28
TC5-1V6SA.rev.06
TC5-1V6SA
This feature also applies when the minimum ventilation speed curve is
activated. Note that for the compensation to take place, the compensation
feature must be activated by the user. When a compensation is applied to
the minimum speed, the compensation pilot light turns on.
Relative
Humidity
Relative
Humidity
Set Point
Stage 1
Min. Speed
Compensation begins
0%
100%
Normal
Min. Speed
Compensation %
10 %
H
UMIDITY COMPENSATION
The stage 1 minimum speed can be adjusted automatically as a function of
relative humidity. As humidity increases, the stage 1 minimum speed in-
creases proportionally to compensate for the change. At humidity levels at
or below the humidity set point, stage 1 minimum speed is equal to the
normal uncompensated speed. The user specifies the percentage increase
in minimum speed for a relative humidity equal to the humidity set point +
10%. For example, if the minimum speed is 40% and the compensation
adjustment is 30%, the minimum speed will be adjusted to 70% of full
speed when the humidity rises 10% above the humidity set point. In addi-
tion to adjusting the minimum speed, the humidity compensation feature
also changes the operation of the minimum ventilation cycle: if the control-
ler is operating in minimum ventilation mode when the relative humidity
exceeds the humidity set point, the minimum ventilation fans are operated
continuously rather than cycled.