background image

Ozone Detector c/w

O3TH

Dec.11

    Automatikprodukter

Indicator for Temperature/Humidity

Technical Data

Gas

 Ozone  O3

Detection principle

 Semiconductor ozone gas senso

Warm up time

First time

96 hours

Operational

1 hour

Mounting height

300mm above floor

O3 Measuring range

10 - 1000ppb

Relay output

One dry contact output

Current

2A  switching (resistance load)

Ranges

Four to be selected to control

the relay turn-on/ turn-off

Analogue output

0-10Vdc linearzed

Output resolution

10Bit

Temperature

measurement 0-+50C

settings

5-+45C

Humidity

measurement 0-99% RH

settings

5-+95%RH

 

Serial Interface RS485

Rate

9600/14400/19200 (default)

28800, 38400bps programmable

selection¨

Base address 3 indepedent

Nodes

Max 31 in a network

Power supply

24Vac/dc

Display resolution

1 ppb

Accuracy

+/- 10 ppb + 20% of reading

Expected lifetime

More than 5 years normal opera

ting environmontal

Humidity range

5-95% rH non-condensing

Operating range

5 up to +45C

Protection Class

IP30  Fire proof ABS material

Features

-

Real time detection of ambient ozone gas level

-

Full time indicate O3 level

-

Wall mount with LCD display

-

Temperature & humidity detection

-

The on/off output for control a fan, O3 generator or

an alarm

-

Provide an analogue output with linearover full
range output

-

Adressing for RS485 mode. eg. Modbus

Description

O3 detector including digital measurement value processing
and temperature compensation for the continuous
monotoring of ozone concentration in the ambient air.

For the detection of ozone within a wide range of industrial
and commercial applications.

     

O3TH

Ordering Codes

O3TH 2      

   Ozone Detector 10 - 1000ppb (0,01 -- 1ppm)

                       c/w one relay output

O3TH 2M      

Ozone Detector 10 - 1000ppb (0,01 -- 1ppm)

                    c/w one relay output and  Modbus

O3TH 12      

 Ozone Detector 10 - 1000ppb (0,01 -- 1ppm)

                    c/w one relay and analogue output

O3TH 12M    

Ozone Detector 10 - 1000ppb (0,01 -- 1ppm)

                    c/w one relay and analogue output, Modbus

Alarm Units

AAW 24          

Warning Siren 24Vdc 98-108dB

AAW 230        

Warning Siren 230Vac 98-108dB

OA 24              

Flash Light 24Vdc red

OAW 24          

Combined Warning Siren and Flash Light 24Vdc

OAW 230       

Combined Warning Siren and Flash Light 230V

Warning Sign

Gasalarm       

Warning Sign 

¨GASALARM¨ 

24Vac/dc

Содержание O3TH

Страница 1: ...Features Real time detection of ambient ozone gas level Full time indicate O3 level Wall mount with LCD display Temperature humidity detection The on off output for control a fan O3 generator or an a...

Страница 2: ...t off power first Simualtaneously depress the 2 clips on either of the sides of the detector gently with your nails or other unsharp tools then move off the face part 2 Mount the detector on the place...

Страница 3: ...range is 10 1000ppb accuracy 1ppb and setting range is 40 1000ppb its maximum measurement limited is 2000ppb 3 Turn on Turn on the monitor by press power for 2 seconds Temperature measurement displays...

Страница 4: ...p on press switch key for about 20 seconds until X10 symbol disappearing It indicates the zero has no any calibration it s still 0 Note Auto zero calibration can be done only when ozone measurement is...

Страница 5: ...tion 1 9600bps 2 14400bps 3 3 19200bps 4 28800bps 5 38400bps RESET Put the DIP1 to ON and press switch key for about 25 seconds until the detector is off then all the setting return to the default Ann...

Страница 6: ...is finished 6 Now go to demarcation point 2 put the controller in sample gas 7 Write down the un twinkling point of X2 and Y2 8 Press switch to the second demarcation point N 2 9 Press tangent down o...

Страница 7: ...key for about 25 seconds until the monitor is off then all the settings return to the default If warm up time is less than 3 months before leaving factory then do emendation as the second row of the...

Страница 8: ...ent Controller Placement The Ozone Detector has been designed to measure the ambient concentration of ozone The controller must not be placed directly in an ozone stream For indoor local area monitori...

Отзывы: