7.4. E-ITN 10
MOUNTING
PLACE
ON
SEGMENTED
AND
PANEL
RADIATORS
Place with suitable relation between the displayed value and the heat emission of the radiator over a
sufficiently operating range must be determined for allocator installation. Place of installation must be
determined according to the unified criteria in single billing (accounting) unit. E-ITN 10 installation must be
permanently protected against manipulation.
Warning: Failure to comply mounting procedure may result allocator malfunction!
7.4.1. Vertical position:
Option 1. - New installation:
Install E-ITN 10 into 75% of the total radiator height (measured from bottom) – in relation to lower
hole of back plate. If the height of the radiator is less than 400mm install allocator to 50 % of total
height. Variations of the mounting points height must not exceed ± 10 mm.
Option 2. - Installation instead evaporating allocators RTN 01, RTN 02:
E-ITN 10 into 75-80% of the total radiator height (measured from bottom) – in relation to lower hole
of back plate. If the height of the radiator is less than 400mm install allocator to 50 % of total height.
Place of installation must be determined according to the unified criteria in single billing unit (e.g.
75 % of radiator height). Variations of the mounting points height must not exceed ± 10 mm.
7.4.2. Horizontal position:
For both variants of vertical installation, place E-ITN 10 into the half of length L. In cause of odd number of
the spaces, place E-ITN 10 into the gap closer to the end of the radiator, i.e. at radiator with 10 segments
between 5. and 6. segment. On radiators with length L>2000 mm or radiators with excessive nominal output
install two E-ITN 10.
21 / 39
Illustration 5: E-ITN 10, RTN 01, RTN 02 location on segmented and panel radiators