12
TC5-1V6SA.rev.06
TC5-1V6SA
To identify the defective probe:
n
Set the selection knob to
ROOM
TEMPERATURE
. The room tem-
perature is displayed.
n
Press the push-button. If the
probe connected to input # 1 and
supplied with the controller is not
defective, the letters"
PR1
" are dis-
played, alternating with the on/off
state of the probe and the tem-
perature measured by the probe.
If the probe is defective, the let-
ters "
PR1
" are displayed, alternat-
ing with the state of the probe and
the letter "
P
".
For each additional probe connected to the controller:
n
Press the push-button once again. If the probe is not defective, the
letters "
PR#
" (where # is the number of the input to which the probe is
connected) are displayed, alternating with the on/off state of the probe
and the temperature measured by the probe. If the probe is defective,
the letters "
PR#
" are displayed, alternating with the on/off state of the
probe and the letter "
P
".
STAGE 1
(T )