5 DTR. LI-24
(ENG
)
5.4.3. -
Power supply with the rectangular characteristics
Ui = 24V Ii = 0,05A Pi = 1,20W
Ta
75
C and T4
Power supply with the rectangular characteristics means that the intrinsically safe supplier voltage does not
change until the current limiter is activated.
Fig. 4 The supplying principle with a source of rectangular characteristics.
The power supplier with rectangular characteristics usually has the “ib” protection level. Each transmitter
power
ed from such supplier is also the intrinsically safe device with “ib” protection level.
5.5. Assembly recommendations
5.5.1.
General recommendations
The LI-24 Transmitter connection should be made in accordance with fig. 5. The transmitter should
be assembled at horizontal rail in the connecting boxes. Should be kept min distance 50mm
between the terminals and the conducted circuit accessories galvanic separated. If the distances
aren’t kept is necessary to apply the isolated or grounded conducted partition. The next electrical
installations in the box should be assembled in the way encroaching of separation rules between
intrinsically safe circuits and non intrinsically safe circuits. At the boxes and at the cases should be
put the signs informing about assembled devices and about leading out places. Essential for the
proper transmitter working with the outside part measuring system is connecting of transmitter with
regard to the intrinsically rules (EN 600079-25) as well as the maintenance of entrance / exit
parameters.
It is not allowed to repair or otherwise interfere with the transmitter’s electrical circuits in any
way. Assessment of damage and any necessary repairs may be carried out only by the
manufacturer or by a firm authorized by the manufacturer.
5.5.2.Special conditions for safe use according to FTZU 08 and ATEX 0160X Certificates.
When installed as category G equipment, the unit must be mounted inside of enclosure or
under the cover complying with requirements of EN 600079-0:2009, clause 7.4.2 or 8.1.2 when
these are made of plastic and light alloy respectively.
When installed as category M1 or M2 equipment the unit must be mounted inside of enclosure
which affords it a degree of protection of at least IP 54. Non metallic enclosures must comply
with requirements of EN 60079-0:2009, clause 7.4.2. Light alloy enclosures are not allowed.