• Adjustment Procedure
Fundamentally, the model VBL needs no adjustments. But adjust the
detecting sensitivity for:
• Fine powders
• Highly fluidized powders
• Sticky and buildup materials.
• Improper adjustment
Powder Detecting Sensitivity
The adjustment of the detecting
sensitivity depends on bulk density,
fluidity, buildups concentrate features and
so on. Accordingly, the data written below
will be nearly general. See the table below:
Polycarbonate pellet (PC pellet), salt,
powdered coffee’s detecting sensitivities
are written below for your reference.
Detecting Levels
Standard
Super High
Powder Names
Bulk Density
Sensitivity
Sensitivity
Salt
1.4
Less than 20 mm
Less than 20 mm
PC Pellet
0.7
Less than 40 mm
Less than 10 mm
Powdered Coffee
0.26
Undetectable
Less than 80 mm
Standard Sensitivity: The sensitivity when shipping
Super High Sensitivity: The most high detecting sensitivity.