 

1234567 addr 

1234567 addr 

1234567 addr 

1234567

 

 

1000000 11 

1101000 21 

1010100 31 

1111100 41 

1001010

 

 

0100000 12 

0011000 22 

0110100 32 

0000010 42 

0101010

 

 

1100000 13 

1011000 23 

1110100 33 

1000010 43 

1101010

 

 

0010000 14 

0111000 24 

0001100 34 

0100010 44 

0011010

 

 

1010000 15 

1111000 25 

1001100 35 

1100010 45 

1011010

 

 

0110000 16 

0000100 26 

0101100 36 

0010010 46 

0111010

 

 

1110000 17 

1000100 27 

1101100 37 

1010010 47 

1111010

 

 

0001000 18 

0100100 28 

0011100 38 

0110010 48 

0000110

 

 

1001000 19 

1100100 29 

1011100 39 

1110010 49 

1000110

 

10 

0101000 20 

0010100 30 

0111100 40 

0001010 50 

0100110

 

51 1100110 

 

61 1011110 

71  1110001 

81 1000101 

91 1101101

 

52 

0010110 62 

0111110 72 

0001001 82 

0100101 92 

0011101

 

53 1010110 

 

63 1111110 

73  1001001 

83 1100101 

93 1011101

 

54 0110110 

 

64 0000001 

74  0101001 

84 0010101 

94 0111101

 

 

55 

1110110 65 

1000001 75 

1101001 85 

1010101 95 

1111101

 

 

56 

0001110 66 

0100001 76 

0011001 86 

0110101 96 

0000011

 

57 

1001110 67 

1100001 77 

1011001 87 

1110101 97 

1000011

 

58 

0101110 68 

0010001 78 

0111001 88 

0001101 98 

0100011

 

59 

1101110 69 

1010001 79 

1111001 89 

1001101 99 

1100011

 

60 0011110 

70 0110001 

80  0000101 

90 0101101 

100 0010011

 

101 

1010011 106 

0101011 111 

1111011 116 

0010111 121 

1001111

 

102 

0110011 107 

1101011 112 

0000111 117 

1010111 122 

0101111

 

103 

1110011 108 

0011011 113 

1000111 118 

0110111 123 

1101111

 

104 

0001011 109 

1011011 114 

0100111 119 

1110111 124 

0011111

 

105 

1001011 110 

0111011 115 

1100111 120 

0001111 125 

1011111

   

  

   

  

126 0111111

Fig 3. Example of address and tone setting 

Tone Setting

5

6

Tone

0

0

Standard

1

0

Slow  Whoop

0

1

DIN

1

1

Standard

© Apollo Fire Detectors Limited 2006-9/JDR/TP

1

2

3

4

5

6

7

8

O
N

1

2

3

4

5

6

O
N

Individual Address

Vol

Group 
Address

Tone

0 1 1 1

0

1

0

1

1

1

0

1

Individual 
Address 78 =

Group
Address 113 =

Tone setting 
Standard =

Example:

Volume
92dB =

0  0

ON = 0

Switch

MOUNTING HOLES

FOR WEATHERPROOF 

INSTALLATION

USE IP RATED CABLE GLANDS

©Apollo Fire Detectors Limited 2012/EKC

ENSURE THAT THERE IS A GOOD SEAL BETWEEN 

THE BACK BOX AND THE UNIT, THE MOUNTING SURFACE

SHOULD BE AS FLAT AS POSSIBLE

ALIGN MATING MARKS

L1(-)

Screen

L1(-)

Screen

L2(+)

L2(+)

L2(+)

L1(-)

L1(-)
L2(+)

12345678

O

N

123456

O

N

Individual Address

V

ol

Group 

Address

T

one

ON = 0

© Apollo Fire Detectors Limited 2006-9/JDR/JLC/TP/EKC

Fig 2. Wiring

Fig 1. Mounting Type B weatherproof products

www.acornfiresecurity.com

www.acornfiresecurity.com