FT – A1, FT – A2, FT –B

HEAT DETECTORS

The detectors comply with EN 54-5:2003.

   Compliance of the detectors with the type and class appear in Table 1.

Table  1

Model

Type

EN 54-5:2003 class

FT – A1 heat detector

Fixed temperature

1

FT – A2 heat detector

Fixed temperature

2

FT – B heat detector

Fixed temperature

The following abbreviations apply in the manual.
AL – alarm loop;
CP – control panel.

1 PURPOSE

1.1 The FT – A1 (FT – A2, FT –B) heat detectors are designed to control ambient temperature indoors.

      1.2 When exceeding the threshold ambient temperature value in guarded premises the detector forms
the alarm signal for CP.

1.3 The Fire mode is indicated with 2 red optical indicators.
1.4 The indication of Fire mode depends on the AL type the detector is connected to. The indication in

DC AL is made with continuous light of optical indicators, and in AC AL – with flashing.

1.5 The detector indicates standby mode with short-term flashes of  the red LED.
1.6 The detector is intended to operate all day long with CP  by 2-wire AL with rated loop voltage

12/24V.

1.7 The MUSH-2 or MUSH-3 modules should be applied to connect detectors to 4-wire CP. .

2 TECHNICAL SPECIFICATIONS

2.1 Static response temperature range, ° :
- FT – A1

54 – 65

- FT – A2

54 – 70

- FT – 

69 – 85

2.2 Supply voltage range, V                                                              9 - 30
2.3 Standby current consumption at 30 V max,                                0,1
2.4 Fire current consumption

set by external resistor in value range

, m       5 - 20

2.5 Internal resistance in Fire mode at 20 mA, Ohm                         500

2.6 Dimensions, mm

85 × 33

2.7 Weight, g                                                                                  50

            2.8 Average lifespan,   years                                                            10

Содержание FT-A1

Страница 1: ...ed optical indicators 1 4 The indication of Fire mode depends on the AL type the detector is connected to The indication in DC AL is made with continuous light of optical indicators and in AC AL with flashing 1 5 The detector indicates standby mode with short term flashes of the red LED 1 6 The detector is intended to operate all day long with CP by 2 wire AL with rated loop voltage 12 24V 1 7 The...

Страница 2: ...to the place of installation using two self tapping screws 20 mm2 not supplied with the detector 5 4 Connect AL to the detector as per Figure 3 Figure 7 Tighten screws Check the reliability of the connection Close the detector head having aligned the marks on the base and on the head Twist the head clockwise relative to the base as far as it will go 5 5 Connect AL with detectors to a control panel...

Страница 3: ...removed the guarantee term is prolonged for the while detectors were not in use because of faults Figure 1 APPEARANCE AND DIMENSIONS Figure 2 DESIGN AND INSTALLATION DIMENSION 1 Screw joints for AL wires connection 2 Mounting holes 3 Red LED 4 Thermal element 5 Input slots for AL conductors The numbers of contacts and places for connection of end of line and limiting resistors for DC AL housing ar...

Страница 4: ...the detector Resistors value is specified by control panel manufacturer Feasible values 24V EOL resistor 2 4 3 9 kOhm CLR 0 68 3 6 kOhm 12 V EOL resistor 1 2 2 kOhm CLR 0 1 1 5 kOhm Figure 4 WIRING DIAGRAM TO AC CONTROL PANEL Resistors values are specified by control panel manufacturer Diode VD 1N4148 ...

Страница 5: ...hm Figure 6 WIRING DIAGRAM FOR CONNECTION OF DETECTORS TO 4 WIRE DC AL THROUGH MUSH 3 MODULE EOLRAL and CLRAL from 1 to 5 kOhm are specified by control panel manufacturer CLR 680 Ohm EOL resistor 2 7 kOhm Figure 7 WIRING DIAGRAM FOR CONNECTION OF DETECTORS TO 4 WIRE AC AL THROUGH MUSH 3 MODULE EOLRAL and CLRAL from 1 to 5 kOhm are specified by control panel manufacturer CLR 680 Ohm EOL resistor 2 ...

Отзывы: