25
TC5-2V2SA.rev.05
TC5-2V2SA
•
At Set Point + Bandwidth 1 + Stage 2 Bandwidth 2
: stage
2 fans reach maximum speed.
•
At Set Point + Bandwidth 1 + Stage 2 Bandwidth 2 + Diff.
3
: stage 3 fans start running.
•
At Set Point + Bandwidth 1 + Stage 2 Bandwidth 2 + Diff.
3 + Diff. 4
: stage 4 fans start running.
If the room temperature falls:
•
At Set Point + Bandwidth 1 + Stage 2 Bandwidth 2 +
Diff. 3
: stage 4 fans return to a stop.
•
At Set Point + Bandwidth 1 + Stage 2 Bandwidth 2
:
stage 3 fans return to a stop; stage 2 fans start decreasing in speed
as the temperature decreases.
•
At Set Point + Bandwidth 1 + Stage 2 Offset
: the stage 2 fans
return to a stop.
•
At Set Point + Bandwidth 1:
Stage 1 fans start decreasing in speed
as the temperature decreases.
•
At Set Point:
the Stage 1 fans reach minimum speed.
•
Below the Set Point
: the stage 1 fans stop operating continuously
and operate according to the minimum ventilation cycle at minimum
speed.