3.4
Input and output power cords and protective earth ground installation
1.
Notes for installation
1)
The UPS must be installed in a location with good ventilation, far away from water,
inflammable gas and corrosive agents.
2)
Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least
0.5m of space on each side.
3)
Condensation to water drops may occur if the UPS is unpacked in a very low
temperature environment. In this case it is necessary to wait until t he UPS is fully dried
inside out before proceeding installation and use. Otherwise there are hazards of
electric shock.
2.
Installation
Installation and wiring must be performed in accordance with the local electric code and
the following instructions by professional personnel.
For safety, please cut off the mains power switch before installation. The battery breaker
also needs to be cut off if it is a long backup time model.
1)
Open the terminal block cover located on the rear panel of the UPS, please refer
to the appearance diagram.
2)
For Plus III-6KLRB UPS, it is recommended to select the UL1015 10AWG(6mm
2
)
wire or other insulated wire which complies with AWG Standard for the UPS input
and output wirings.
3)
For PlusIII-10KLRB, it is recommended to select the UL1015 8AWG(10mm
2
) wire or
other insulated wire which complies with AWG Standard for the UPS input and output
wirings
Note: Do not use the wall receptacle as the input power source for the UPS, as its
rated current is less than the UPS’s maximum input current. Otherwise the
receptacle may be burned and destroyed.
4)
Connect the input and output wires to the corresponding input and output
terminals according to the following diagram.